125,000/90,000 BTUH INPUT
180,000/120,000 BTUH INPUT
240,000/180,000 BTUH INPUT 250,000/200,000 BTUH INPUT
C08447
Fig. 37 - Spark Adjustment (08-14)
48TC
Burner Ignition
Unit is equipped with a direct spark ignition 100% lockout system. Integrated Gas Unit Controller (IGC) is located in the control box. (See Fig. 36.) The IGC contains a
If lockout occurs, unit may be reset by interrupting power supply to unit for at least 5 seconds.
Table 9 – LED Error Code Description*
LED INDICATION | ERROR CODE | |
DESCRIPTION | ||
| ||
|
| |
ON | Normal Operation | |
|
| |
OFF | Hardware Failure | |
|
| |
2 Flashes | Limit Switch Fault | |
|
| |
3 Flashes | Flame Sense Fault | |
|
| |
4 Flashes | 4 Consecutive Limit Switch Faults | |
|
| |
5 Flashes | Ignition Lockout Fault | |
|
| |
6 Flashes | ||
|
| |
7 Flashes | Rollout Switch Fault | |
|
| |
8 Flashes | Internal Control Fault | |
|
| |
9 Flashes | Software Lockout | |
|
|
LEGEND
LED
*A 3 – second pause exists between LED error code flashes. If more than one error code exists, all applicable codes will be displayed in numerical sequence.
IMPORTANT: Refer to Troubleshooting Tables 13 and 14 for additional information.
29