10-5-4. Wiring Connection

Packed valve handling precautions

Open the valve stem all the way; but do not try to open it beyond the stopper. Securely tighten the valve stem cap with torque in the following table:

Gas side

50 to 62 N·m

(φ12.7 mm)

(5.0 to 6.2 kgf·m)

 

 

Gas side

33 to 42 N·m

(φ9.52 mm)

(3.3 to 4.2 kgf·m)

 

 

Liquid side

14 to 18 N·m

(φ6.35 mm)

(1.4 to 1.8 kgf·m)

 

 

Service port

14 to 18 N·m

 

(1.4 to 1.8 kgf·m)

 

 

Hexagon wrench is required.

4 mm

10-5-4. Wiring Connection

1.Remove the valve cover, the electric parts cover and the cord clamp from the outdoor unit.

2.Connect the connecting cable to the terminal as identified by the matching numbers on the terminal block of indoor and outdoor unit.

3.Insert the power cord and the connecting cable fully into the terminal block and secure it tightly with screws.

4.Insulate the unused cords (conductors) from water entering in the outdoor unit. Locate them so that they do not touch any electrical or metal parts.

5.Secure the power cord and the connecting cable with the cord clamp.

6.Attach the electric parts cover and the valve cover on the outdoor unit.

Stripping length of connecting cable

Terminal block

1

2

3

1

2

3

L

N

 

1 2 3

L N

10

 

 

10

 

 

10

 

 

40

10

 

40

30

30

 

 

 

 

 

 

 

 

 

Power cord

Earth line

 

 

 

Earth line

Connecting

 

Connecting

 

Power cord

 

 

Connecting

 

 

cable

 

 

cable for unit A

 

 

 

 

 

 

 

 

 

 

 

 

cable for unit B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

RAS-M14EAV-E

 

RAS-M18EAV-E

 

RAS-M14EACV-E

RAS-M18EACV-E

 

 

 

 

 

 

 

 

 

Power source

 

 

 

 

220–240V

~50Hz

 

 

 

 

 

220V

~60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum running current

10.0A

 

 

15.0A

 

8.0A

11.0A

 

 

 

 

 

 

 

 

 

Installation fuse rating

 

 

 

 

25A (D type

)

 

 

 

 

 

 

 

Power cord

 

 

 

H07RN-F or 245IEC66 (1.5 mm2 or more)

 

Connecting cable

 

 

 

H07RN-F or 245IEC66 (1.0 mm2 or more)

 

CAUTION

Incorrect wiring connection may cause electrical parts to burn out.

Be sure to comply with local regulations/codes when running the wire from outdoor unit to indoor unit. (Size of wire and wiring method etc.)

Every wire must be securely connected.

This installation fuse (25A D type – 74 – ) must be used for the power supply line.

If incorrect or incomplete wiring is carried out, fire or smoke may result.

Prepare the power supply for the exclusive use of the air conditioner.

This product can be connected to the main breaker.

Connection to fixed wiring: A switch which disconnects all poles and has a contact separation of at least 3 mm must be incorporated in the fixed wiring when connecting to a main breaker circuit.