Command Reference
Command Reference
Table
ASTS?Command | DescriptionAsks for the supply’s accumulated status register. The accumulated status register |
| stores any bit that was entered in the status register since the accumulated status |
| query command (ASTS?) was last used, regardless of whether the condition still |
| exists. The accumulated status register has the same bits, weights, and conditions |
| as the status register. A bit in the accumulated status register will be set at 1 if the |
| corresponding bit in the status register has been 1 (TRUE) at any time since the |
| register was last read. See “Accumulated Status, Status, and Fault Registers” on |
| page |
| Response: ASTS <status mask> where status mask is the decimal equivalent of the |
| total bit weights for the operating conditions as listed in the status register. |
|
|
AUXA <1/ON>, | Controls the AUXA output signal level at rear panel connector Pin 7. Active low. |
<0/OFF> | Initial value: AUXA 0 |
|
|
AUXA? | Asks for the present set value of the AUXA output signal. |
| Response: AUXA 0 (OFF) or AUXA 1 (ON) |
|
|
AUXB <1/ON>, | Controls the AUXB output signal level at rear panel connector Pin 8. Active low. |
<0/OFF> | Initial value: AUXB 0 |
|
|
AUXB? | Asks for the present set value of the AUXB output signal. |
| Response: AUXB 0 (OFF) or AUXB 1 (ON) |
|
|
CLR | Initializes the power supply to its power ON condition. If issued while in local |
| mode, CLR will force power supply settings to register default values as in but |
| these default settings will not come into effect until the power supply is switched to |
| remote mode operation. The CLR commands will clear faults from the fault |
| register. CLR will not reset CMODE. |
|
|
CMODE <1/ON>, | CMODE ON places the power supply into calibration mode for processing |
<0/OFF> | calibration commands. |
| Initial value: CMODE OFF or CMODE 0 |
|
|
CMODE? | Asks for the power supply’s calibration mode status. |
| Response: CMODE 0 (disabled) |
| CMODE 1 (enabled) |
|
|