Carrier 48TC*D08 appendix BACview6 Handheld Connections, LEDs

Page 52

48TC

C07170

 

Fig. 69 - BACview6 Handheld Connections

 

 

Table 22 – LEDs

 

The LEDs on the RTU-MP show the status of certain functions

 

 

 

If this LED is on...

 

Status is...

Power

 

The RTU MP has power

Rx

 

The RTU MP is receiving data from the network segment

Tx

 

The RTU MP is transmitting data over the network segment

DO#

 

The digital output is active

The Run and Error LEDs indicate control module and network status

If Run LED shows...

And Error LED shows...

Status is...

2 flashes per second

Off

Normal

2 flashes per second

2 flashes,

Five minute auto---restart delay after

alternating with Run LED

system error

 

2 flashes per second

3 flashes,

Control module has just been

then off

formatted

 

2 flashes per second

4 flashes,

Two or more devices on this network

then pause

have the same ARC156 network address

 

2 flashes per second

On

Exec halted after frequent system errors

or control programs halted

 

 

5 flashes per second

On

Exec start---up aborted, Boot is running

5 flashes per second

Off

Firmware transfer in progress, Boot is

running

 

 

7 flashes per second

7 flashes per second, alternating with

Ten second recovery period after

Run LED

brownout

 

14 flashes per second

14 flashes per second,

Brownout

alternating with Run LED

 

 

 

 

Failure. Try the following solutions:

 

 

S Turn the RTU---MP off, then on.

On

On

S Format the RTU---MP.

 

 

S Download memory to the RTU---MP.

 

 

S Replace the RTU---MP.

