NOTE: The default value for the
If the limit switch trips at the start of the heating cycle during the evaporator on delay, the time period of the on delay for the next cycle will be 5 seconds less than the time at which the switch tripped. (Example: If the limit switch trips at 30 seconds, the
The
To restore the original default value, reset the power to the unit.
To shut off unit, set system selector switch at OFF position. Resetting heating selector lever below room temperature will temporarily shut unit off until space temperature falls below thermostat setting.
Ventilation (Continuous Fan)
Set fan and system selector switches at ON and OFF positions, respectively. Evaporator fan operates continuously to provide constant air circulation. When the
START-UP, PREMIERLINKt CONTROLS
Use the Carrier network communication software to start up and configure the PremierLink controller.
Changes can be made using the ComfortWORKSr software, ComfortVIEWt software, Network Service Tool, System Pilott device, or Touch Pilott device. The System Pilot and Touch Pilot are portable interface devices that allow the user to change system
NOTE: All
For specific operating instructions, refer to the literature provided with user interface software.
Perform System Check-Out
1.Check correctness and tightness of all power and communication connections.
2.At the unit, check fan and system controls for proper operation.
3.At the unit, check electrical system and connections of any optional electric reheat coil.
4.Check to be sure the area around the unit is clear of construction dirt and debris.
5.Check that final filters are installed in the unit. Dust and debris can adversely affect system operation.
6.Verify that the PremierLink controls are properly connected to the CCN bus.
Initial Operation and Test
Perform the following procedure:
1.Apply 24 vac power to the control.
2.Connect the service tool to the phone jack service port of the controller.
3.Using the Service Tool, upload the controller from address 0, 31 at 9600 baud rate. The address may be set at this time. Make sure that Service Tool is connected to only one unit when changing the address.
Memory Reset
DIP switch 4 causes an
To cause a reset of the
Refer to Rooftop PremierLink Installation,
START-UP, RTU-MP CONTROL
Field Service Test, explained below, will assist in proper
Field Service Test
The Field Service Test function can be used to verify proper operation of compressors, heating stages, indoor fan, power exhaust fans, economizer, and dehumidification. Use of Field Service Test is recommended at initial system start up and during troubleshooting. See
48TC
71