Specifications for XFR 1.2kW with Ethernet/RS-232 Interface Installed

Table A-2XFR 1.2kW 60 V to 600 V

ProgramModelsResolution

60-20

100-12

150-8

300-4

600-2

Voltage

9.3mV

15.5mV

23.2mV

46.4mV

92.7mV

Current

2.6mA

.5mA

.0mA

.5mA

.3mA

OVP

9.3mV

15.5mV

23.2mV

46.4mV

92.7mV

 

 

 

 

 

 

Program Accuracya

150mV

150mV

225mV

225mV

300mV

Voltage

 

±0.25%

±0.35%

±0.35%

±0.35%

±0.35%

Current

120mA

80mA

80mA

80mA

75mA

 

±0.1%

±0.1%

±0.1%

±0.1%

±0.1%

OVP

600mV

.0V

.5V

.0V

6V

 

 

 

 

 

 

Readback Resolution

 

 

 

 

 

Voltage

9.3mV

15.5mV

23.2mV

46.4mV

92.7mV

Current

2.6mA

.5mA

.0mA

.5mA

.3mA

 

 

 

 

 

 

Readback Accuracya

150mV

150mV

225mV

225mV

300mV

Voltage

 

±0.25%

±0.35%

±0.35%

±0.35%

±0.35%

Current

120mA

80mA

80mA

80mA

75mA

 

±0.1%

±0.1%

±0.1%

±0.1%

±0.1%

 

 

 

 

 

 

a.Apply accuracy specifications according to the following voltage program accuracy example: Set a model 20-60 power supply to 10 volts.

The expected result will be within the range of 10 volts ± 75mV ± 0.12% of the set voltage of 10 volts.

TM-XR9B-01XN

A–3

Page 85
Image 85
Xantrex Technology ENET-XFR3 manual 600-2