Carrier 48TC*D08 appendix Troubleshooting

Page 23

INDICATORS

Normal State

The smoke detector operates in the normal state in the absence of any trouble conditions and when its sensing chamber is free of smoke. In the normal state, the Power LED on both the sensor and the controller are on and all other LEDs are off.

Alarm State

The smoke detector enters the alarm state when the amount of smoke particulate in the sensor’s sensing chamber exceeds the alarm threshold value. (See Table 3.) Upon entering the alarm state:

SThe sensor’s Alarm LED and the controller’s Alarm LED turn on.

S The contacts on the controller’s two auxiliary relays switch positions.

S The contacts on the controller’s alarm initiation relay close.

S The controller’s remote alarm LED output is activated (turned on).

S The controller’s high impedance multiple fan shutdown control line is pulled to ground Trouble state.

The SuperDuct duct smoke detector enters the trouble state under the following conditions:

S A sensor’s cover is removed and 20 minutes pass before it is properly secured.

S A sensor’s environmental compensation limit is reached (100% dirty).

S A wiring fault between a sensor and the controller is detected.

An internal sensor fault is detected upon entering the trouble state:

S The contacts on the controller’s supervisory relay switch positions. (See Fig. 28.)

S If a sensor trouble, the sensor’s Trouble LED the controller’s Trouble LED turn on.

S If 100% dirty, the sensor’s Dirty LED turns on and the controller’s Trouble LED flashes continuously.

S If a wiring fault between a sensor and the controller, the controller’s Trouble LED turns on but not the sensor’s.

 

Trouble

Alarm

Power

 

Test/reset

 

switch

 

C07298

Fig. 28 - Controller Assembly

NOTE: All troubles are latched by the duct smoke detector. The trouble condition must be cleared and then the duct smoke detector must be reset in order to restore it to the normal state.

Resetting Alarm and Trouble Condition Trips:

Manual reset is required to restore smoke detector systems to Normal operation. For installations using two sensors, the duct smoke detector does not differentiate which sensor signals an alarm or trouble condition. Check each sensor for Alarm or Trouble status (indicated by LED). Clear the condition that has generated the trip at this sensor. Then reset the sensor by pressing and holding the reset button (on the side) for 2 seconds. Verify that the sensor’s Alarm and Trouble LEDs are now off. At the controller, clear its Alarm or Trouble state by pressing and holding the manual reset button (on the front cover) for 2 seconds. Verify that the controller’s Alarm and Trouble LEDs are now off. Replace all panels.

Troubleshooting

Controller’s Trouble LED is On

1.Check the Trouble LED on each sensor connected to the controller. If a sensor’s Trouble LED is on, de- termine the cause and make the necessary repairs.

2.Check the wiring between the sensor and the control- ler. If wiring is loose or missing, repair or replace as required.

Controller’s Trouble LED is Flashing

1.One or both of the sensors is 100% dirty.

2.Determine which Dirty LED is flashing then clean that sensor assembly as described in the detector cleaning section.

Sensor’s Trouble LED is On

1.Check the sensor’s Dirty LED. If it is flashing, the sensor is dirty and must be cleaned.

2.Check the sensor’s cover. If it is loose or missing, se- cure the cover to the sensor housing.

3.Replace sensor assembly.

Sensor’s Power LED is Off

1.Check the controller’s Power LED. If it is off, de- termine why the controller does not have power and make the necessary repairs.

2.Check the wiring between the sensor and the control- ler. If wiring is loose or missing, repair or replace as required.

