Carrier 48TC*D08 appendix Troubleshooting Heating System, Minimum Heating Entering Air Temperature

Page 33

Minimum Heating Entering Air Temperature

When operating on first stage heating, the minimum temperature of air entering the dimpled heat exchanger is 50_F continuous and 45_F intermittent for standard heat exchangers and 40_F continuous and 35_F intermittent for stainless steel heat exchangers. To operate at lower mixed-air temperatures, a field-supplied outdoor-air thermostat must be used to initiate both stages of heat when the temperature is below the minimum required temperature to ensure full fire operation. Wire the outdoor-air thermostat OALT (part no. HH22AG106) in series with the second stage gas valve. See Fig. 40. Set the outdoor-air thermostat at 35_F for stainless steel heat exchangers or 45_F for standard heat exchangers. This temperature setting will bring on the second stage of heat whenever the ambient temperature is below the thermostat setpoint. Indoor comfort may be compromised when heating is initiated using low entering air temperatures with insufficient heating temperature rise.

Thermostat

LCTB

TH1

W1

W1

 

OALT

TH2

 

W2

W2

C08442

Fig. 40 - OATL Connections

Troubleshooting Heating System

Refer to Table 13 and 14 for additional troubleshooting topics.

48TC

 

Table 13 – Heating Service Analysis

 

 

 

PROBLEM

CAUSE

REMEDY

 

Misaligned spark electrodes.

Check flame ignition and sensor electrode positioning.

 

Adjust as needed.

 

 

 

 

 

 

 

Check gas line for air, purge as necessary. After purging

 

No gas at main burners.

gas line of air, allow gas to dissipate for at least 5 minutes

 

before attempting to relight unit.

 

 

 

 

 

 

 

Check gas valve.

Burners Will Not Ignite.

Water in gas line.

Drain water and install drip leg to trap water.

 

 

No power to furnace.

Check power supply, fuses, wiring, and circuit breaker.

 

 

No 24 v power supply to control

Check transformer. Transformers with internal overcurrent

 

circuit.

protection require a cool down period before resetting.

 

 

 

 

Miswired or loose connections.

Check all wiring and wire nut connections.

 

 

 

 

Burned---out heat anticipator in

Replace thermostat.

 

thermostat.

 

 

 

 

 

 

Broken thermostat wires.

Run continuity check. Replace wires, if necessary.

 

Dirty air filter.

Clean or replace filter as necessary.

 

 

 

 

Gas input to unit too low.

Check gas pressure at manifold. Clock gas meter for input.

 

If too low, increase manifold pressure, or replace with

 

 

correct orifices.

 

 

 

 

Unit undersized for application.

Replace with proper unit or add additional unit.

Inadequate Heating.

Restricted airflow.

Clean filter, replace filter, or remove any restrictions.

 

 

Blower speed too low.

Use high speed tap, increase fan speed, or install optional

 

 

blower, as suitable for individual units.

 

 

 

 

 

 

Limit switch cycles main burners.

Check rotation of blower, thermostat heat anticipator

 

settings, and temperature rise of unit. Adjust as needed.

 

 

 

 

 

 

Too much outdoor air.

Adjust minimum position.

 

 

 

Check economizer operation.

 

 

 

 

Check all screws around flue outlets and burner

 

Incomplete combustion (lack of

compartment. Tighten as necessary.

 

 

Poor Flame

Cracked heat exchanger.

combustion air) results in:

 

Overfired unit — reduce input, change orifices, or adjust

Characteristics.

Aldehyde odors, CO, sooting

gas line or manifold pressure.

 

flame, or floating flame.

 

 

 

Check vent for restriction. Clean as necessary.

 

 

 

 

Check orifice to burner alignment.

 

 

 

Burners Will Not Turn

Unit is locked into Heating mode

Wait until mandatory one---minute time period has elapsed

Off.

for a one minute minimum.

or reset power to unit.

 

 

 

