Condenser Fan Motor Protection
The condenser fan motor is internally protected against overtemperature.
Control Circuit, 24-V
The control circuit is protected against overcurrent conditions by a circuit breaker mounted on control transformer TRAN. Reset is manual.
GAS HEATING SYSTEM
General
The heat exchanger system consists of a gas valve feeding multiple inshot burners off a manifold. The burners fire into matching primary tubes. The primary tubes discharge into combustion plenum where gas flow converges into secondary tubes. The secondary tubes exit into the induced draft fan wheel inlet. The induced fan wheel discharges into a flue passage and flue gases exit out a flue hood on the side of the unit. The induced draft fan motor includes a Hall Effect sensor circuit that confirms adequate wheel speed via the Integrated Gas Control (IGC) board. Safety switches include a Rollout Switch (at the top of the burner compartment) and a limit switch (mounted through the fan deck, over the tubes). (See Fig. 29 and 30.)
INDUCED- |
| |
DRAFT |
| |
MOTOR | ROLLOUT | |
MOUNTING | ||
SWITCH | ||
PLATE | ||
| ||
BURNER | FLUE | |
SECTION | EXHAUST | |
INDUCED- | VESTIBULE | |
DRAFT MOTOR | PLATE | |
MANIFOLD |
| |
PRESSURE |
| |
TAP |
| |
GAS | BLOWER | |
VALVE | HOUSING | |
| C09153 |
Fig. 29 - Burner Section Details
Limit Switch |
and Shield |
C08284
Fig. 30 - Limit Switch Location
Fuel Types and Pressures
Natural Gas — The 48TC unit is
Gas line pressure entering the unit’s main gas valve must be within specified ranges. Adjust unit gas regulator valve as required or consult local gas utility.
Table 5 – Natural Gas Supply Line Pressure Ranges
UNIT MODEL | UNIT SIZE | MIN | MAX | |
|
|
|
| |
48TC | All | 4.0 in. wg | 13.0 in. wg | |
(996 Pa) | (3240 Pa) | |||
|
| |||
|
|
|
|
Manifold pressure is
Table 6 – Natural Gas Manifold Pressure Ranges
UNIT | UNIT | HIGH | LOW | RANGE | |
MODEL | SIZE | FIRE | FIRE | ||
| |||||
|
|
|
|
| |
48TC | All | 3.5 in. wg | 1.7 in. wg | ||
(872 Pa) | (423 Pa) | ||||
|
| ||||
|
|
|
|
|
Liquid Propane — Accessory packages are available for
Fuel line pressure entering unit gas valve must remain within specified range.
Table 7 – Liquid Propane Supply Line Pressure Ranges
UNIT MODEL | UNIT SIZE | MIN | MAX | |
48TC | All | 11.0 in. wg | 13.0 in. wg | |
(2740 Pa) | (3240 Pa) | |||
|
| |||
|
|
|
|
Manifold pressure for LP fuel use must be adjusted to specified range. Follow instructions in the accessory kit to make initial readjustment.
Table 8 – Liquid Propane Manifold Pressure Ranges
UNIT MODEL | UNIT SIZE | HIGH FIRE | LOW FIRE | |
48TC | All | 10.0 in. wg | 5.0 in. wg | |
(2490 Pa) | (1245 Pa) | |||
|
| |||
|
|
|
|
Supply Pressure Switch — The LP conversion kit includes a supply low pressure switch. The switch contacts (from terminal C to terminal NO) will open the gas valve power whenever the supply line pressure drops below the setpoint. (See Fig. 31 and 32.) If the low pressure remains open for 15 minutes during a call for heat, the IGC circuit will initiate a Ignition Fault (5 flashes) lockout. Reset of the low pressure switch is automatic on rise in supply line pressure. Reset of the IGC requires a recycle of unit power after the low pressure switch has closed.
48TC
25