Configuration

Eqz Volts

 

 

 

 

 

 

Full name

Equalization voltage

 

 

 

 

Configurable setting

This setting lets you set the desired equalization voltage. This menu is

 

displayed only if charger equalization is enabled. Select a setting based on

 

the battery manufacturer’s recommendation. For more information, see

 

“Battery Charging Reference” on page B–1.

 

 

 

 

 

 

 

 

Eqz Volts

[15.8V]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Range of values

 

Increment

 

Default

 

 

 

 

 

 

 

 

13.5 to 15.8 VDC

 

0.1 volts

 

15.8 VDC

Force Charge

 

 

 

 

 

 

 

 

 

 

 

 

Full name

Force Charge

 

 

 

 

Configurable setting

This setting forces the charger to be enabled (On) whenever you have

 

qualified AC or reacquired qualified AC. If Force Enabled is not on, you

 

must turn it to On using the System Control Panel.

 

 

 

 

 

 

 

Force Charge

[On]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Values

 

Default

 

 

 

 

 

 

 

 

 

 

 

On

 

On

 

 

 

 

 

 

 

 

 

 

 

Off

 

 

 

 

 

 

 

 

 

When to use

If you want the charger to automatically start when you connect to

 

qualified AC input.

 

 

 

 

Outcome

The charger starts whenever qualified AC input appears.