48TC

23

Image 23
Contents Safety Considerations Table of ContentsWhat to do if you smell gas Unit Arrangement and AccessGeneral Seasonal Maintenance Routine MaintenanceManual Outside Air Hood Screen Supply FAN Blower SectionSupply Fan Belt-Drive Supply-Fan Pulley Adjustment Bearings Adjustable-Pitch Pulley on MotorCondenser Coil Coil Maintenance and Cleaning RecommendationPeriodic Clean Water Rinse CoolingRoutine Cleaning of Evaporator Coil Sufaces Routine Cleaning of Novation Condenser Coil SurfacesRefrigerant Charge Refrigerant System Pressure Access PortsPuronr R-410A Refrigerant Seatcore Cooling Charging Charts D08 Cooling Charging ChartsCooling Charging Charts D12 Cooling Charging Charts D14 Circuit a Cooling Charging Charts D14 Circuit B Problem Cause Remedy Cooling Service AnalysisCompressors Condenser-Fan Adjustment D08-D12 sizeCondenser-Fan Adjustment D14 size Troubleshooting Cooling SystemDuty Cycle Non-Powered TypeUnit-Powered Type Convenience OutletsSmoke Detectors Typical Supply Air Smoke Detector Sensor Location Smoke Detector LocationsFiop Smoke Detector Wiring and Response Completing Installation of Return Air Smoke SensorSensor and Controller Tests Sensor Alarm TestSensor Alarm Test Procedure Controller Alarm TestTo Configure the Dirty Sensor Test Operation Controller Alarm Test ProcedureDirty Controller Test Procedure Dirty Sensor Test ProcedureDirty Sensor Test Using an SD-TRK4 Detector CleaningSD-TRK4 Remote Alarm Test Procedure Remote Test/Reset Station Dirty Sensor TestTroubleshooting Compressor Protection Protective DevicesFuel Types and Pressures GAS Heating SystemControl Circuit Combustion-Air Blower Flue Gas PassagewaysMain Burners Burners and IgnitersLimit Switch Cleaning and AdjustmentCheck Unit Operation and Make Necessary Adjustments Burner Ignition LED Error Code DescriptionLED Indication Error Code Description Gas Valve Orifice ReplacementOutputs Integrated Gas Control IGC Board IGC ConnectionsElevation Orifice SizesAltitude Compensation Orifice Carrier Drill Drill Size Part NumberProblem Cause Remedy Troubleshooting Heating SystemMinimum Heating Entering Air Temperature Heating Service AnalysisIGC IGC Board LED Alarm CodesReplacing Novation Condenser Coil Condenser Coil ServiceRepairing Novation Condenser Tube Leaks PREMIERLINKt Control Typical PremierLinkt System Control Wiring Diagram Temp Resistance 55 Space Temperature Sensor WiringPremierLink Sensor Usage Space Sensor ModeTB1 Terminal Field Connection Input Signal 56 Internal Connections Thermostat ModeLctb Indoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection Color Code Recommendations Signal Type CCN BUS Wire CCN Plug PIN Color NumberRTU-MP Control System Recommended CablesRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram Type of I/O Connection PIN Name Numbers Inputs Configurable InputsRTU-MP Controller Inputs and Outputs Point NameRTU-MP T-55 Sensor Connections Space Temperature SPT SensorsRTU-MP / Indoor CO2 Sensor 33ZCSENCO2 Connections Communication Wiring Protocols Connecting Discrete InputsPower Exhaust output RTU-MP Troubleshooting LEDs BACview6 Handheld ConnectionsTroubleshooting Alarms BACnet MS/TP AlarmsModule Status Report Modstat Example Code Name Meaning Basic Protocol TroubleshootingModbus Manufacture DateEconoMi$er IV Component Locations ECONOMI$ER SystemsEconoMi$er IV Wiring Inputs Outputs EconoMi$erEconoMi$er IV Input/Output Logic Outdoor Dry Bulb Changeover Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor EconoMi$er IV Control ModesOutdoor Enthalpy Changeover Differential Dry Bulb ControlMinimum Position Control Exhaust Setpoint AdjustmentIndoor Air Quality IAQ Sensor Input Demand Control Ventilation DCV Damper MovementThermostats Analog CO2 CO2 Sensor ConfigurationCO2 Sensor Standard Settings Differential Enthalpy DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Sensor Usage EconoMi$er IV PreparationSupply-Air Sensor Input Wiring DiagramsEconoMi$er IV Troubleshooting Completion DCV Minimum and Maximum Position48TC Typical Unit Wiring Diagram Power D08, 208/230-3-60 48TC Typical Unit Wiring Diagram Control D08, 208/230-3-60 Gas Piping PRE-START-UPSTART-UP, General Unit PreparationOutdoor-Air Inlet Screens Internal WiringRefrigerant Service Ports Return-Air FiltersPerform System Check-Out Field Service TestSTART-UP, RTU-MP Control Ventilation Continuous FanConfiguration Heating Lockout Temp Cooling/Econ SAT Low SetptCooling Lockout Temp Heating Heating SAT High SetptIAQ High Reference @ 20mA Power Exhaust SetptT55/56 Override Duration IAQ Low Reference @ 4mAOperating Sequences PremierLinkt Control Supplemental Controls48TC 48TC Number Stages Economizer Available Cooling Stages48TC 48TC Linkage Modes Rooftop Mode Value Linkage ModeScheduling Loadshed Command Gas and Electric Heat UnitsAlways Occupied Default Occupancy RTU-MP Sequence of OperationIndoor Fan BACnet ScheduleBAS On/Off DI On/OffIndoor Air Quality Power ExhaustFastener Torque Values EconomizerTorque Values Position Number Typical Designates Appendix I. Model Number SignificanceModel Number Nomenclature Serial Number Format12.5TONS Appendix II. Physical DataPhysical Data Natural Gas Heat, Liquid Propane Heat Heat Anticipator Setting AmpsPhysical Data Heating 12.5TONS 48TC**08 48TC**12 48TC**14 Gas ConnectionCFM RPM BHP Appendix III. FAN Performance579 FAN PerformanceRPM BHP 48TC**14Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentElectrical Information Type DISC. Size Unit Combustion PowerMCA/MOCP Determination no C.O. or Unpwrd C.O NOM IFM FAN Motor Exhaust No P.ESize Voltage Control Power Appendix IV. Wiring Diagram ListWiring Diagrams Catalog No 48TC-3SM Appendix V. Motormaster Sensor LocationsPreliminary Information Unit START-UP Checklist