Toshiba RAS-M14EACV-E, RAS-M13EKCVP-E, RAS-M18EACV-E, RAS-M16EKCVP-E Caution at Servicing, 83

Models: RAS-B10EKVP-E RAS-M14EAV-E RAS-B13EKVP-E RAS-M18EAV-E RAS-M10EKCVP-E RAS-M16EKCVP-E RAS-M14EACV-E RAS-M18EACV-E RAS-M13EKCVP-E

1 136
Download 136 pages 38.01 Kb
Page 83
Image 83
11-4-2. Caution at Servicing

11-4-2. Caution at Servicing

(1)After servicing, push the START/STOP button to return to the normal mode.

(2)After servicing by the check code, turn off breaker of the power supply, and turn on breaker of the power supply again so that memory in the microcomputer returns the initial status. However, the check codes are not deleted even if the power supply is turned off because they are stored in the fixed memory.

(3)After servicing, push [CLR] button under check mode status and then send the check code “7F” to the indoor unit. The error code stored in memory is cleared.

Table 11-4-1

Block distinction

 

Operation of diagnosis function

 

 

 

 

 

 

 

 

 

 

Check

 

Check

 

Air

 

 

Judgment and action

Block

Cause of operation

conditioner

 

Remarks

 

code

code

 

 

 

 

status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor P.C.

 

Short-circuit or discon-

Operation

 

Displayed when

1. Check the room temp. sensor.

 

board etc.

 

nection of the room

continues.

 

error is detected.

2. When the room temp. sensor is

 

 

 

temperature sensor

 

 

 

 

 

 

 

 

 

normal, check P.C. board.

 

 

 

(TA sensor).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Being out of place,

Operation

 

Displayed when

1. Check heat exchanger sensor.

 

 

 

disconnection, short-

continues.

 

error is detected.

2. When heat exchanger sensor is

 

 

 

circuit, or migration of

 

 

 

 

 

 

 

 

 

normal, check P.C. board.

 

 

 

heat exchanger sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

(TC sensor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lock of indoor fan or

All off

 

Displayed when

1. Check the motor.

 

 

 

trouble on the indoor fan

 

 

error is detected.

2. When the motor is normal,

 

 

 

circuit

 

 

 

 

 

 

 

 

 

check P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Not

 

Trouble on other indoor

Operation

 

Displayed when

Replace P.C. board.

 

displayed

 

P.C. boards

continues.

 

error is detected.

 

 

 

 

 

 

 

 

 

 

Connecting

 

Return serial signal is

Operation

 

Flashes when

1. When the outdoor unit never

 

cable and

 

not sent to indoor side

continues.

 

trouble is detected

operate:

 

serial signal

 

from operation started.

 

 

on Return serial

(1) Check connecting cable,

 

 

 

 

 

 

signal, and normal

 

 

 

(1) Defective wiring of

 

 

and correct if defective

 

 

 

 

 

status when signal

 

 

 

connecting cable

 

 

wiring.

 

 

 

 

 

is reset.

 

 

 

(2) Operation of

 

 

(2) Check 25A fuse of inverter

 

 

 

 

 

 

 

 

 

compressor thermo.

 

 

 

P.C. board.

 

 

 

Gas shortage Gas

 

 

 

(3) Check 3.15A of inverter P.C.

 

 

 

leak

 

 

 

 

 

 

 

 

 

board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. To display [Other] block during

 

 

 

 

 

 

 

operation, check compressor

 

 

 

 

 

 

 

thermo. operation and supply

 

 

 

 

 

 

 

gas (check gas leak also).

 

 

 

 

 

 

 

3. Unit operates normally during

 

 

 

 

 

 

 

check.

 

 

 

 

 

 

 

If Return serial signal does not

 

 

 

 

 

 

 

stop between indoor terminal

 

 

 

 

 

 

 

board 2 and 3, replace inverter

 

 

 

 

 

 

 

P.C. board.

 

 

 

 

 

 

 

If signal stops between indoor

 

 

 

 

 

 

 

terminal board 2 and 3, replace

 

 

 

 

 

 

 

indoor P.C. board.

 

 

 

 

 

 

 

 

 

Outdoor P.C.

 

Inverter over-current

All off

 

Displayed when

Even if trying operation again, all

 

board

 

protective circuit

 

 

error is detected.

operations stop immediately. :

 

 

 

operates. (Short time)

 

 

 

Replace P.C. board.

 

 

 

 

 

 

 

 

 

 

 

Position-detect circuit

All off

 

Displayed when

1. Even if connecting lead wire of

 

 

 

error or short-circuit

 

 

error is detected.

compressor is removed,

 

 

 

between windings of

 

 

 

position-detect circuit error

 

 

 

compressor

 

 

 

occurred. : Replace P.C. board.

 

 

 

 

 

 

 

2. Measure resistance between

 

 

 

 

 

 

 

wires of compressor, and

 

 

 

 

 

 

 

perform short-circuit. : Replace

 

 

 

 

 

 

 

compressor.

 

 

 

 

 

 

 

 

– 83 –

Page 83
Image 83