Xantrex Technology ENET-XFR3 manual MnemonicCV, 8 Accumulated Status, Status and Fault Registers

Models: ENET-XFR ENET-XFR3

1 100
Download 100 pages 7.21 Kb
Page 68
Image 68
Table 3-8Accumulated Status, Status and Fault Registers

Operation

Table 3-8Accumulated Status, Status and Fault Registers

ConstantConditionvoltage operation

MnemonicCV

PositionBit0

WeightBit1

Constant current operation

CC

1

2

 

 

 

 

Not used

2

4

 

 

 

 

Overvoltage protection tripped

OV

3

8

 

 

 

 

Over temperature protection tripped

OT

4

16

 

 

 

 

Supply external shutdown active Pin 1 of the

SD

5

32

user lines connector

 

 

 

 

 

 

 

Foldback mode operation

FOLD

6

64

 

 

 

 

Remote programming error

ERR

7

128

 

 

 

 

Power ON

PON

8

256

(accumulated status, status registers only)

 

 

 

 

 

 

 

Remote mode

REM

9

512

(accumulated status, status registers only)

 

 

 

 

 

 

 

AC fail condition

ACF

10

1024

 

 

 

 

Output fail condition

OPF

11

2048

 

 

 

 

Sense protection tripped

SNSP

12

4096

 

 

 

 

Notes:

1.All mnemonics can be masked or unmasked.

2.The error (ERR) bit is reset in the accumulated status, status, and serial poll registers with an error query (ERR?).

3.The accumulated status register is cleared with an accumulated status query (ASTS?).

4.A fault is cleared with a fault query (FAULT?).