| Configuration |
When to use | This setting lets you adjust the AC parameters when the AC supply is |
| outside the lower frequency range required for electrical equipment. |
Outcome | The lower frequency of voltage that will be qualified as “good” by the |
| inverter/charger can be varied. |
Hi AC Volt
Full name | Hi AC transfer voltage (AC over voltage level) | |||||||
Configurable setting | This setting lets you adjust the voltage above which the inverter/charger | |||||||
| no longer qualifies AC as “good” and attempts to transfer to Invert. | |||||||
|
|
|
|
|
|
|
|
|
| Hi AC Volt |
| [135V] |
|
|
|
| |
|
|
|
|
|
|
|
|
|
| Range of values |
|
| Increment |
|
| Default | |
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| 120 to 145 VAC |
|
| 1 volt |
|
| 135 VAC | |
|
|
|
|
|
|
| ||
When to use | This setting lets you adjust the AC parameters when AC supply is outside | |||||||
| the upper voltage range required for electrical equipment. | |||||||
Outcome | The upper level of voltage that will be qualified as “good” by the inverter/ | |||||||
| charger can be varied. |
|
|
|
| |||
Hi AC Freq |
|
|
|
|
|
|
|
|
Full name | Hi AC transfer frequency (AC over frequency level) | |||||||
Configurable setting | This setting lets you adjust the frequency at which the RS2000 no longer | |||||||
| qualifies AC as “good” and attempts to transfer to Invert. | |||||||
|
|
|
|
|
|
|
| |
| Hi AC Freq |
| [65Hz] |
|
|
|
| |
|
|
|
|
|
|
| ||
| Range of values |
| Increment |
| Default | |||
|
|
| ||||||
|
|
|
|
|
|
| ||
| 62 to 70 Hz |
| 1 Hz |
| 65 Hz | |||
|
|
|
|
|
| |||
When to use | This setting lets you adjust the AC parameters when the AC supply is | |||||||
| outside the higher frequency range required for electrical equipment. | |||||||
Outcome | The higher frequency of voltage that will be qualified as “good” by the | |||||||
| inverter/charger can be varied. |
|
|
|
|