NOTE: See
N2
1. Verify that the BAS and controller are both set to |
speak the N2 protocol. The protocol of the controller |
is set via SW3 (switches 3, 4, 5, and 6). The protocol |
can also be verified by getting a Modstat of the |
controller through the BACview. Hit the “FN” key |
and the ’.’ key at the same time to pull up a Modstat. |
ECONOMI$ER SYSTEMS
The 48TC units may be equipped with a
Both EconoMi$ers use
Scroll to the bottom of the page and there is a section | |||
entitled | ”Network Communications.” | The | active |
protocol and baud rate will be shown in this section. | |||
2. Verify that the BAS and controller are set for 9600 | |||
baud. The baud rate of the controller is set via SW3 | |||
(switches 1 and 2). The baud rate can also be verified | |||
via the BACview by obtaining a Modstat. (See Fig. | |||
70.) |
|
|
|
3. Verify that the BAS is configured to speak | |||
to the controller. The BAS | may | have to |
WIRING HARNESS
ACTUATOR (HIDDEN)
LOW TEMPERATURE
COMPRESSOR
LOCKOUT SWITCH
OUTSIDE AIR TEMPERATURE SENSOR (OPERATING LOCATION)
ECONOMI$ER IV
CONTROLLER
48TC
| configure jumper or DIP switches on their end. |
4. | Verify that the BAS and the controller have the same |
| communication settings (8 data bits, No Parity, and 1 |
| stop bit). |
5. | Verify that the controller has a unique N2 slave |
| address on the N2 bus. The controller’s N2 slave |
| address is set by its rotary address switches. |
6. | Verify proper wiring between the BAS and the |
| controller. |
7. | Verify that the BAS is reading or writing to the proper |
| network point addresses on the controller. Download |
| the latest points list for the controller to verify. |
8. | Verify that the BAS is sending his requests to the |
| proper slave address of our controller. |
NOTE: See
C07367
Fig. 71 - EconoMi$er IV Component Locations
| OUTDOOR | |
| AIR HOOD | |
ECONOMI$ER2 | HOOD | |
PLUG | ||
SHIPPING | ||
| BRACKET |
GEAR DRIVEN
BAROMETRICDAMPER RELIEF
DAMPER
C06022
Fig. 72 - EconoMi$er2 Component Locations
57