48TC
Table 1 – Cooling Service Analysis
PROBLEM | CAUSE | REMEDY | |
| Power failure. | Call power company. | |
|
|
| |
| Fuse blown or circuit breaker tripped. | Replace fuse or reset circuit breaker. | |
|
|
| |
Compressor and Condenser | Defective thermostat, contactor, transformer, | Replace component. | |
or control relay. | |||
Fan Will Not Start. |
| ||
|
| ||
Insufficient line voltage. | Determine cause and correct. | ||
| |||
|
|
| |
| Incorrect or faulty wiring. | Check wiring diagram and rewire correctly. | |
|
|
| |
| Thermostat setting too high. | Lower thermostat setting below room temperature. | |
| Faulty wiring or loose connections in | Check wiring and repair or replace. | |
| compressor circuit. | ||
|
| ||
|
|
| |
| Compressor motor burned out, seized, or | Determine cause. Replace compressor. | |
Compressor Will Not Start But | internal overload open. | ||
| |||
Condenser Fan Runs. |
|
| |
Defective run/start capacitor, overload, start | Determine cause and replace. | ||
| relay. | ||
|
| ||
|
|
| |
| One leg of | Replace fuse or reset circuit breaker. Determine | |
| cause. | ||
|
| ||
|
|
| |
| Refrigerant overcharge or undercharge. | Recover refrigerant, evacuate system, and recharge | |
| to nameplate. | ||
|
| ||
|
|
| |
| Defective compressor. | Replace and determine cause. | |
|
|
| |
Compressor Cycles (other | Insufficient line voltage. | Determine cause and correct. | |
|
| ||
Blocked condenser. | Determine cause and correct. | ||
than normally satisfying | |||
|
| ||
Defective run/start capacitor, overload, or start |
| ||
thermostat). | Determine cause and replace. | ||
relay. | |||
|
| ||
|
|
| |
| Defective thermostat. | Replace thermostat. | |
|
|
| |
| Faulty | Replace. | |
|
|
| |
| Restriction in refrigerant system. | Locate restriction and remove. | |
| Dirty air filter. | Replace filter. | |
|
|
| |
| Unit undersized for load. | Decrease load or increase unit size. | |
|
|
| |
Compressor Operates | Thermostat set too low. | Reset thermostat. | |
|
| ||
Low refrigerant charge. | Locate leak; repair and recharge. | ||
Continuously. | |||
|
| ||
Leaking valves in compressor. | Replace compressor. | ||
| |||
| Air in system. | Recover refrigerant, evacuate system, and recharge. | |
|
|
| |
| Condenser coil dirty or restricted. | Clean coil or remove restriction. | |
|
|
| |
| Dirty air filter. | Replace filter. | |
| Dirty condenser coil. | Clean coil. | |
Excessive Head Pressure. |
|
| |
Refrigerant overcharged. | Recover excess refrigerant. | ||
|
|
| |
| Air in system. | Recover refrigerant, evacuate system, and recharge. | |
| Condenser air restricted or air | Determine cause and correct. | |
|
|
| |
| Low refrigerant charge. | Check for leaks; repair and recharge. | |
Head Pressure Too Low. |
|
| |
Compressor valves leaking. | Replace compressor. | ||
|
|
| |
| Restriction in liquid tube. | Remove restriction. | |
|
|
| |
| High head load. | Check for source and eliminate. | |
Excessive Suction Pressure. |
|
| |
Compressor valves leaking. | Replace compressor. | ||
|
|
| |
| Refrigerant overcharged. | Recover excess refrigerant. | |
|
|
| |
| Dirty air filter. | Replace filter. | |
| Low refrigerant charge. | Check for leaks; repair and recharge. | |
|
|
| |
| Metering device or low side restricted. | Remove source of restriction. | |
Suction Pressure Too Low. |
|
| |
Insufficient evaporator airflow. | Increase air quantity. Check filter and replace if | ||
| necessary. | ||
|
| ||
|
|
| |
| Temperature too low in conditioned area. | Reset thermostat. | |
|
|
| |
| Outdoor ambient below 25° F. | Install | |
|
|
| |
Evaporator Fan Will Not Shut | Time off delay not finished. | Wait for | |
Off. | |||
|
| ||
|
|
| |
Compressor Makes Excessive | Compressor rotating in wrong direction. | Reverse the | |
Noise. | |||
|
| ||
|
|
|