Toshiba RAS-B10EKVP-E, RAS-M13EKCVP-E, RAS-M18EACV-E, RAS-M14EACV-E Installation/Service Tools, 62

Models: RAS-B10EKVP-E RAS-M14EAV-E RAS-B13EKVP-E RAS-M18EAV-E RAS-M10EKCVP-E RAS-M16EKCVP-E RAS-M14EACV-E RAS-M18EACV-E RAS-M13EKCVP-E

1 136
Download 136 pages 38.01 Kb
Page 62
Image 62
Installation/Service Tools

Installation/Service Tools

Changes in the product and components

In air conditioners using R410A, in order to prevent any other refrigerant from being accidentally charged, the service port diameter size of the outdoor unit control valve (3 way valve) has been changed. (1/2 UNF 20 threads per inch)

In order to increase the pressure resisting strength of the refrigerant piping, flare processing diameter and opposing flare nuts sizes have been changed. (for copper pipes with nominal dimensions 1/2 and 5/8)

New tools for R410A

New tools for R410A

Applicable to R22 model

Changes

 

 

 

 

Gauge manifold

 

 

As the working pressure is high, it is impossible to measure

 

 

 

the working pressure using conventional gauges. In order to

 

 

 

prevent any other refrigerant from being charged, the port

 

 

 

diameters have been changed.

 

 

 

 

Charge hose

 

 

In order to increase pressure resisting strength, hose

 

 

 

materials and port sizes have been changed (to 1/2 UNF 20

 

 

 

threads per inch).

 

 

 

When purchasing a charge hose, be sure to confirm the

 

 

 

port size.

 

 

 

 

Electronic balance for refrigerant

 

 

As working pressure is high and gasification speed is fast, it

charging

 

 

is difficult to read the indicated value by means of charging

 

 

 

cylinder, as air bubbles occur.

 

 

 

 

Torque wrench

 

 

The size of opposing flare nuts have been increased.

(nominal dia. 1/2, 5/8)

 

 

Incidentally, a common wrench is used for nominal

 

 

 

diameters 1/4 and 3/8.

 

 

 

 

Flare tool (clutch type)

 

 

By increasing the clamp bar’s receiving hole size, strength

 

 

 

of spring in the tool has been improved.

 

 

 

 

Gauge for projection adjustment

 

Used when flare is made by using conventional flare tool.

 

 

 

 

Vacuum pump adapter

 

 

Connected to conventional vacuum pump. It is necessary to

 

 

 

use an adapter to prevent vacuum pump oil from flowing

 

 

 

back into the charge hose. The charge hose connecting

 

 

 

part has two ports — one fo r conventional refrigerant (7/16

 

 

 

UNF 20 threads per inch) and one for R410A. If the vacuum

 

 

 

pump oil (mineral) mixes with R410A a sludge may occur

 

 

 

and damage the equipment.

 

 

 

 

Gas leakage detector

 

 

Exclusive for HFC refrigerant.

 

 

 

 

Incidentally, the “refrigerant cylinder” comes with the refrigerant designation (R410A) and protector coating in the U.S’s ARI specified rose color (ARI color code: PMS 507).

Also, the “charge port and packing for refrigerant cylinder” requires 1/2 UNF 20 threads per inch corresponding to the chargehose’s port size.

– 62 –

Page 62
Image 62
Toshiba RAS-B10EKVP-E, RAS-M13EKCVP-E, RAS-M18EACV-E, RAS-M14EACV-E, RAS-M16EKCVP-E Installation/Service Tools, 62