48TC
B
D
C
F
E
A
C08246
Fig. 25 - Typical Smoke Detector System Wiring
Highlight C:
PremierLinkt and
Highlight D: On smoke alarm condition, the smoke detector NO Alarm contact will close, supplying
Highlight E: GRA lead at Smoke Alarm input on LCTB provides
PremierLink: This signal is conveyed to PremierLink FIOP’s TB1 at terminal
Using Remote Logic: Five conductors are provided for field use (see Highlight F) for additional annunciation functions.
Additional Application Data — Refer to Catalog No.
Sensor and Controller Tests
Sensor Alarm Test
The sensor alarm test checks a sensor’s ability to signal an alarm state. This test requires that you use a field provided
!CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel and authority concern.
This test places the duct detector into the alarm state. Unless part of the test, disconnect all auxiliary equipment from the controller before performing the test. If the duct detector is connected to a fire alarm system, notify the proper authorities before performing the test.
Sensor Alarm Test Procedure
1.Hold the test magnet where indicated on the side of the sensor housing for seven seconds.
2.Verify that the sensor’s Alarm LED turns on.
3.Reset the sensor by holding the test magnet against the sensor housing for two seconds.
4.Verify that the sensor’s Alarm LED turns off.
Controller Alarm Test
The controller alarm test checks the controller’s ability to initiate and indicate an alarm state.
20