Troubleshooting
Table | Fault Messages |
|
|
|
Fault |
| Fault |
|
|
|
|
| ||
Number | Message | Type | Cause | Solution |
|
|
|
|
|
F14 | Input AC too high. | Automatic | AC Over Voltage | Not applicable for RS2000 |
| Check source, clear |
| Shutdown (AC Line 2 |
|
| fault, try again. |
| input) |
|
|
|
|
|
|
F15 | Input AC too low. | Automatic | AC Under Voltage | Not applicable to RS2000. |
| Check source, clear |
| Shutdown (AC Line 2 |
|
| fault, try again. |
| input) |
|
|
|
|
|
|
F16 | AC input frequency | Automatic | AC Over Frequency | Clear the fault and attempt |
| problem. Check gen |
| Shutdown (AC Line 1 | restart. Check AC input |
| for overspeed. |
| input) | frequency. Check and adjust |
|
|
|
| AC input high frequency |
|
|
|
| setting. |
|
|
|
|
|
F17 | AC input frequency | Automatic | AC Under Frequency | Clear the fault and attempt |
| problem. Check gen |
| Shutdown (AC Line 1 | restart. Check AC input |
| for underspeed. |
| input) | frequency. Check and adjust |
|
|
|
| AC input low frequency |
|
|
|
| setting. |
|
|
|
|
|
F18 | AC input frequency | Automatic | AC Over Frequency | Not applicable to RS2000. |
| problem. Check gen |
| Shutdown (AC Line 2 |
|
| for overspeed. |
| input) |
|
|
|
|
|
|
F19 | AC input frequency | Automatic | AC Under Frequency | Not applicable to RS2000. |
| problem. Check gen |
| Shutdown (AC Line 2 |
|
| for underspeed. |
| input) |
|
|
|
|
|
|
F23 | Reset the RS2000. If | Escalating | AC Over Voltage | Clear the fault and attempt |
| problem persists, call | Auto Fault. | Shutdown (Inverter | restart. If problem persists, call |
| customer service. | Must occur | AC output) | customer service. |
|
| 3 times in |
|
|
|
| 30 seconds |
|
|
|
| before |
|
|
|
| becoming |
|
|
|
| a manual |
|
|
|
| fault. |
|
|
|
|
|
|
|