5-11
Configuration
On - Callback ONLY (Without Password Prompt): Callbacks will be performed
for user accounts that include a Callback Number, and the username/password
prompt will not be displayed when the user’s modem answers. Accounts that do
not include a Callback Number will not be able to access command mode via an
RSM modem port.
On - Callback ONLY (With Password Prompt): Callbacks will be performed
for user accounts that include a Callback Number, and the username/password
prompt will be displayed when the user’s modem answers (users will be required
to re-enter their username/password when their modem answers.) Accounts that
do not include a Callback Number will not be able to access command mode via
an RSM modem port.
Callback Attempts: The number of times that the RSM will attempt to call the
Callback number. (Default = 3 attempts.)
Callback Delay: The amount of time that the RSM will wait between Callback
attempts. (Default = 30 seconds.)
Notes:
After configuring and enabling Callback Security, you must then define a
callback phone number for each desired user account (as described in
Section 5.6) in order for this feature to function properly.
When using the "On - Callback (With Password Prompt)" option, it is
important to always define a callback number for each user account.
Otherwise accounts that do not include a callback number will be allowed to
immediately access command mode, and the callback function will not be
performed.