Table 29 – EconoMi$er IV Sensor Usage
| ECONOMI$ER IV WITH OUTDOOR AIR DRY | |||
APPLICATION | BULB SENSOR | |||
| Accessories Required | |||
Outdoor Air | None. The outdoor air dry bulb sensor is | |||
Dry Bulb | factory installed. | |||
Differential | CRTEMPSN002A00* | |||
Dry Bulb | ||||
|
|
| ||
Single Enthalpy | HH57AC078 | |||
Differential | HH57AC078 and CRENTDIF004A00* | |||
Enthalpy | ||||
|
|
| ||
CO2 for DCV |
|
|
| |
Control using a | 33ZCSENCO2 | |||
|
|
| ||
CO2 Sensor |
|
|
| |
CO2 for DCV | 33ZCSENCO2† and | O |
| |
Control using a | CRCBDIOX005A00†† | |||
33ZCASPCO2** | R | |||
CO2 Sensor |
|
|
|
*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many different base units. As such, these kits may contain parts that will not be needed for installation.
† 33ZCSENCO2 is an accessory CO2 sensor.
**33ZCASPCO2 is an accessory aspirator box required for
††CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and 33ZCASPCO2 accessories.
3.Use the Up/Down button to select the preset number. (See Table 28.)
4.Press Enter to lock in the selection.
5.Press Mode to exit and resume normal operation.
The custom settings of the CO2 sensor can be changed anytime after the sensor is energized. Follow the steps below to change the
1.Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.
2.Press Mode twice. The STDSET Menu will appear.
3.Use the Up/Down button to toggle to the NONSTD menu and press Enter.
4.Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.
5.Press Mode to move through the variables.
6.Press Enter to lock in the selection, then press Mode to continue to the next variable.
Dehumidification of Fresh Air with DCV (Demand Controlled Ventilation) Control
If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level, an energy recovery unit and/or a dehumidification option should be considered.
EconoMi$er IV Preparation
This procedure is used to prepare the EconoMi$er IV for troubleshooting. No troubleshooting or testing is done by performing the following procedure.
NOTE: This procedure requires a
IMPORTANT: Be sure to record the positions of all potentiometers before starting troubleshooting.
1.Disconnect power at TR and TR1. All LEDs should be off. Exhaust fan contacts should be open.
2.Disconnect device at P and P1.
3.Jumper P to P1.
4.Disconnect wires at T and T1. Place 5.6
5.Jumper TR to 1.
6.Jumper TR to N.
7.If connected, remove sensor from terminals SO and +. Connect 1.2
8.Put
9.Set minimum position, DCV setpoint, and exhaust potentiometers fully CCW (counterclockwise).
10.Set DCV maximum position potentiometer fully CW (clockwise).
11.Set enthalpy potentiometer to D.
12.Apply power (24 vac) to terminals TR and TR1.
Differential Enthalpy
To check differential enthalpy:
1.Make sure EconoMi$er IV preparation procedure has been performed.
2.Place
3.Place 1.2
4.Remove
5.Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
Single Enthalpy
To check single enthalpy:
1.Make sure EconoMi$er IV preparation procedure has been performed.
2.Set the enthalpy potentiometer to A (fully CCW). The Free Cool LED should be lit.
3.Set the enthalpy potentiometer to D (fully CW). The Free Cool LED should turn off.
4.Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
DCV (Demand Controlled Ventilation) and Power Exhaust
To check DCV and Power Exhaust:
1.Make sure EconoMi$er IV preparation procedure has been performed.
2.Ensure terminals AQ and AQ1 are open. The LED for both DCV and Exhaust should be off. The actuator should be fully closed.
3.Connect a
4.Turn the Exhaust potentiometer CW until the Exhaust LED turns off. The LED should turn off when the potentiometer is approximately 90%. The actuator should remain in position.
48TC
65