Carrier 48TC*D08 appendix Space Temperature Sensor Wiring, Temp Resistance

Page 38

48TC

Table 15 – Thermistor Resistance vs Temperature Values for Space Temperature Sensor, Supply Air Temperature Sensor, and Outdoor Air Temperature Sensor

TEMP

TEMP

RESISTANCE

(C)

(F)

(Ohms)

---40

---40

335,651

---35

---31

242,195

 

 

 

---30

---22

176,683

---25

---13

130,243

---20

---4

96,974

 

 

 

---15

5

72,895

---10

14

55,298

 

 

 

---5

23

42,315

 

 

 

0

32

32,651

5

41

25,395

 

 

 

10

50

19,903

15

59

15,714

20

68

12,494

 

 

 

25

77

10,000

30

86

8,056

35

95

6,530

 

 

 

40

104

5,325

45

113

4,367

 

 

 

50

122

3,601

 

 

 

55

131

2,985

60

140

2,487

 

 

 

65

149

2,082

 

 

 

70

158

1,752

NOTE: The sensor must be mounted in the discharge airstream downstream of the cooling coil and any heating devices. Be sure the probe tip does not come in contact with any of the unit’s heater surfaces.

Outdoor Air Temperature (OAT) Sensor — The OAT is factory-mounted in the EconoMi$er 2 (FIOP or accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring. See Table 15 for temperature-resistance characteristic.

EconoMi$er 2 — The PremierLink control is used with EconoMi$er 2 (option or accessory) for outdoor air management. The damper position is controlled directly by the PremierLink control; EconoMi$er 2 has no internal logic device.

Outdoor air management functions can be enhanced with field-installation of these accessory control devices:

Enthalpy control (outdoor air or differential sensors) Space CO2 sensor

Outdoor air CO2 sensor

Refer to Table 16 for accessory part numbers.

Field connections — Field connections for accessory sensor and input devices are made at the 16-pole terminal block (TB1) located on the control box bottom shelf in front of the PremierLink control. Some input devices also require a 24-vac signal source; connect at LCTB terminal R at “THERMOSTAT” connection strip for this signal source. See connections figures on following pages for field connection locations (and for continued connections at the PremierLink board inputs).

Table 17 provides a summary of field connections for units equipped with Space Sensor. Table 18 provides a summary of field connections for units equipped with Space Thermostat.

Space Sensors — The PremierLink controller is factory-shipped configured for Space Sensor Mode. A Carrier T-55 or T-56 space sensor must be used. T-55 space temperature sensor provides a signal of space temperature to the PremierLink control T-56 provides same space temperature signal plus it allows for adjustment of space temperature setpoints from the face of the sensor by the occupants. See Table 15 for temperature versus resistance characteristic on the space sensors.

Connect T-55 — See Fig. 44 for typical T-55 internal connections. Connect the T-55 SEN terminals to TB1 terminals 1 and 3 (see Fig. 45).

1

2

3

4

5

6

RED(+)

 

 

 

 

 

 

WHT(GND)

CCN COM

 

 

 

 

 

 

BLK(-)

 

 

 

 

 

 

 

 

 

 

SEN

 

 

 

 

 

SW1

 

 

 

 

 

 

 

 

 

 

 

BRN (GND)

SENSOR WIRING

 

 

 

 

 

BLU (SPT)

 

