Table 14 – IGC Board LED Alarm Codes

LED

DESCRIPTION

ACTION TAKEN BY

RESET METHOD

PROBABLE CAUSE

FLASH

CONTROL

CODE

 

 

 

 

 

 

 

 

 

 

 

 

On

Normal Operation

 

 

 

 

 

 

 

 

 

Loss of power to the IGC. Check 5 amp

Off

Hardware Failure

No gas heating.

fuse on IGC, power to unit, 24V circuit

breaker, transformer, and wiring to the

 

 

 

 

 

 

 

 

IGC.

 

 

 

 

 

 

 

 

 

High temperature limit switch is open.

 

 

Gas valve and igniter

 

Check the operation of the indoor

 

 

 

(evaporator) fan motor.

2

Limit Switch Fault

Off.

Limit switch closed,

Ensure that the supply-air temperature

Flashes

Indoor fan and inducer

or heat call (W) Off.

 

 

On.

 

rise is within the range on the unit

 

 

 

nameplate. Check wiring and limit switch

 

 

 

 

 

 

 

 

operation.

 

 

 

 

 

3

Flame Sense Fault

Indoor fan and inducer

Flame sense normal.

The IGC sensed a flame when the gas

Flashes

On.

Power reset for LED

valve should be closed. Check wiring,

 

 

 

reset.

flame sensor, and gas valve operation.

4

Four Consecutive Limit

No gas heating.

Heat call (W) Off.

4 consecutive limit switch faults within a

Power reset for LED

Flashes

Switch Fault

single call for heat. See Limit Switch Fault.

 

reset.

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit unsuccessfully attempted ignition for

 

 

 

Heat call (W) Off.

15 minutes. Check igniter and flame

5

Ignition Fault

No gas heating.

sensor electrode spacing, gaps, etc.

Power reset for LED

Flashes

Check flame sense and igniter wiring.

 

 

 

reset.

Check gas valve operation and gas

 

 

 

 

 

 

 

 

supply.

 

 

 

 

 

 

 

If heat off: no gas

Inducer sense

Inducer sense On when heat call Off, or

6

Induced Draft Motor

inducer sense Off when heat call On.

heating.

normal, or heat call

Check wiring, voltage, and operation of

Flashes

Fault

If heat on: gas valve

(W) Off.

IGC motor. Check speed sensor wiring to

 

 

Off and inducer On.

 

 

 

IGC.

 

 

 

 

 

 

 

 

 

7

 

Gas valve and igniter

 

Rollout switch has opened. Check gas

Rollout Switch Lockout

Off.

Power reset.

valve operation. Check induced-draft

Flashes

Indoor fan and inducer

blower wheel is properly secured to motor

 

 

On.

 

shaft.

 

 

 

 

 

 

 

 

 

IGC has sensed internal hardware or

8

 

 

 

software error. If fault is not cleared by

Internal Control Lockout

No gas heating.

Power reset.

resetting 24 v power, replace the IGC.

Flashes

 

 

 

 

Check gas valve connections to IGC

 

 

 

 

terminals. BRN lead must be on Pin 11.

 

 

 

 

 

9

Temporary Software

No gas heating.

1 hour auto reset, or

Electrical interference is disrupting the

Flashes

Lockout

power reset.

IGC software.

 

 

 

 

 

 

LEGEND

IGC --- Integrated Gas Unit Control

LED --- Light--- Emitting Diode

NOTES:

1.There is a 3--- second pause between alarm code displays.

2.If more than one alarm code exists, all applicable alarm codes will be displayed in numerical sequence.

3.Alarm codes on the IGC will be lost if power to the unit is interrupted.

