Toshiba RAS-M14EACV-E 38, Ts +, Fan only operation Cooling-onlymodel, +1.0, +0.5, Item

Models: RAS-B10EKVP-E RAS-M14EAV-E RAS-B13EKVP-E RAS-M18EAV-E RAS-M10EKCVP-E RAS-M16EKCVP-E RAS-M14EACV-E RAS-M18EACV-E RAS-M13EKCVP-E

1 136
Download 136 pages 38.01 Kb
Page 38
Image 38
Item

Item

 

 

Operation flow and applicable data, etc.

 

Description

 

 

 

 

 

 

 

1. Basic operation

4) AUTO operation

 

1) Detects the room temperature

 

Selection of operation mode

 

(Ta) when the operation started.

 

 

2) Selects an operation mode from

 

As shown in the following figure, the operation starts by

 

 

 

Ta in the left figure.

 

selecting automatically the status of room temperature

 

 

 

 

 

(Ta) when starting AUTO operation.

 

3) Fan operation continues until an

 

 

 

 

 

 

operation mode is selected.

 

 

 

 

 

 

4) When AUTO operation has

 

 

 

 

 

 

started within 2 hours after

 

 

 

 

 

 

heating operation stopped and if

 

 

 

 

 

 

the room temperature is 20°C or

 

 

 

 

 

 

more, the fan operation is

 

Ta

 

 

 

 

performed with ”Super Ultra

 

 

 

 

LOW” mode for 3 minutes.

 

 

 

 

 

 

 

 

 

 

 

 

Cooling operation

 

Then, select an operation mode.

 

 

 

 

5) If the status of compressor-OFF

 

 

 

 

 

 

 

Ts + 1

 

 

 

 

continues for 15 minutes the

 

 

 

 

room temperature after selecting

 

 

 

 

 

 

 

Monitoring (Fan)

 

an operation mode (COOL/

 

 

 

 

HEAT), reselect an operation

 

 

 

 

 

 

mode.

 

Ts – 1

 

 

 

 

 

 

Heating operation (Heat pump model)

 

 

 

 

 

 

 

 

 

 

Fan only operation (Cooling-only model)

 

 

 

 

 

 

 

 

 

*1. When reselecting the operation mode, the fan speed

 

 

 

is controlled by the previous operation mode.

 

 

 

 

 

 

 

 

 

 

5) DRY operation

 

1) Detects the room temperature

 

DRY operation is performed according to the difference

 

(Ta) when the DRY operation

 

 

started.

 

between room temperature and the setup temperature

 

 

 

 

 

as shown below.

 

2) Starts operation under condi-

 

In DRY operation, fan speed is controlled in order to

 

tions in the left figure according

 

 

to the temperature difference

 

prevent lowering of the room temperature and to avoid

 

 

 

between the room temperature

 

air flow from blowing directly to persons.

 

 

 

and the setup temperature (Tsc).

 

 

 

 

 

 

 

 

 

 

 

 

Setup temperature (Tsc) =

 

[˚C]

 

Set temperature on remote

 

 

controller (Ts) + (0.0 to 1.0)

 

Ta

 

 

3) When the room temperature is

 

 

 

 

 

 

lower 1°C or less than the setup

 

 

 

 

L– (W5)

 

temperature, turn off the

 

 

 

 

 

compressor.

 

 

 

 

 

 

 

+1.0

 

 

(W5+W3) / 2

 

 

 

 

 

 

 

 

 

+0.5

 

 

 

 

 

 

 

 

 

SL (W3)

 

 

 

Tsc

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan speed

 

 

 

 

 

 

 

 

 

– 38 –

Page 38
Image 38
Toshiba RAS-M14EACV-E, RAS-M13EKCVP-E 38, Ts +, Fan only operation Cooling-onlymodel, +1.0, +0.5, Item, Description