Carrier 48TC*D08 appendix Indoor CO2 Sensor 33ZCSENCO2 Connections

Page 42

The CO2 sensors are all factory set for a range of 0 to 2000 ppm and a linear mA output of 4 to 20. Refer to the instructions supplied with the CO2 sensor for electrical requirements and terminal locations. See Fig. 51 for typical CO2 sensor wiring schematic.

48TC

C07134

Fig. 51 - Indoor/Outdoor Air Quality (CO2) Sensor

(33ZCSENCO2) - Typical Wiring Diagram

To accurately monitor the quality of the air in the conditioned air space, locate the sensor near a return-air grille (if present) so it senses the concentration of CO2 leaving the space. The sensor should be mounted in a location to avoid direct breath contact.

Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft (0.9 m) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream.

Wiring the Indoor Air Quality Sensor —

For each sensor, use two 2-conductor 18 AWG (American Wire Gage) twisted-pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the control board terminals.

To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 51. Connect the 4-20 mA terminal to terminal TB1-9 and connect the SIG COM terminal to terminal TB1-11. See Fig. 52.

C09155

Fig. 52 - Indoor CO2 Sensor (33ZCSENCO2)

Connections

Refer to the Rooftop PremierLink Installation, Start-Up, and Configuration Instructions (Form 33CS-58SI), PremierLink Installation, Start-up, and Configuration Instructions, for detailed configuration information

Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus weatherproof enclosure) — The outdoor air CO2 sensor is designed to monitor carbon dioxide (CO2) levels in the outside ventilation air and interface with the ventilation damper in an HVAC system. The OAQ sensor is packaged with an outdoor cover. See Fig. 53. The outdoor air CO2 sensor must be located in the economizer outside air hood.

COVER REMOVED

SIDE VIEW

C07135

Fig. 53 - Outdoor Air Quality Sensor Cover

Wiring the Outdoor Air CO2 Sensor — A dedicated power supply is required for this sensor. A two-wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2.

To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the OAQ sensor. See Fig. 51. Connect the 4 to 20 mA terminal to 48TC’s terminal TB1-13. Connect the SIG COM terminal to 48TC’s terminal TB1-11. See Fig. 54.

