Max Chg Rate |
|
|
|
|
|
|
Full name | Maximum charge rate |
|
|
| ||
Configurable setting | The actual battery charge rate is determined by two things. First, the | |||||
| RS2000 uses the bank size setting (C) divided by 5 (C÷5). This value is | |||||
| then regulated by the charge rate setting. For example, if the battery bank | |||||
| size is set to 300 Ah and the charge rate was set at 100%, the calculation | |||||
| would be: 300 ÷ 5 or 60 amps × 100% which is a 60 amp charge rate. If | |||||
| the charge rate is adjusted to 50%, the resulting charge rate would be 30 | |||||
| amps (60 amps × 50%). |
|
|
| ||
| The RS2000 has a maximum charge rate of 100 amps. Even though you | |||||
| can set a bank size of 2000 Ah, where C÷5 is 400 amps, the RS2000 | |||||
| would still charge at 100 amp maximum. |
|
|
| ||
|
|
|
|
|
|
|
| Max Chg Rate | [100%] |
|
|
| |
|
|
|
|
|
|
|
| Range of values |
| Increment |
| Default | |
|
|
| ||||
|
|
|
|
|
|
|
| 10% to 100% |
| 10 |
| 100% |
|
|
|
|
|
|
| |
When to use | Displayed only if in charger mode when you wish to control the | |||||
| maximum charge rate to your batteries. |
|
|
| ||
Load Sense |
|
|
|
|
|
|
Configurable setting | This setting lets you enable or disable the load sensing function. | |||||
|
|
|
|
|
|
|
| Load sense |
| [On] |
|
|
|
|
|
|
|
|
|
|
Value
On
Off
Default
Off
When to use | Enable this setting if you want the inverter to conserve battery power |
| when there are small loads or no loads applied. |
Outcome | A small load like a clock display on a microwave may not get power. |
| When loads are below the load sense threshold, the inverter will turn off |
| the output to save battery power. |