HEATER TUBE
ASSEMBLY
SEAL STRIPS,
SPONGE RUBBER
REGULATOR
GASKET
REGULATOR
RETAINER
WIND CAP ASSEMBLY (SHOWN INVERTED, AS SHIPPED)
SUPPORT INSULATION ASSEMBLY
INDUCER
BURNER ASSEMBLY
C08227
Fig. 33 - Heat Exchanger Assembly
48TC
Burners and Igniters
!CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
When working on gas train, do not hit or plug orifice spuds.
ORIFICE
(25.4 mm)
MANIFOLD
PIPE
C08211
Main Burners
To access burners, remove burner access panel and slide out burner partition. At the beginning of each heating season, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames and adjust, if necessary.
Orifice projection — Refer to Fig. 34 for maximum projection dimension for orifice face to manifold tube.
Fig. 34 - Orifice Projection
Removal and Replacement of Gas Train
See Fig. 29, 33, and 35.
1.Shut off manual gas valve.
2.Shut off power to unit.
3.Slide out burner partition.
4.Disconnect gas piping at unit gas valve.
5.Remove wires connected to gas valve. Mark each wire.
27