Specifications

Transfer and General Specifications

All transfer specifications are at nominal conditions: ambient temperature of 77 °F (25 °C), 120 VAC, 60 Hz input, unless otherwise specified.

Table A-3Transfer and General Specifications

Transfer time—utility to invert

20 ms

Minimum AC input voltage for transfer

90 VAC RMS

 

 

Maximum AC input voltage for transfer

135 VAC RMS

 

 

Minimum AC input frequency for transfer

55 Hz

 

 

Maximum AC input frequency for transfer

65 Hz

 

 

Cooling

Fan-cooled, temperature controlled.

 

 

Network power supply

800 mA at 15 VDC

 

 

Environmental Specifications

Table A-4Environmental Specifications

Nominal Ambient temperature

77 °F (25 °C)

Full Power Operating Ambient

–4 ° to 122 °F (–20 ° to 50 °C)

Temperature Range

 

 

 

Maximum Operating Temperature

140 °F (60 °C)

 

 

Storage temperature range

–40 ° to 185 °F (–40 to 85 °C)

 

 

Humidity: Operation/Storage

≤ 95% RH, non-condensing

 

 

A–4

975-0125-01-01

Page 106
Image 106
Xantrex Technology RS2000 manual Transfer and General Specifications, Environmental Specifications