Toshiba RAS-M16EKCVP-E, RAS-M13EKCVP-E, RAS-M18EACV-E, RAS-M14EACV-E Operation Data, 30

Models: RAS-B10EKVP-E RAS-M14EAV-E RAS-B13EKVP-E RAS-M18EAV-E RAS-M10EKCVP-E RAS-M16EKCVP-E RAS-M14EACV-E RAS-M18EACV-E RAS-M13EKCVP-E

1 136
Download 136 pages 38.01 Kb
Page 30
Image 30
7-2. Operation Data

7-2. Operation Data

<Cooling> RAS-M14EAV-E, RAS-M14EACV-E

Temperature

N o.of

Operating combination

Standard

Heat exchanger

In-

Out

compressor

condition

operating

(Unit)

 

pressure P

pipe temp.

door

door

revolution

indoor

outdoor

un its

A

 

B

(Mpa)

T1 (° C)

T2 (° C)

fan

fan

(rps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 unit

10

 

 

0.7 to 0.9

11 to 13

43 to 45

High

700rpm

39

27 / 19

35 / –

 

13

 

 

0.9 to 1.1

8 to 11

47 to 49

High

750rpm

66

 

 

 

 

 

 

 

 

 

 

2 units

10

 

10

0.9 to 1.1

14 to 16

47 to 49

High

750rpm

64

 

 

 

 

 

 

13

 

10

0.9 to 1.1

14 to 16

47 to 49

High

750rpm

65

 

 

 

 

 

 

 

 

 

 

 

 

<Heating> RAS-M14EAV-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature

N o.of

Operating combination

Standard

Heat exchanger

In-

Out

compressor

condition

operating

(Unit)

 

pressure P

pipe temp.

door

door

revolution

 

 

un its

 

 

 

(Mpa)

 

 

fan

fan

(rps)

indoor

outdoor

A

 

B

T1 (° C)

T2 (° C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 unit

10

 

 

2.2 to 2.4

36 to 38

0 to 2

High

750rpm

60

20/–

7/6

 

13

 

 

2.5 to 2.7

41 to 43

-1 to 1

High

750rpm

76

 

 

 

 

 

 

 

 

 

 

2 units

10

 

10

1.9 to 2.1

30 to 32

-1 to 1

High

750rpm

78

 

 

 

 

 

 

13

 

10

1.9 to 2.1

30 to 32

-1 to 1

High

750rpm

80

<Cooling> RAS-M18EAV-E, RAS-M18EACV-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature

No.of

Operating combination

Standard

Heat exchanger

In-

Out

compressor

condition

operating

(Unit)

 

pressure P

pipe temp.

door

door

revolution

 

 

units

 

 

 

(Mpa)

 

 

fan

fan

(rps)

indoor

outdoor

A

 

B

T1 (° C)

T2 (° C)

 

 

 

 

1 unit

10

 

 

0.9 to 1.1

11 to 13

41 to 43

High

700rpm

35

 

 

 

13

 

 

0.8 to 1.0

8 to 10

45 to 47

High

750rpm

58

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

 

0.8 to 1.0

7 to 9

47 to 49

High

750rpm

75

27/19

35/

 

 

 

 

 

 

 

 

 

 

2 units

10

 

10

0.9 to 1.1

11 to 13

48 to 50

High

750rpm

71

 

 

 

13

 

10

0.9 to 1.1

11 to 13

48 to 50

High

750rpm

71

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

0.9 to 1.1

11 to 13

48 to 50

High

750rpm

71

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

10

0.9 to 1.1

11 to 13

48 to 50

High

750rpm

71

<Heating> RAS-M18EAV-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature

No.of

Operating combination

Standard

Heat exchanger

In-

Out

compressor

condition

operating

(Unit)

 

pressure P

pipe temp.

door

door

revolution

 

 

un its

 

 

 

(Mpa)

 

 

fan

fan

(rps)

indoor

outdoor

A

 

B

T1 (° C)

T2 (° C)

 

 

 

 

1 unit

10

 

 

3.2 to 3.4

44 to 46

0 to 2

High

750rpm

62

 

 

 

13

 

 

3.4 to 3.6

50 to 53

0 to 2

High

750rpm

81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

 

3.4 to 3.6

51 to 53

0 to 2

High

750rpm

85

20/–

7/6

 

 

 

 

 

 

 

 

 

 

2 units

10

 

10

2.6 to 2.8

37 to 39

-1 to 1

High

750rpm

93

 

 

 

13

 

10

2.6 to 2.8

38 to 40

-1 to 1

High

750rpm

101

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

2.6 to 2.8

38 to 40

-1 to 1

High

750rpm

101

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

10

2.6 to 2.8

38 to 40

-1 to 1

High

750rpm

101

NOTES :

(1)Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent. (Thermistor thermometer)

(2)Connecting piping condition : 7.5meters 2 units

– 30 –

Page 30
Image 30
Toshiba RAS-M16EKCVP-E, RAS-M13EKCVP-E, RAS-M18EACV-E, RAS-M14EACV-E, RAS-M10EKCVP-E, RAS-M18EAV-E Operation Data, 30