Specifications

Specifications for XFR 1.2kW with Ethernet/RS-232 Interface Installed

Table A-1XFR 1.2kW 7.5 V to 40 V

ProgramModelsResolution

7.5-140

12-100

20-60

35-35

40-30

Voltage

1.2mV

3.1mV

5.1mV

.4mV

6.2mV

Current

18.3mA

7.1mA

4.7mA

.4mA

3.6mA

OVP

1.2mV

3.1mV

5.1mV

.4mV

6.2mV

 

 

 

 

 

 

Program Accuracya

10mV

75mV

75mV

75mV

75mV

Voltage

 

±0.12%

±0.12%

±0.12%

±0.3%

±0.3%

Current

500mA

250mA

165mA

200mA

140mA

 

±0.1%

±0.1%

±0.15%

±0.1%

±0.15%

OVP

80mV

200mV

330mV

350mV

400mV

 

 

 

 

 

 

Readback Resolution

 

 

 

 

 

Voltage

1.2mV

3.1mV

5.1mV

.4mV

6.2mV

Current

18.3mA

7.1mA

4.7mA

.4mA

3.6mA

 

 

 

 

 

 

Readback Accuracya

30mV

75mV

75mV

75mV

75mV

Voltage

 

±0.12%

±0.12%

±0.2%

±0.3%

±0.3%

Current

500mA

250mA

165mA

200mA

140mA

 

±0.1%

±0.1%

±0.15%

±0.1%

±0.15%

a.Apply accuracy specifications according to the following voltage program accuracy example: Set a model 20-60 power supply to 10 volts.

The expected result will be within the range of 10 volts ± 75mV ± 0.12% of the set voltage of 10 volts.

A–2

TM-XR9B-01XN

Page 84
Image 84
Xantrex Technology ENET-XFR3 manual 40-30, Ovp