Toshiba RAS-M18EAV-E, RAS-M13EKCVP-E, RAS-M18EACV-E, RAS-M14EACV-E Purpose, Description, Operation

Models: RAS-B10EKVP-E RAS-M14EAV-E RAS-B13EKVP-E RAS-M18EAV-E RAS-M10EKCVP-E RAS-M16EKCVP-E RAS-M14EACV-E RAS-M18EACV-E RAS-M13EKCVP-E

1 136
Download 136 pages 38.01 Kb
Page 50
Image 50
1. Purpose

Item

Operation flow and applicable data, etc.

Description

12. Air

 

 

 

 

 

1. Purpose

 

 

 

 

 

The air purifying control function is to alert

purifying

 

Purifying operation

 

 

 

control

 

 

 

 

the user to trouble in the ionizing or air

[Detection

 

 

 

 

 

purifying operation.

of abnor-

 

Total

 

 

 

2. Description

mality]

YES

 

 

 

 

 

operation time

 

 

 

Trouble is determined to have occurred

 

 

1000H

 

 

 

 

 

 

 

 

(indicated by the FILTER indicator) in the

 

 

NO

 

 

 

 

 

 

 

 

following four cases.

 

FILTER indicator ON

 

 

 

 

 

 

NO

 

 

1) When a count of 1000H has been

 

 

Error input

 

 

reached on the timer

 

 

 

 

 

 

 

YES

 

 

 

2) When the panel switch has been set to

 

Purifier power OFF

 

 

 

OFF by the opening of the air inlet grile,

 

 

 

 

 

 

 

 

Purifier power ON

NO

FILTER incicator-OFF

 

etc.

 

 

 

3) When an abnormal discharge caused

 

 

1 minute or less

 

continues.

 

 

 

YES

 

 

 

by a symptom such as the build-up of

 

 

 

 

 

dirt has been detected while the air

 

 

FILTER indicator ON

 

Purifier power OFF

 

 

 

 

 

purifier is ON

 

 

 

 

 

 

 

 

 

 

 

 

4) When the electric dust collector has not

 

 

Purifier power OFF

 

Error detection

NO

been installed correctly

 

 

 

Approx. 10 minutes

* Trouble case (2) or (3) is deemed to

 

 

 

 

passed.

 

 

 

 

 

 

have occurred when the action

 

 

 

 

YES

 

 

 

 

 

 

concerned continues for more than

 

 

 

 

 

 

 

 

 

 

Purifier power ON

 

one second.

 

 

 

 

Error input

NO

3. Operation

 

 

 

 

 

The sequence that FILTER indicator is

 

 

 

 

YES

 

 

 

 

 

 

turned on are described in the left flow-

 

 

 

 

 

 

 

 

 

 

 

 

chart.

 

1

2

 

3

 

! When 1000H timer counts up, the

 

 

 

 

 

 

FILTER indicator keeps lighting even if

 

 

 

 

 

 

the operation is stopped by the remote

 

1) Reset by RESET button.

 

 

 

controller.

 

2) Reset by RESET button or by the stop direction from

The timer is stored in memory of the

 

microcomputer, and the operation time

 

the remote controller.

 

 

 

 

 

 

 

is cleared by filter RESET button on the

 

* When the breaker is turned [ON] (In restart time

 

indoor unit or a power failure. (FILTER

 

after power failure) or RESET button is pushed

 

 

 

indicator goes off.)

 

while the FILTER indicator is turned on, the air

 

 

 

" A trouble detected within 1 minute after

 

purifier is not turned on until the integrated opera-

 

activation of the air is immediately

 

tion time of the indoor fan exceeds 1 hour after

 

 

 

judged as an error and the FILTER

 

operation start (It is nor the air purifier operation

 

indicator goes on.

 

time).

 

 

 

 

 

 

 

 

 

# In case that 1 minute passed after

 

It is the safety measures considering an incomplete

 

drain when electric dust collector has been cleaned

activation of the purifier, the purifier is

 

with water.

 

 

 

turned off while the PURE indicator

 

 

 

 

 

 

keeps ON. After 10 minutes passed,

 

 

 

 

 

 

restart the purifier and an error is

 

 

 

 

 

 

judged again.

13. Discharge

 

 

1. Purpose

tempera-

Td value

Control operation

This function detects error on the

ture control

120˚C

Judges as an error and stops the compressor.

refrigerating cycle or error on the

 

 

 

compressor, and performs protective

 

Reduce the compressor speed.

 

115˚C

control.

 

 

 

Reduce slowly compressor speed.

 

111˚C

 

 

 

2. Operation

 

Keeps the compressor speed.

 

 

 

108˚C

• Control of the compressor speed

 

 

 

If the operation is performed with lower speed

 

 

The speed control is performed as

 

 

than one commanded by the serial signal, speed

 

101˚C

is slowly raised up to the commanded speed.

described in the left table based upon

 

 

the discharge temperature.

 

Operates with speed commanded by the serial

 

 

 

 

 

signal.

 

 

 

 

 

– 50 –