Carrier 48TC*D08 appendix

Page 77

Routine No. 2: If DXLOCK (or DX Cooling Lockout is disabled) < OAT 68_F when Y1 input is energized, the economizer will be modulated to maintain SAT at SASP = SATLO1 + 3_F. If the SAT > SASP + 5_F and the economizer position > 85% then the economizer will close the to minimum position for three minutes or until the SAT > 68_F. The economizer integrator will then be reset and begin modulating to maintain the SASP after stage one has been energized for 90 seconds.

When Y2 is energized, the economizer will be modulated to control to a lower supply air setpoint SASP= SATLO2

+3_F If the SAT > SASP + 5_F it will close the economizer to minimum position for 3 minutes, reset the integrator for the economizer, then start modulating the economizer to maintain the SASP after the stage two has been on for 90 seconds. This provides protection for the compressor against flooded starts and allow refrigerant flow to stabilize before modulating the economizer again. By using return air across the evaporator coil just after the compressor has started allows for increased refrigerant flow rates providing better oil return of any oil washed out during compressor start-up.

Routine No. 3: If the OAT > 68_F and the enthalpy is low and the OAT < SPT then the economizer will open to 100% and compressors 1 and 2 will be cycled based on Y1 and Y2 inputs respectively. If any of these conditions are not met the economizer will go to minimum position.

If there is no call for heating or cooling, the economizer, if available, will maintain the SASP at 70_F.

Heating — For gas or electric heat, HS1 and HS2 outputs will follow W1 and W2 inputs respectively. The fan will also be turned on if it is configured for electric heat.

Heating may also be energized when an IAQ sensor installed and has overridden the minimum economizer damper position. If the OAT < 55_F and an IAQ sensor is installed and the IAQ minimum position > minimum damper position causing the SAT to decrease below the SPT - 10_F, then the heat stages will be cycled to temper the SAT to maintain a temperature between the SPT and the SPT + 10_F.

Auxiliary Relay configured for Exhaust Fan — If the Auxiliary Relay is configured for exhaust fan (AUXOUT

=1) in the CONFIG configuration table and Continuous Power Exhaust (MODPE) is enable in the SERVICE configuration table then the output (HS3) will be energized whenever the G input is on. If the MODPE is disabled then output will be energized based on the Power Exhaust Setpoint (PES) in the SETPOINT table.

Indoor Air Quality — If the optional indoor air quality (IAQI) sensor is installed, the PremierLink controller will maintain indoor air quality within the space at the user-configured differential setpoint (IAQD) in the CONFIG configuration table. The setpoint is the difference between the IAQI and an optional outdoor air quality sensor (OAQ). If the OAQ is not present then a fixed value of 400 ppm is used. The actual space IAQ setpoint (IAQS) is calculated as follows:

IAQS = IAQD + OAQ (OAQ = 400 ppm if not present)

As air quality within the space changes, the minimum position of the economizer damper will be changed also thus allowing more or less outdoor air into the space depending on the relationship of the IAQI to the IAQS. The IAQ algorithm runs every 30 seconds and calculates IAQ minimum position value using a PID loop on the IAQI deviation from the IAQS. The IAQ minimum position is then compared against the user configured minimum position (MDP) and the greatest value becomes the final minimum damper position (IQMP). If the calculated IAQ Minimum Position is greater than the IAQ maximum damper position (IAQMAXP) decision in the SERVICE configuration table, then it will be clamped to IAQMAXP value.

If IAQ is configured for low priority, the positioning of the economizer damper can be overridden by comfort requirements. If the SAT < SASP -8_F and both stages of heat are on for more then 4 minutes or the SAT > SASP + 5_F and both stages of cooling on for more then 4 minutes then the IAQ minimum damper position will become 0 and the IQMP = MDP. IAQ mode will resume when the SAT > SASP -8_F in heating or the SAT < SASP + 5_F in cooling.