34

Image 34
Contents Table of Contents Safety ConsiderationsGeneral Unit Arrangement and AccessWhat to do if you smell gas Routine Maintenance Seasonal MaintenanceSupply Fan Belt-Drive Supply FAN Blower SectionManual Outside Air Hood Screen Adjustable-Pitch Pulley on Motor Supply-Fan Pulley Adjustment BearingsCooling Coil Maintenance and Cleaning RecommendationPeriodic Clean Water Rinse Condenser CoilRoutine Cleaning of Novation Condenser Coil Surfaces Routine Cleaning of Evaporator Coil SufacesPuronr R-410A Refrigerant Refrigerant System Pressure Access PortsRefrigerant Charge Seatcore Cooling Charging Charts Cooling Charging Charts D08Cooling Charging Charts D12 Cooling Charging Charts D14 Circuit a Cooling Charging Charts D14 Circuit B Cooling Service Analysis Problem Cause RemedyTroubleshooting Cooling System Condenser-Fan Adjustment D08-D12 sizeCondenser-Fan Adjustment D14 size CompressorsConvenience Outlets Non-Powered TypeUnit-Powered Type Duty CycleSmoke Detectors Smoke Detector Locations Typical Supply Air Smoke Detector Sensor LocationCompleting Installation of Return Air Smoke Sensor Fiop Smoke Detector Wiring and ResponseController Alarm Test Sensor Alarm TestSensor Alarm Test Procedure Sensor and Controller TestsDirty Sensor Test Procedure Controller Alarm Test ProcedureDirty Controller Test Procedure To Configure the Dirty Sensor Test OperationRemote Test/Reset Station Dirty Sensor Test Detector CleaningSD-TRK4 Remote Alarm Test Procedure Dirty Sensor Test Using an SD-TRK4Troubleshooting Protective Devices Compressor ProtectionControl Circuit GAS Heating SystemFuel Types and Pressures Flue Gas Passageways Combustion-Air BlowerBurners and Igniters Main BurnersCheck Unit Operation and Make Necessary Adjustments Cleaning and AdjustmentLimit Switch LED Indication Error Code Description LED Error Code DescriptionBurner Ignition Orifice Replacement Gas ValveIntegrated Gas Control IGC Board IGC Connections OutputsOrifice Carrier Drill Drill Size Part Number Orifice SizesAltitude Compensation ElevationHeating Service Analysis Troubleshooting Heating SystemMinimum Heating Entering Air Temperature Problem Cause RemedyIGC Board LED Alarm Codes IGCRepairing Novation Condenser Tube Leaks Condenser Coil ServiceReplacing Novation Condenser Coil PREMIERLINKt Control Typical PremierLinkt System Control Wiring Diagram 55 Space Temperature Sensor Wiring Temp ResistanceTB1 Terminal Field Connection Input Signal Space Sensor ModePremierLink Sensor Usage Thermostat Mode 56 Internal ConnectionsLctb Indoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection Recommended Cables Signal Type CCN BUS Wire CCN Plug PIN Color NumberRTU-MP Control System Color Code RecommendationsRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram Point Name Configurable InputsRTU-MP Controller Inputs and Outputs Type of I/O Connection PIN Name Numbers InputsSpace Temperature SPT Sensors RTU-MP T-55 Sensor ConnectionsRTU-MP / Indoor CO2 Sensor 33ZCSENCO2 Connections Power Exhaust output Connecting Discrete InputsCommunication Wiring Protocols RTU-MP Troubleshooting BACview6 Handheld Connections LEDsTroubleshooting Alarms Alarms BACnet MS/TPModule Status Report Modstat Example Manufacture Date Basic Protocol TroubleshootingModbus Code Name MeaningECONOMI$ER Systems EconoMi$er IV Component LocationsEconoMi$er IV Wiring EconoMi$er IV Input/Output Logic EconoMi$erInputs Outputs EconoMi$er IV Control Modes Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor Outdoor Dry Bulb ChangeoverDifferential Dry Bulb Control Outdoor Enthalpy ChangeoverIndoor Air Quality IAQ Sensor Input Exhaust Setpoint AdjustmentMinimum Position Control Thermostats Damper MovementDemand Control Ventilation DCV CO2 Sensor Standard Settings CO2 Sensor ConfigurationAnalog CO2 EconoMi$er IV Preparation DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Sensor Usage Differential EnthalpyDCV Minimum and Maximum Position Wiring DiagramsEconoMi$er IV Troubleshooting Completion Supply-Air Sensor Input48TC Typical Unit Wiring Diagram Power D08, 208/230-3-60 48TC Typical Unit Wiring Diagram Control D08, 208/230-3-60 Unit Preparation PRE-START-UPSTART-UP, General Gas PipingReturn-Air Filters Internal WiringRefrigerant Service Ports Outdoor-Air Inlet ScreensVentilation Continuous Fan Field Service TestSTART-UP, RTU-MP Control Perform System Check-OutConfiguration Heating Heating SAT High Setpt Cooling/Econ SAT Low SetptCooling Lockout Temp Heating Lockout TempIAQ Low Reference @ 4mA Power Exhaust SetptT55/56 Override Duration IAQ High Reference @ 20mAOperating Sequences Supplemental Controls PremierLinkt Control48TC 48TC Available Cooling Stages Number Stages Economizer48TC 48TC Rooftop Mode Value Linkage Mode Linkage ModesRTU-MP Sequence of Operation Loadshed Command Gas and Electric Heat UnitsAlways Occupied Default Occupancy SchedulingDI On/Off BACnet ScheduleBAS On/Off Indoor FanEconomizer Power ExhaustFastener Torque Values Indoor Air QualityTorque Values Serial Number Format Appendix I. Model Number SignificanceModel Number Nomenclature Position Number Typical DesignatesPhysical Data Appendix II. Physical Data12.5TONS 48TC**08 48TC**12 48TC**14 Gas Connection Heat Anticipator Setting AmpsPhysical Data Heating 12.5TONS Natural Gas Heat, Liquid Propane HeatAppendix III. FAN Performance CFM RPM BHPFAN Performance 57948TC**14 RPM BHPPulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboElectrical Information NOM IFM FAN Motor Exhaust No P.E Unit Combustion PowerMCA/MOCP Determination no C.O. or Unpwrd C.O Type DISC. SizeWiring Diagrams Appendix IV. Wiring Diagram ListSize Voltage Control Power Appendix V. Motormaster Sensor Locations Catalog No 48TC-3SMUnit START-UP Checklist Preliminary Information