C08201

Fig. 44 - T-55 Space Temperature Sensor Wiring

TB1PL

SEN 1 J6-7

SEN 3 J6-6

C08212

Fig. 45 - PremierLink T-55 Sensor

38

Image 38
Contents Table of Contents Safety ConsiderationsWhat to do if you smell gas Unit Arrangement and AccessGeneral Routine Maintenance Seasonal MaintenanceManual Outside Air Hood Screen Supply FAN Blower SectionSupply Fan Belt-Drive Adjustable-Pitch Pulley on Motor Supply-Fan Pulley Adjustment BearingsCooling Coil Maintenance and Cleaning RecommendationPeriodic Clean Water Rinse Condenser CoilRoutine Cleaning of Novation Condenser Coil Surfaces Routine Cleaning of Evaporator Coil SufacesRefrigerant Charge Refrigerant System Pressure Access PortsPuronr R-410A Refrigerant Seatcore Cooling Charging Charts Cooling Charging Charts D08Cooling Charging Charts D12 Cooling Charging Charts D14 Circuit a Cooling Charging Charts D14 Circuit B Cooling Service Analysis Problem Cause RemedyTroubleshooting Cooling System Condenser-Fan Adjustment D08-D12 sizeCondenser-Fan Adjustment D14 size CompressorsConvenience Outlets Non-Powered TypeUnit-Powered Type Duty CycleSmoke Detectors Smoke Detector Locations Typical Supply Air Smoke Detector Sensor LocationCompleting Installation of Return Air Smoke Sensor Fiop Smoke Detector Wiring and ResponseController Alarm Test Sensor Alarm TestSensor Alarm Test Procedure Sensor and Controller TestsDirty Sensor Test Procedure Controller Alarm Test ProcedureDirty Controller Test Procedure To Configure the Dirty Sensor Test OperationRemote Test/Reset Station Dirty Sensor Test Detector CleaningSD-TRK4 Remote Alarm Test Procedure Dirty Sensor Test Using an SD-TRK4Troubleshooting Protective Devices Compressor ProtectionFuel Types and Pressures GAS Heating SystemControl Circuit Flue Gas Passageways Combustion-Air BlowerBurners and Igniters Main BurnersLimit Switch Cleaning and AdjustmentCheck Unit Operation and Make Necessary Adjustments Burner Ignition LED Error Code DescriptionLED Indication Error Code Description Orifice Replacement Gas ValveIntegrated Gas Control IGC Board IGC Connections OutputsOrifice Carrier Drill Drill Size Part Number Orifice SizesAltitude Compensation ElevationHeating Service Analysis Troubleshooting Heating SystemMinimum Heating Entering Air Temperature Problem Cause RemedyIGC Board LED Alarm Codes IGCReplacing Novation Condenser Coil Condenser Coil ServiceRepairing Novation Condenser Tube Leaks PREMIERLINKt Control Typical PremierLinkt System Control Wiring Diagram 55 Space Temperature Sensor Wiring Temp ResistancePremierLink Sensor Usage Space Sensor ModeTB1 Terminal Field Connection Input Signal Thermostat Mode 56 Internal ConnectionsLctb Indoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection Recommended Cables Signal Type CCN BUS Wire CCN Plug PIN Color NumberRTU-MP Control System Color Code RecommendationsRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram Point Name Configurable InputsRTU-MP Controller Inputs and Outputs Type of I/O Connection PIN Name Numbers InputsSpace Temperature SPT Sensors RTU-MP T-55 Sensor ConnectionsRTU-MP / Indoor CO2 Sensor 33ZCSENCO2 Connections Communication Wiring Protocols Connecting Discrete InputsPower Exhaust output RTU-MP Troubleshooting BACview6 Handheld Connections LEDsTroubleshooting Alarms Alarms BACnet MS/TPModule Status Report Modstat Example Manufacture Date Basic Protocol TroubleshootingModbus Code Name MeaningECONOMI$ER Systems EconoMi$er IV Component LocationsEconoMi$er IV Wiring Inputs Outputs EconoMi$erEconoMi$er IV Input/Output Logic EconoMi$er IV Control Modes Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor Outdoor Dry Bulb ChangeoverDifferential Dry Bulb Control Outdoor Enthalpy ChangeoverMinimum Position Control Exhaust Setpoint AdjustmentIndoor Air Quality IAQ Sensor Input Demand Control Ventilation DCV Damper MovementThermostats Analog CO2 CO2 Sensor ConfigurationCO2 Sensor Standard Settings EconoMi$er IV Preparation DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Sensor Usage Differential EnthalpyDCV Minimum and Maximum Position Wiring DiagramsEconoMi$er IV Troubleshooting Completion Supply-Air Sensor Input48TC Typical Unit Wiring Diagram Power D08, 208/230-3-60 48TC Typical Unit Wiring Diagram Control D08, 208/230-3-60 Unit Preparation PRE-START-UPSTART-UP, General Gas PipingReturn-Air Filters Internal WiringRefrigerant Service Ports Outdoor-Air Inlet ScreensVentilation Continuous Fan Field Service TestSTART-UP, RTU-MP Control Perform System Check-OutConfiguration Heating Heating SAT High Setpt Cooling/Econ SAT Low SetptCooling Lockout Temp Heating Lockout TempIAQ Low Reference @ 4mA Power Exhaust SetptT55/56 Override Duration IAQ High Reference @ 20mAOperating Sequences Supplemental Controls PremierLinkt Control48TC 48TC Available Cooling Stages Number Stages Economizer48TC 48TC Rooftop Mode Value Linkage Mode Linkage ModesRTU-MP Sequence of Operation Loadshed Command Gas and Electric Heat UnitsAlways Occupied Default Occupancy SchedulingDI On/Off BACnet ScheduleBAS On/Off Indoor FanEconomizer Power ExhaustFastener Torque Values Indoor Air QualityTorque Values Serial Number Format Appendix I. Model Number SignificanceModel Number Nomenclature Position Number Typical Designates12.5TONS Appendix II. Physical DataPhysical Data 48TC**08 48TC**12 48TC**14 Gas Connection Heat Anticipator Setting AmpsPhysical Data Heating 12.5TONS Natural Gas Heat, Liquid Propane HeatAppendix III. FAN Performance CFM RPM BHPFAN Performance 57948TC**14 RPM BHPPulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboElectrical Information NOM IFM FAN Motor Exhaust No P.E Unit Combustion PowerMCA/MOCP Determination no C.O. or Unpwrd C.O Type DISC. SizeSize Voltage Control Power Appendix IV. Wiring Diagram ListWiring Diagrams Appendix V. Motormaster Sensor Locations Catalog No 48TC-3SMUnit START-UP Checklist Preliminary Information