If the PremierLink controller is configured for 1 stage of heat and cool or is only using a single stage thermostat input, this function will not work as it requires the both Y1 and Y2 or W1 and W2 inputs to be active. In this application, it is recommended that the user configure IAQ priority for high.

If IAQ is configured for high priority and the OAT < 55_F and the SAT < (SPT -10_F), the algorithm will enable the heat stages to maintain the SAT between the SPT and the SPT + 10_F.

CCN SENSOR MODE — When the PremierLink controller is configured for CCN control, it will control the compressor, economizer and heating outputs based its own space temperature input and setpoints or those received from Linkage. An optional CO2 IAQ sensor mounted in the space or received through communications can also influence the economizer and heating outputs. The PremierLink controller does not have a hardware clock so it must have another device on the CCN communication bus broadcasting time. The controller will maintain its own time once it has received time as long as it has power and will send a request for time once a minute until it receives time when it has lost power and power is restored. The controller will control to unoccupied setpoints until it has received a valid time. The controller must have valid time in order to perform any broadcast function, follow an occupancy schedule, perform IAQ pre-occupancy purge and many other functions as well. The following sections describe the operation for the functions of the PremierLink controller.

48TC

77

Image 77
Contents Safety Considerations Table of ContentsWhat to do if you smell gas Unit Arrangement and AccessGeneral Seasonal Maintenance Routine MaintenanceManual Outside Air Hood Screen Supply FAN Blower SectionSupply Fan Belt-Drive Supply-Fan Pulley Adjustment Bearings Adjustable-Pitch Pulley on MotorPeriodic Clean Water Rinse Coil Maintenance and Cleaning RecommendationCooling Condenser CoilRoutine Cleaning of Evaporator Coil Sufaces Routine Cleaning of Novation Condenser Coil SurfacesRefrigerant Charge Refrigerant System Pressure Access PortsPuronr R-410A Refrigerant Seatcore Cooling Charging Charts D08 Cooling Charging ChartsCooling Charging Charts D12 Cooling Charging Charts D14 Circuit a Cooling Charging Charts D14 Circuit B Problem Cause Remedy Cooling Service AnalysisCondenser-Fan Adjustment D14 size Condenser-Fan Adjustment D08-D12 sizeTroubleshooting Cooling System CompressorsUnit-Powered Type Non-Powered TypeConvenience Outlets Duty CycleSmoke Detectors Typical Supply Air Smoke Detector Sensor Location Smoke Detector LocationsFiop Smoke Detector Wiring and Response Completing Installation of Return Air Smoke SensorSensor Alarm Test Procedure Sensor Alarm TestController Alarm Test Sensor and Controller TestsDirty Controller Test Procedure Controller Alarm Test ProcedureDirty Sensor Test Procedure To Configure the Dirty Sensor Test OperationSD-TRK4 Remote Alarm Test Procedure Detector CleaningRemote Test/Reset Station Dirty Sensor Test Dirty Sensor Test Using an SD-TRK4Troubleshooting Compressor Protection Protective DevicesFuel Types and Pressures GAS Heating SystemControl Circuit Combustion-Air Blower Flue Gas PassagewaysMain Burners Burners and IgnitersLimit Switch Cleaning and AdjustmentCheck Unit Operation and Make Necessary Adjustments Burner Ignition LED Error Code DescriptionLED Indication Error Code Description Gas Valve Orifice ReplacementOutputs Integrated Gas Control IGC Board IGC ConnectionsAltitude Compensation Orifice SizesOrifice Carrier Drill Drill Size Part Number ElevationMinimum Heating Entering Air