48TC
C07170
| Fig. 69 - BACview6 Handheld Connections | |
|
| Table 22 – LEDs |
| The LEDs on the | |
|
|
|
If this LED is on... |
| Status is... |
Power |
| The RTU MP has power |
Rx |
| The RTU MP is receiving data from the network segment |
Tx |
| The RTU MP is transmitting data over the network segment |
DO# |
| The digital output is active |
The Run and Error LEDs indicate control module and network status
If Run LED shows... | And Error LED shows... | Status is... | |
2 flashes per second | Off | Normal | |
2 flashes per second | 2 flashes, | Five minute | |
alternating with Run LED | system error | ||
| |||
2 flashes per second | 3 flashes, | Control module has just been | |
then off | formatted | ||
| |||
2 flashes per second | 4 flashes, | Two or more devices on this network | |
then pause | have the same ARC156 network address | ||
| |||
2 flashes per second | On | Exec halted after frequent system errors | |
or control programs halted | |||
|
| ||
5 flashes per second | On | Exec | |
5 flashes per second | Off | Firmware transfer in progress, Boot is | |
running | |||
|
| ||
7 flashes per second | 7 flashes per second, alternating with | Ten second recovery period after | |
Run LED | brownout | ||
| |||
14 flashes per second | 14 flashes per second, | Brownout | |
alternating with Run LED | |||
|
| ||
|
| Failure. Try the following solutions: | |
|
| S Turn the | |
On | On | S Format the | |
|
| S Download memory to the | |
|
| S Replace the |
52