52

Image 52
Contents Table of Contents Safety ConsiderationsGeneral Unit Arrangement and AccessWhat to do if you smell gas Routine Maintenance Seasonal MaintenanceSupply Fan Belt-Drive Supply FAN Blower SectionManual Outside Air Hood Screen Adjustable-Pitch Pulley on Motor Supply-Fan Pulley Adjustment BearingsCoil Maintenance and Cleaning Recommendation Periodic Clean Water RinseCooling Condenser CoilRoutine Cleaning of Novation Condenser Coil Surfaces Routine Cleaning of Evaporator Coil SufacesPuronr R-410A Refrigerant Refrigerant System Pressure Access PortsRefrigerant Charge Seatcore Cooling Charging Charts Cooling Charging Charts D08Cooling Charging Charts D12 Cooling Charging Charts D14 Circuit a Cooling Charging Charts D14 Circuit B Cooling Service Analysis Problem Cause RemedyCondenser-Fan Adjustment D08-D12 size Condenser-Fan Adjustment D14 sizeTroubleshooting Cooling System CompressorsNon-Powered Type Unit-Powered TypeConvenience Outlets Duty CycleSmoke Detectors Smoke Detector Locations Typical Supply Air Smoke Detector Sensor LocationCompleting Installation of Return Air Smoke Sensor Fiop Smoke Detector Wiring and ResponseSensor Alarm Test Sensor Alarm Test ProcedureController Alarm Test Sensor and Controller TestsController Alarm Test Procedure Dirty Controller Test ProcedureDirty Sensor Test Procedure To Configure the Dirty Sensor Test OperationDetector Cleaning SD-TRK4 Remote Alarm Test ProcedureRemote Test/Reset Station Dirty Sensor Test Dirty Sensor Test Using an SD-TRK4Troubleshooting Protective Devices Compressor ProtectionControl Circuit GAS Heating SystemFuel Types and Pressures Flue Gas Passageways Combustion-Air BlowerBurners and Igniters Main BurnersCheck Unit Operation and Make Necessary Adjustments Cleaning and AdjustmentLimit Switch LED Indication Error Code Description LED Error Code DescriptionBurner Ignition Orifice Replacement Gas ValveIntegrated Gas Control IGC Board IGC Connections OutputsOrifice Sizes Altitude CompensationOrifice Carrier Drill Drill Size Part Number ElevationTroubleshooting Heating System Minimum Heating Entering Air TemperatureHeating Service Analysis Problem Cause RemedyIGC Board LED Alarm Codes IGCRepairing Novation Condenser Tube Leaks Condenser Coil ServiceReplacing Novation Condenser Coil PREMIERLINKt Control Typical PremierLinkt System Control Wiring Diagram 55 Space Temperature Sensor Wiring Temp ResistanceTB1 Terminal Field Connection Input Signal Space Sensor ModePremierLink Sensor Usage Thermostat Mode 56 Internal ConnectionsLctb Indoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection Signal Type CCN BUS Wire CCN Plug PIN Color Number RTU-MP Control SystemRecommended Cables Color Code RecommendationsRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram Configurable Inputs RTU-MP Controller Inputs and OutputsPoint Name Type of I/O Connection PIN Name Numbers InputsSpace Temperature SPT Sensors RTU-MP T-55 Sensor ConnectionsRTU-MP / Indoor CO2 Sensor 33ZCSENCO2 Connections Power Exhaust output Connecting Discrete InputsCommunication Wiring Protocols RTU-MP Troubleshooting BACview6 Handheld Connections LEDsTroubleshooting Alarms Alarms BACnet MS/TPModule Status Report Modstat Example Basic Protocol Troubleshooting ModbusManufacture Date Code Name MeaningECONOMI$ER Systems EconoMi$er IV Component LocationsEconoMi$er IV Wiring EconoMi$er IV Input/Output Logic EconoMi$erInputs Outputs Supply Air Temperature SAT Sensor Outdoor Air Lockout SensorEconoMi$er IV Control Modes Outdoor Dry Bulb ChangeoverDifferential Dry Bulb Control Outdoor Enthalpy ChangeoverIndoor Air Quality IAQ Sensor Input Exhaust Setpoint AdjustmentMinimum Position Control Thermostats Damper MovementDemand Control Ventilation DCV CO2 Sensor Standard Settings CO2 Sensor ConfigurationAnalog CO2 DCV Demand Controlled Ventilation and Power Exhaust EconoMi$er IV Sensor UsageEconoMi$er IV Preparation Differential EnthalpyWiring Diagrams EconoMi$er IV Troubleshooting CompletionDCV Minimum and Maximum Position Supply-Air Sensor Input48TC Typical Unit Wiring Diagram Power D08, 208/230-3-60 48TC Typical Unit Wiring Diagram Control D08, 208/230-3-60 PRE-START-UP START-UP, GeneralUnit Preparation Gas PipingInternal Wiring Refrigerant Service PortsReturn-Air Filters Outdoor-Air Inlet ScreensField Service Test START-UP, RTU-MP ControlVentilation Continuous Fan Perform System Check-OutConfiguration Cooling/Econ SAT Low Setpt Cooling Lockout TempHeating Heating SAT High Setpt Heating Lockout TempPower Exhaust Setpt T55/56 Override DurationIAQ Low Reference @ 4mA IAQ High Reference @ 20mAOperating Sequences Supplemental Controls PremierLinkt Control48TC 48TC Available Cooling Stages Number Stages Economizer48TC 48TC Rooftop Mode Value Linkage Mode Linkage ModesLoadshed Command Gas and Electric Heat Units Always Occupied Default OccupancyRTU-MP Sequence of Operation SchedulingBACnet Schedule BAS On/OffDI On/Off Indoor FanPower Exhaust Fastener Torque ValuesEconomizer Indoor Air QualityTorque Values Appendix I. Model Number Significance Model Number NomenclatureSerial Number Format Position Number Typical DesignatesPhysical Data Appendix II. Physical Data12.5TONS Heat Anticipator Setting Amps Physical Data Heating 12.5TONS48TC**08 48TC**12 48TC**14 Gas Connection Natural Gas Heat, Liquid Propane HeatAppendix III. FAN Performance CFM RPM BHPFAN Performance 57948TC**14 RPM BHPPulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboElectrical Information Unit Combustion Power MCA/MOCP Determination no C.O. or Unpwrd C.ONOM IFM FAN Motor Exhaust No P.E Type DISC. SizeWiring Diagrams Appendix IV. Wiring Diagram ListSize Voltage Control Power Appendix V. Motormaster Sensor Locations Catalog No 48TC-3SMUnit START-UP Checklist Preliminary Information