Temperature Troubleshooting Heating SystemHeating Service Analysis Problem Cause RemedyIGC IGC Board LED Alarm CodesReplacing Novation Condenser Coil Condenser Coil ServiceRepairing Novation Condenser Tube Leaks PREMIERLINKt Control Typical PremierLinkt System Control Wiring Diagram Temp Resistance 55 Space Temperature Sensor WiringPremierLink Sensor Usage Space Sensor ModeTB1 Terminal Field Connection Input Signal 56 Internal Connections Thermostat ModeLctb Indoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection RTU-MP Control System Signal Type CCN BUS Wire CCN Plug PIN Color NumberRecommended Cables Color Code RecommendationsRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs Configurable InputsPoint Name Type of I/O Connection PIN Name Numbers InputsRTU-MP T-55 Sensor Connections Space Temperature SPT SensorsRTU-MP / Indoor CO2 Sensor 33ZCSENCO2 Connections Communication Wiring Protocols Connecting Discrete InputsPower Exhaust output RTU-MP Troubleshooting LEDs BACview6 Handheld ConnectionsTroubleshooting Alarms BACnet MS/TP AlarmsModule Status Report Modstat Example Modbus Basic Protocol TroubleshootingManufacture Date Code Name MeaningEconoMi$er IV Component Locations ECONOMI$ER SystemsEconoMi$er IV Wiring Inputs Outputs EconoMi$erEconoMi$er IV Input/Output Logic Outdoor Air Lockout Sensor Supply Air Temperature SAT SensorEconoMi$er IV Control Modes Outdoor Dry Bulb ChangeoverOutdoor Enthalpy Changeover Differential Dry Bulb ControlMinimum Position Control Exhaust Setpoint AdjustmentIndoor Air Quality IAQ Sensor Input Demand Control Ventilation DCV Damper MovementThermostats Analog CO2 CO2 Sensor ConfigurationCO2 Sensor Standard Settings EconoMi$er IV Sensor Usage DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Preparation Differential EnthalpyEconoMi$er IV Troubleshooting Completion Wiring DiagramsDCV Minimum and Maximum Position Supply-Air Sensor Input48TC Typical Unit Wiring Diagram Power D08, 208/230-3-60 48TC Typical Unit Wiring Diagram Control D08, 208/230-3-60 START-UP, General PRE-START-UPUnit Preparation Gas PipingRefrigerant Service Ports Internal WiringReturn-Air Filters Outdoor-Air Inlet ScreensSTART-UP, RTU-MP Control Field Service TestVentilation Continuous Fan Perform System Check-OutConfiguration Cooling Lockout Temp Cooling/Econ SAT Low SetptHeating Heating SAT High Setpt Heating Lockout Temp T55/56 Override Duration Power Exhaust Setpt IAQ Low Reference @ 4mA IAQ High Reference @ 20mAOperating Sequences PremierLinkt Control Supplemental Controls48TC 48TC Number Stages Economizer Available Cooling Stages48TC 48TC Linkage Modes Rooftop Mode Value Linkage ModeAlways Occupied Default Occupancy Loadshed Command Gas and Electric Heat UnitsRTU-MP Sequence of Operation SchedulingBAS On/Off BACnet ScheduleDI On/Off Indoor FanFastener Torque Values Power ExhaustEconomizer Indoor Air QualityTorque Values Model Number Nomenclature Appendix I. Model Number SignificanceSerial Number Format Position Number Typical Designates12.5TONS Appendix II. Physical DataPhysical Data Physical Data Heating 12.5TONS Heat Anticipator Setting Amps48TC**08 48TC**12 48TC**14 Gas Connection Natural Gas Heat, Liquid Propane HeatCFM RPM BHP Appendix III. FAN Performance579 FAN PerformanceRPM BHP 48TC**14Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentElectrical Information MCA/MOCP Determination no C.O. or Unpwrd C.O Unit Combustion PowerNOM IFM FAN Motor Exhaust No P.E Type DISC. SizeSize Voltage Control Power Appendix IV. Wiring Diagram ListWiring Diagrams Catalog No 48TC-3SM Appendix V. Motormaster Sensor LocationsPreliminary Information Unit START-UP Checklist