33

Image 33
Contents Safety Considerations Table of ContentsUnit Arrangement and Access GeneralWhat to do if you smell gas Seasonal Maintenance Routine MaintenanceSupply FAN Blower Section Supply Fan Belt-DriveManual Outside Air Hood Screen Supply-Fan Pulley Adjustment Bearings Adjustable-Pitch Pulley on MotorPeriodic Clean Water Rinse Coil Maintenance and Cleaning RecommendationCooling Condenser CoilRoutine Cleaning of Evaporator Coil Sufaces Routine Cleaning of Novation Condenser Coil SurfacesRefrigerant System Pressure Access Ports Puronr R-410A RefrigerantRefrigerant Charge Seatcore Cooling Charging Charts D08 Cooling Charging ChartsCooling Charging Charts D12 Cooling Charging Charts D14 Circuit a Cooling Charging Charts D14 Circuit B Problem Cause Remedy Cooling Service AnalysisCondenser-Fan Adjustment D14 size Condenser-Fan Adjustment D08-D12 sizeTroubleshooting Cooling System CompressorsUnit-Powered Type Non-Powered TypeConvenience Outlets Duty CycleSmoke Detectors Typical Supply Air Smoke Detector Sensor Location Smoke Detector LocationsFiop Smoke Detector Wiring and Response Completing Installation of Return Air Smoke SensorSensor Alarm Test Procedure Sensor Alarm TestController Alarm Test Sensor and Controller TestsDirty Controller Test Procedure Controller Alarm Test ProcedureDirty Sensor Test Procedure To Configure the Dirty Sensor Test OperationSD-TRK4 Remote Alarm Test Procedure Detector CleaningRemote Test/Reset Station Dirty Sensor Test Dirty Sensor Test Using an SD-TRK4Troubleshooting Compressor Protection Protective DevicesGAS Heating System Control CircuitFuel Types and Pressures Combustion-Air Blower Flue Gas PassagewaysMain Burners Burners and IgnitersCleaning and Adjustment Check Unit Operation and Make Necessary AdjustmentsLimit Switch LED Error Code Description LED Indication Error Code DescriptionBurner Ignition Gas Valve Orifice ReplacementOutputs Integrated Gas Control IGC Board IGC ConnectionsAltitude Compensation Orifice SizesOrifice Carrier Drill Drill Size Part Number ElevationMinimum Heating Entering Air Temperature Troubleshooting Heating SystemHeating Service Analysis Problem Cause RemedyIGC IGC Board LED Alarm CodesCondenser Coil Service Repairing Novation Condenser Tube LeaksReplacing Novation Condenser Coil PREMIERLINKt Control Typical PremierLinkt System Control Wiring Diagram Temp Resistance 55 Space Temperature Sensor WiringSpace Sensor Mode TB1 Terminal Field Connection Input SignalPremierLink Sensor Usage 56 Internal Connections Thermostat ModeLctb Indoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection RTU-MP Control System Signal Type CCN BUS Wire CCN Plug PIN Color NumberRecommended Cables Color Code RecommendationsRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs Configurable InputsPoint Name Type of I/O Connection PIN Name Numbers InputsRTU-MP T-55 Sensor Connections Space Temperature SPT SensorsRTU-MP / Indoor CO2 Sensor 33ZCSENCO2 Connections Connecting Discrete Inputs Power Exhaust outputCommunication Wiring Protocols RTU-MP Troubleshooting LEDs BACview6 Handheld ConnectionsTroubleshooting Alarms BACnet MS/TP AlarmsModule Status Report Modstat Example Modbus Basic Protocol TroubleshootingManufacture Date Code Name MeaningEconoMi$er IV Component Locations ECONOMI$ER SystemsEconoMi$er IV Wiring EconoMi$er EconoMi$er IV Input/Output LogicInputs Outputs Outdoor Air Lockout Sensor Supply Air Temperature SAT SensorEconoMi$er IV Control Modes Outdoor Dry Bulb ChangeoverOutdoor Enthalpy Changeover Differential Dry Bulb ControlExhaust Setpoint Adjustment Indoor Air Quality IAQ Sensor InputMinimum Position Control Damper Movement ThermostatsDemand Control Ventilation DCV CO2 Sensor Configuration CO2 Sensor Standard SettingsAnalog CO2 EconoMi$er IV Sensor Usage DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Preparation Differential EnthalpyEconoMi$er IV Troubleshooting Completion Wiring DiagramsDCV Minimum and Maximum Position Supply-Air Sensor Input48TC Typical Unit Wiring Diagram Power D08, 208/230-3-60 48TC Typical Unit Wiring Diagram Control D08, 208/230-3-60 START-UP, General PRE-START-UPUnit Preparation Gas PipingRefrigerant Service Ports Internal WiringReturn-Air Filters Outdoor-Air Inlet ScreensSTART-UP, RTU-MP Control Field Service TestVentilation Continuous Fan Perform System Check-OutConfiguration Cooling Lockout Temp Cooling/Econ SAT Low SetptHeating Heating SAT High Setpt Heating Lockout TempT55/56 Override Duration Power Exhaust SetptIAQ Low Reference @ 4mA IAQ High Reference @ 20mAOperating Sequences PremierLinkt Control Supplemental Controls48TC 48TC Number Stages Economizer Available Cooling Stages48TC 48TC Linkage Modes Rooftop Mode Value Linkage ModeAlways Occupied Default Occupancy Loadshed Command Gas and Electric Heat UnitsRTU-MP Sequence of Operation SchedulingBAS On/Off BACnet ScheduleDI On/Off Indoor FanFastener Torque Values Power ExhaustEconomizer Indoor Air QualityTorque Values Model Number Nomenclature Appendix I. Model Number SignificanceSerial Number Format Position Number Typical DesignatesAppendix II. Physical Data Physical Data12.5TONS Physical Data Heating 12.5TONS Heat Anticipator Setting Amps48TC**08 48TC**12 48TC**14 Gas Connection Natural Gas Heat, Liquid Propane HeatCFM RPM BHP Appendix III. FAN Performance579 FAN PerformanceRPM BHP 48TC**14Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentElectrical Information MCA/MOCP Determination no C.O. or Unpwrd C.O Unit Combustion PowerNOM IFM FAN Motor Exhaust No P.E Type DISC. SizeAppendix IV. Wiring Diagram List Wiring DiagramsSize Voltage Control Power Catalog No 48TC-3SM Appendix V. Motormaster Sensor LocationsPreliminary Information Unit START-UP Checklist