7. REFRIGERANT CYCLE DIAGRAM

7. REFRIGERANT CYCLE DIAGRAM

7-1. Refrigerant Cycle Diagram

RAS-B13EKVP-E, RAS-B10EKVP-E

RAS-M14EAV-E

To B room

PPressure measurement

Gauge attaching port

Vacuum pump connecting port

Deoxidized copper pipe

Both A and B rooms

Outer dia. : 9.52mm

Thickness : 0.8mm

TGb7-1. Refrigerant Cycle Diagram

*1

Tca

INDOOR UNIT

Indoor heat exchanger

Indoor fan

Ta

Deoxidized copper pipe

Both A and B rooms

Outer dia. : 6.35mm

Thickness : 0.8mm

Sectional shape of heat insulator

Muffler

RAS-B13EKVP-E, RAS-B10EKVP-E– 26 –TGa

T1 Temp. measurement

To B room

 

lengthpipeAllowable

Per 1 unit

heightAllowable 10m:difference

Max.: 20m

Total: 30m

 

 

Chargeless

 

 

= 20m

 

 

Charge

 

 

= 20g/m

 

 

(21 to 30m)

Capillary Ø2.2 x 200 Manual background

4-way valve (STF-0108Z)

TS

Temp. measurement T2

Manual background Muffler

Td

Compressor

DA111A1F-20F1

Outdoor heat exchanger

Manual background TE

TO

Propeller fan

OUTDOOR UNIT

Manual background Strainer

Pulse motor

valve at liquid side (CAM-B22YGTF-2)

Capillary Ø2.2 x 200 Manual background

Refrigerant amount : 0.90kg

NOTE : Manual background Gas leak check position Manual background Refrigerant flow (Cooling)

*1 The TC sensor is at the center of the indoor unit’s heat exchanger.

Refrigerant flow (Heating)

NOTE :

The maximum pipe length of this air conditioner is 30m. When the pipe length exceeds 20m, the additional charge of refrigerant, 20g per 1m for the part of pipe exceeded 20m is required (Max. 200g)

– 26 –