– 42 –

Item

 

 

Operation flow and applicable data, etc.

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating operation

 

 

 

 

 

 

 

 

 

 

 

1) Operation is performed at the

 

 

TE

 

Zone A:

Zone A: The fan revolutions are

MAX revolutions shown in the

 

 

 

 

 

 

left tables for 3 minutes after

 

 

 

 

 

 

 

 

 

 

 

 

 

decreased by 100 rpm

compressor operation starts and

 

 

 

 

 

 

 

 

 

every 20 seconds (to the

for 1 minute after defrosting

 

 

 

 

 

 

 

 

 

MIN revolutions).

 

 

 

operation ends.

 

 

 

 

 

 

 

 

 

When Zone A operation

2) Following 1) above, operation is

 

 

 

 

 

 

 

 

 

continues for 5 minutes,

 

 

 

 

 

 

 

 

 

performed at the outdoor unit fan

 

 

 

 

 

 

 

 

 

the compressor is stopped

 

 

 

 

 

 

 

 

 

revolutions shown in the left

 

 

 

 

 

 

 

 

 

and then restarted.

 

 

24°C

 

 

 

 

 

 

tables according to the outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Zone B:

Zone B: The fan revolutions are

heatexchanger sensor (TE

 

 

 

 

 

 

 

 

sensor) temperature.

 

 

 

 

 

 

 

 

 

decreased by 100 rpm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

every 20 seconds (to the

 

 

 

21°C

 

 

 

 

 

 

MIN revolutions).

 

 

 

 

 

 

 

 

 

Zone C: The fan revolutions are

 

 

 

Zone C:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

decreased by 50 rpm

 

 

 

 

 

 

 

 

 

 

every 20 seconds (to the

 

 

 

18°C

 

 

 

 

 

 

MIN revolutions).

 

 

 

 

 

 

 

 

 

Zone D: The fan revolutions are

 

 

 

Zone D:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

maintained at the current

 

 

 

15°C

 

 

 

 

 

 

revolutions.

 

 

 

 

 

 

 

 

 

 

Zone E: The fan revolutions are

 

 

 

Zone E:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

increased by 50 rpm

 

 

 

 

 

 

 

 

 

 

every 20 seconds (to the

 

 

 

 

 

 

 

 

 

 

MAX revolutions).

 

 

 

 

 

 

RAS-M18EAV-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor revolution(rps)

 

 

~20

 

~48

 

48~

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan revolution

 

MIN

 

MAX

MIN

 

MAX

MIN

 

MAX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal

 

To>10˚C

 

250

 

400

250

 

600

250

 

700

 

 

 

 

 

5.5<To10

 

250

 

400

250

 

700

250

 

750

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-5<To5.5

 

250

 

600

250

 

750

250

 

800

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To-5

 

250

 

600

250

 

750

250

 

800

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To>10˚C

 

250

 

400

250

 

500

250

 

600

 

 

 

 

econo

 

5.5<To10

 

250

 

400

250

 

600

250

 

700

 

 

 

 

operation

 

 

250

 

600

250

 

700

250

 

700

 

 

 

 

 

 

 

-5<To 5.5

 

 

 

 

 

 

 

 

 

 

 

To-5

 

250

 

600

250

 

700

250

 

700

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To is abnormal

 

 

250

 

400

250

 

700

250

 

750

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To:outdoor sensor temp. (˚C)

 

 

 

 

 

 

 

 

 

 

RAS-M14EAV-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor revolution(rps)

 

 

~20

 

~60

 

60~

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan revolution

 

MIN

 

MAX

MIN

 

MAX

MIN

 

MAX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal

 

To>10˚C

 

250

 

400

250

 

600

250

 

700

 

 

 

 

 

5.5<To10

 

250

 

400

250

 

700

250

 

750

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-5<To5.5

 

250

 

600

250

 

750

250

 

800

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To-5

 

250

 

600

250

 

750

250

 

800

 

 

 

 

 

 

 

To>10˚C

 

250

 

400

250

 

500

250

 

600

 

 

 

 

econo

 

5.5<To10

 

250

 

400

250

 

600

250

 

700

 

 

 

 

operation

 

-5<To5.5

 

250

 

600

250

 

700

250

 

700

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To-5

 

250

 

600

250

 

700

250

 

700

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To is abnormal

 

 

250

 

400

250

 

700

250

 

750

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To:outdoor sensor temp. (˚C)

– 42 –