OAQ Sensor/RH Sensor

TB1PL SEN 13 J5-2

TB1

COM 11 J5-3

24 VAC

C08275

Fig. 54 - Outdoor CO2 Sensor Connections

42

Image 42
Contents Table of Contents Safety ConsiderationsUnit Arrangement and Access GeneralWhat to do if you smell gas Routine Maintenance Seasonal MaintenanceSupply FAN Blower Section Supply Fan Belt-DriveManual Outside Air Hood Screen Adjustable-Pitch Pulley on Motor Supply-Fan Pulley Adjustment BearingsCooling Coil Maintenance and Cleaning RecommendationPeriodic Clean Water Rinse Condenser CoilRoutine Cleaning of Novation Condenser Coil Surfaces Routine Cleaning of Evaporator Coil SufacesRefrigerant System Pressure Access Ports Puronr R-410A RefrigerantRefrigerant Charge Seatcore Cooling Charging Charts Cooling Charging Charts D08Cooling Charging Charts D12 Cooling Charging Charts D14 Circuit a Cooling Charging Charts D14 Circuit B Cooling Service Analysis Problem Cause RemedyTroubleshooting Cooling System Condenser-Fan Adjustment D08-D12 sizeCondenser-Fan Adjustment D14 size CompressorsConvenience Outlets Non-Powered TypeUnit-Powered Type Duty CycleSmoke Detectors Smoke Detector Locations Typical Supply Air Smoke Detector Sensor LocationCompleting Installation of Return Air Smoke Sensor Fiop Smoke Detector Wiring and ResponseController Alarm Test Sensor Alarm TestSensor Alarm Test Procedure Sensor and Controller TestsDirty Sensor Test Procedure Controller Alarm Test ProcedureDirty Controller Test Procedure To Configure the Dirty Sensor Test OperationRemote Test/Reset Station Dirty Sensor Test Detector CleaningSD-TRK4 Remote Alarm Test Procedure Dirty Sensor Test Using an SD-TRK4Troubleshooting Protective Devices Compressor ProtectionGAS Heating System Control CircuitFuel Types and Pressures Flue Gas Passageways Combustion-Air BlowerBurners and Igniters Main BurnersCleaning and Adjustment Check Unit Operation and Make Necessary AdjustmentsLimit Switch LED Error Code Description LED Indication Error Code DescriptionBurner Ignition Orifice Replacement Gas ValveIntegrated Gas Control IGC Board IGC Connections OutputsOrifice Carrier Drill Drill Size Part Number Orifice SizesAltitude Compensation ElevationHeating Service Analysis Troubleshooting Heating SystemMinimum Heating Entering Air Temperature Problem Cause RemedyIGC Board LED Alarm Codes IGCCondenser Coil Service Repairing Novation Condenser Tube LeaksReplacing Novation Condenser Coil PREMIERLINKt Control Typical PremierLinkt System Control Wiring Diagram 55 Space Temperature Sensor Wiring Temp ResistanceSpace Sensor Mode TB1 Terminal Field Connection Input SignalPremierLink Sensor Usage Thermostat Mode 56 Internal ConnectionsLctb Indoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection Recommended Cables Signal Type CCN BUS Wire CCN Plug PIN Color NumberRTU-MP Control System Color Code RecommendationsRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram Point Name Configurable InputsRTU-MP Controller Inputs and Outputs Type of I/O Connection PIN Name Numbers InputsSpace Temperature SPT Sensors RTU-MP T-55 Sensor ConnectionsRTU-MP / Indoor CO2 Sensor 33ZCSENCO2 Connections Connecting Discrete Inputs Power Exhaust outputCommunication Wiring Protocols RTU-MP Troubleshooting BACview6 Handheld Connections LEDsTroubleshooting Alarms Alarms BACnet MS/TPModule Status Report Modstat Example Manufacture Date Basic Protocol TroubleshootingModbus Code Name MeaningECONOMI$ER Systems EconoMi$er IV Component LocationsEconoMi$er IV Wiring EconoMi$er EconoMi$er IV Input/Output LogicInputs Outputs EconoMi$er IV Control Modes Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor Outdoor Dry Bulb ChangeoverDifferential Dry Bulb Control Outdoor Enthalpy ChangeoverExhaust Setpoint Adjustment Indoor Air Quality IAQ Sensor InputMinimum Position Control Damper Movement ThermostatsDemand Control Ventilation DCV CO2 Sensor Configuration CO2 Sensor Standard SettingsAnalog CO2 EconoMi$er IV Preparation DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Sensor Usage Differential EnthalpyDCV Minimum and Maximum Position Wiring DiagramsEconoMi$er IV Troubleshooting Completion Supply-Air Sensor Input48TC Typical Unit Wiring Diagram Power D08, 208/230-3-60 48TC Typical Unit Wiring Diagram Control D08, 208/230-3-60 Unit Preparation PRE-START-UPSTART-UP, General Gas PipingReturn-Air Filters Internal WiringRefrigerant Service Ports Outdoor-Air Inlet ScreensVentilation Continuous Fan Field Service TestSTART-UP, RTU-MP Control Perform System Check-OutConfiguration Heating Heating SAT High Setpt Cooling/Econ SAT Low SetptCooling Lockout Temp Heating Lockout TempIAQ Low Reference @ 4mA Power Exhaust SetptT55/56 Override Duration IAQ High Reference @ 20mAOperating Sequences Supplemental Controls PremierLinkt Control48TC 48TC Available Cooling Stages Number Stages Economizer48TC 48TC Rooftop Mode Value Linkage Mode Linkage ModesRTU-MP Sequence of Operation Loadshed Command Gas and Electric Heat UnitsAlways Occupied Default Occupancy SchedulingDI On/Off BACnet ScheduleBAS On/Off Indoor FanEconomizer Power ExhaustFastener Torque Values Indoor Air QualityTorque Values Serial Number Format Appendix I. Model Number SignificanceModel Number Nomenclature Position Number Typical DesignatesAppendix II. Physical Data Physical Data12.5TONS 48TC**08 48TC**12 48TC**14 Gas Connection Heat Anticipator Setting AmpsPhysical Data Heating 12.5TONS Natural Gas Heat, Liquid Propane HeatAppendix III. FAN Performance CFM RPM BHPFAN Performance 57948TC**14 RPM BHPPulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboElectrical Information NOM IFM FAN Motor Exhaust No P.E Unit Combustion PowerMCA/MOCP Determination no C.O. or Unpwrd C.O Type DISC. SizeAppendix IV. Wiring Diagram List Wiring DiagramsSize Voltage Control Power Appendix V. Motormaster Sensor Locations Catalog No 48TC-3SMUnit START-UP Checklist Preliminary Information