<In cooling/dry operation>

Item

Operation flow and applicable data, etc.

6. Release

<In cooling/dry operation>

protective

(Prevent-freezing control for indoor heat exchanger)

control by

In cooling/dry operation, the sensor of indoor heat ex-

temperature of

changer detects evaporation temperature and controls the

indoor heat

compressor speed so that temperature of the heat ex-

exchanger

changer does not exceed the specified value.

 

temperature

7˚C

 

Usual cooling capacity control

When the value is

 

 

 

 

 

 

 

R

 

exchanger

 

 

P

in Q zone, the

 

 

 

 

 

Q

 

 

 

compressor speed

 

6˚C

 

 

 

 

 

is kept.

 

 

 

heat

5˚C

 

 

 

 

 

 

 

 

 

 

Indoor

 

 

Reduction of compressor speed

 

 

 

 

 

<In heating operation> (Heat pump model) (Prevent-overpressure control for refrigerating cycle)

In heating operation, the sensor of indoor heat exchanger detects condensation temperature and controls the com- pressor speed so that temperature of the heat exchanger does not exceed the specified value.

temperature

 

 

Reduction of compressor speed

 

 

 

 

 

 

P

exchanger

55˚C

 

When the value is

 

50˚C

 

 

 

Q in Q zone, the

 

 

 

 

 

 

 

 

compressor speed

heat

 

 

is kept.

46˚C

 

R

Indoor

 

 

 

 

 

Usual heating capacity control

 

 

 

Description

1)When temperature of the indoor heat exchanger drops below 5°C, the compressor speed is reduced. (P zone)

2)When temperature of the indoor heat exchanger rises in the range from 6°C to under 7°C, the compressor speed is kept. (Q zone)

3)When temperature of the indoor heat exchanger rises to 7°C or higher, the capacity control operation returns to the usual control in cooling operation.

(R zone)

1)When temperature of the indoor heat exchanger rises in the range from 50°C to 55°C, the compressor speed is kept.

(Q zone)

When temperature of the indoor heat exchanger drops in the range from 46°C to under 55°C, the compressor speed is kept. (Q zone)

2)When temperature of the indoor heat exchanger rises to 55°C or higher, the compressor speed is reduced. (P zone)

3)When temperature of the indoor heat exchanger does not rise to 50°C, or when it drops below to 46°C, the capacity control operation returns to the usual control in heating operation.

(R zone)

– 44 –