Toshiba RAS-M14EACV-E, RAS-M18EACV-E Troubleshooting, 92, How to check output of the air purifier

Models: RAS-B10EKVP-E RAS-M14EAV-E RAS-B13EKVP-E RAS-M18EAV-E RAS-M10EKCVP-E RAS-M16EKCVP-E RAS-M14EACV-E RAS-M18EACV-E RAS-M13EKCVP-E

1 136
Download 136 pages 38.01 Kb
Page 92
Image 92
11-7. Troubleshooting

11-7. Troubleshooting

11-7-1. How to Check Whether the Air Purifier is Good or Not

Primary check

Turn off the power breaker once, and turn on again after 10 seconds.

Does the OPERATION indicator flash?

How to check output of the air purifier YES

Turn off the power breaker and remove CN34 (Micro switch connector). Short-circuit between 1 and 2 pin of CN34 at PC side, and turn on the power breaker after 10 seconds.

Is DC12V applied

between 1 (Red/DC12V) and (Brown/GND) of CN1 of the high-voltage generator?

<Caution on High Voltage!!> YES

Is there conduction of

micro-switch connector under OFF status of the micro-switch (Front panel opened)?

– 92 – NO

Is there conduction of

micro-switch connector under ON status of the micro-switch (Front panel closed)?

NO

NO

Is DC12V applied

NO

between 1 (+) and 2 (–)

 

of CN33 of the main

 

 

P.C. board (MCC5020)?

 

 

 

 

 

YES

 

 

YES

Micro-switch is stuck

 

 

 

NO

Micro-switch malfunction

To item “Power supply is not turned on”

Manual backgroundManual background Replace the main P.C. board (MCC5020)

Replace micro-switch.

• Conduction check of micro-switch

Manual background YES

1)Check operation while short-circuiting CN34 of the main P.C. board.

2)Perform air purifying operation by the remote controller.

In this time, check that the remote controller is in status which is shortened by time on the reactivation preventive timer and all display indicators go on for approx. 3 seconds

when a signal is received.

( If time on the reactivation preventive timer is not shortened,) the high-voltage is not applied to electrode of the air purifier for approx. 1 hour.

While the air purifier operates, check that the fan speed [AUTO] is not displayed. (Because the power ON/OFF is controlled on the program)

3)Be sure not to touch the electric dust collector, ionizer, or ionized wire unit with the human body.

Manual background Push the switch

ON ON

Release the switch

OFF

Tester

Operation check

 

Does the indoor fan rotate?

 

NO

 

 

 

 

 

 

 

 

 

 

 

To item “Only indoor fan does not operate”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Does the PURE indicator (Blue) or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace the main P.C. board (MCC5020).

 

 

the FILTER indicator (Orange) go on?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

Is DC-5V to DC-10V

 

 

 

 

How to check output of the air purifier

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Does the PURE indicator

 

NO

 

 

applied between

NO

 

 

 

go off within 2 seconds after

 

 

 

4 (Brown/Negative voltage)

 

 

<Caution on High Voltage!!>

 

it was ON, and does the FILTER

 

 

 

 

 

 

 

and 2 (Brown/GND)

 

 

 

 

 

 

 

 

 

 

 

indicator (Orange) go on?

 

 

 

 

 

 

 

 

of CN33 of the main

 

 

 

 

 

 

 

 

Collector

 

 

 

 

 

 

 

 

 

 

 

 

 

P.C. board?

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are the electric dust

NO

 

 

 

 

 

Dry the electric

 

 

 

 

 

 

 

 

 

 

 

 

 

 

collector and ionizer dried?

 

 

 

 

 

dust collector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Electrode check)

 

 

 

 

 

 

and ionizer.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ionizer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Referring to the right figure, check the

 

Be sure not to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

output

 

 

 

 

 

 

 

 

 

 

 

high-output voltage of the air filter unit.

 

come to contact

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(NOTE)

 

to the gray part

 

High-voltage

 

 

 

 

 

 

 

 

 

 

 

Use an exclusive high voltage tester;

 

or not to touch

 

 

 

 

 

 

 

 

 

 

 

 

otherwise the tester may be broken.

 

the ionized

 

tester

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cables.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

Refer to items, cleaning and check

 

 

 

 

 

 

 

Is output of the ionizer

NO

 

 

 

 

 

 

for the electric dust collector/ionizer/

 

 

 

 

approx. 4.0 kV to 4.8 kV?

Replace the high-voltage generator.

 

ionized wire units.

 

 

 

 

 

 

 

 

Is output of the collector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When the ionized wire is

 

 

 

 

 

 

 

 

approx. 3.0 kV to 3.8 kV?

 

 

 

 

 

 

 

 

 

 

 

disconnected or when dirt is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

( not cleaned even cleaned,

)

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

replace each unit.

 

 

 

 

 

 

 

 

Are the electric dust

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

collector/ionizer/ionized

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

NO

 

 

 

 

 

 

 

 

 

 

 

wire units dirty?

No trouble

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is an abnormal sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(cracking noise) heard

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

from the electrode?

 

 

 

 

 

 

 

 

 

 

– 92 –

Page 92
Image 92
Toshiba RAS-M14EACV-E Troubleshooting, 92, How to check output of the air purifier, <Caution on High Voltage!!>