Toshiba RAS-B13EKVP-E, RAS-M13EKCVP-E 51, Operation flow and applicable data, etc, Description

Models: RAS-B10EKVP-E RAS-M14EAV-E RAS-B13EKVP-E RAS-M18EAV-E RAS-M10EKCVP-E RAS-M16EKCVP-E RAS-M14EACV-E RAS-M18EACV-E RAS-M13EKCVP-E

1 136
Download 136 pages 38.01 Kb
Page 51
Image 51
– 51 –

Item

 

Operation flow and applicable data, etc.

Description

 

 

 

14. Pulse Motor

This function controls throttle amount of the refrigerant in

1) When starting the operation, move

valve

the refrigerating cycle.

the valve once until it fits to the

(PMV)

According to operating status of the air conditioner, this

stopper. (Initialize)

control

 

function also controls the open degree of valve with an

* In this time, “Click” sound may be

 

 

expansion valve with pulse motor.

heard.

 

 

 

 

 

 

 

 

 

 

 

 

 

2) Adjust the open degree of valve by

 

 

 

 

 

 

 

 

 

 

 

 

 

super heat amount. (SH control)

 

 

 

 

 

 

 

 

 

 

 

 

 

3) If the discharge temperature was

 

 

 

 

 

Starting up

 

 

 

 

excessively up, adjust the open

 

 

 

 

 

 

 

 

degree of valve so that it is in the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

range of set temperature.

 

 

 

 

 

 

 

 

 

 

 

 

 

(Discharge temp. control)

 

 

 

 

 

Initialize

 

 

 

 

 

 

 

 

 

 

 

 

4) When defrost operation is per-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

formed, the open degree of valve is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

adjusted according to each setup

 

 

 

 

 

Move to

 

 

 

conditions during preparation for

 

 

 

 

 

initial position

 

 

 

defrost and during defrost opera-

 

 

 

 

 

 

 

 

 

 

 

 

 

tion (4-way valve is inversed.).

 

 

 

 

 

 

 

 

 

 

 

 

 

5) To turn off the compressor while the

 

 

 

 

 

 

 

 

Compressor ON

 

 

 

 

 

 

 

 

 

 

 

 

air conditioner stops by control of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the thermostat or by remote

 

 

 

 

 

 

 

 

 

 

 

 

 

controller, adjust the open degree

 

 

SH control

 

 

 

 

Td

 

 

of valve to the setup value before

 

 

 

 

 

release control

 

 

stop of the compressor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PMV open degree control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop by

 

 

Room temp. sensor

 

 

remote controller

 

 

(Ta sensor) control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power OFF

 

 

 

 

 

Defrost

 

 

 

 

 

 

 

 

 

 

 

 

 

*SH (Super Heat amount, cooling operation) =

Tg (Temperature of gas pipe) – Tc (Heat exchanger temperature of indoor unit)

*SH (Super Heat amount, heating operation) =

Ts (Temperature of suction pipe of the compressor) – Te (Heat exchanger temperature of outdoor unit)

*PMV: Pulse Motor Valve