Troubleshooting

Table 4-4

Fault Messages

 

 

 

Fault

 

Fault

 

 

 

 

 

Number

Message

Type

Cause

Solution

 

 

 

 

 

F14

Input AC too high.

Automatic

AC Over Voltage

Not applicable for RS2000

 

Check source, clear

 

Shutdown (AC Line 2

 

 

fault, try again.

 

input)

 

 

 

 

 

 

F15

Input AC too low.

Automatic

AC Under Voltage

Not applicable to RS2000.

 

Check source, clear

 

Shutdown (AC Line 2

 

 

fault, try again.

 

input)

 

 

 

 

 

 

F16

AC input frequency

Automatic

AC Over Frequency

Clear the fault and attempt

 

problem. Check gen

 

Shutdown (AC Line 1

restart. Check AC input

 

for overspeed.

 

input)

frequency. Check and adjust

 

 

 

 

AC input high frequency

 

 

 

 

setting.

 

 

 

 

 

F17

AC input frequency

Automatic

AC Under Frequency

Clear the fault and attempt

 

problem. Check gen

 

Shutdown (AC Line 1

restart. Check AC input

 

for underspeed.

 

input)

frequency. Check and adjust

 

 

 

 

AC input low frequency

 

 

 

 

setting.

 

 

 

 

 

F18

AC input frequency

Automatic

AC Over Frequency

Not applicable to RS2000.

 

problem. Check gen

 

Shutdown (AC Line 2

 

 

for overspeed.

 

input)

 

 

 

 

 

 

F19

AC input frequency

Automatic

AC Under Frequency

Not applicable to RS2000.

 

problem. Check gen

 

Shutdown (AC Line 2

 

 

for underspeed.

 

input)

 

 

 

 

 

 

F23

Reset the RS2000. If

Escalating

AC Over Voltage

Clear the fault and attempt

 

problem persists, call

Auto Fault.

Shutdown (Inverter

restart. If problem persists, call

 

customer service.

Must occur

AC output)

customer service.

 

 

3 times in

 

 

 

 

30 seconds

 

 

 

 

before

 

 

 

 

becoming

 

 

 

 

a manual

 

 

 

 

fault.

 

 

 

 

 

 

 

4–14

975-0125-01-01

Page 98
Image 98
Xantrex Technology RS2000 manual Fault Messages