Table 27 – EconoMi$er IV Input/Output Logic
|
|
|
|
|
|
|
|
| |
| INPUTS |
|
|
|
|
| OUTPUTS |
| |
Demand Control | Enthalpy* |
|
|
| Compressor | N Terminal† | |||
Outdoor | Return | Y1 | Y2 | Stage | Stage | Occupied | Unoccupied | ||
Ventilation (DCV) | |||||||||
|
| 1 | 2 | Damper | |||||
|
|
|
|
| |||||
| High | Low | On | On | On | On | Minimum position | Closed | |
| (Free Cooling LED | On | Off | On | Off | ||||
| Off) |
|
|
|
|
|
|
| |
Below set |
| Off | Off | Off | Off |
|
| ||
|
| On | On | On | Off | Modulating** (between | Modulating** | ||
(DCV LED Off) | Low |
| |||||||
High | min. position and | (between closed and | |||||||
| (Free Cooling LED |
|
|
|
| ||||
| On | Off | Off | Off | |||||
| |||||||||
| On) |
|
|
|
|
|
|
| |
|
| Off | Off | Off | Off | Minimum position | Closed | ||
|
|
| |||||||
| High |
| On | On | On | On | Modulating†† (between | Modulating†† | |
|
|
|
|
|
| (between closed and | |||
| (Free Cooling LED | Low | On | Off | On | Off | min. position and DCV | ||
| DCV | ||||||||
Above set | Off) |
|
|
|
|
| maximum) | ||
| Off | Off | Off | Off | maximum) | ||||
(DCV LED On) |
|
|
|
|
|
|
|
| |
Low | High | On | On | On | Off | Modulating*** | Modulating††† | ||
| |||||||||
| (Free Cooling LED |
|
|
|
| ||||
| On | Off | Off | Off | |||||
| On) |
|
|
|
|
|
|
| |
|
| Off | Off | Off | Off |
|
|
*For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint.
†Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied). ** Modulation is based on the
†† Modulation is based on the DCV signal.
*** Modulation is based on the greater of DCV and
††† Modulation is based on the greater of DCV and
48TC
C06053
Fig. 75 - EconoMi$er IV Functional View
EconoMi$er IV
Table 27 provides a summary of EconoMi$er IV. Troubleshooting instructions are enclosed.
A functional view of the EconoMi$er is shown in Fig. 75. Typical settings, sensor ranges, and jumper positions are also shown. An EconoMi$er IV simulator program is available from Carrier to help with EconoMi$er IV training and troubleshooting.
EconoMi$er IV Standard Sensors
Outdoor Air Temperature (OAT) Sensor
The outdoor air temperature sensor (HH57AC074) is a 10 to 20 mA device used to measure the