Carrier 48TC*D08 Modbus, Manufacture Date, Basic Protocol Troubleshooting, Code Name Meaning

Page 56

48TC

Table 24 – Manufacture Date

When troubleshooting, you may need to know a control module’s manufacture date

Obtain the manufacture date from

Notes

 

a...

 

 

Module status report (modstat)

To obtain a modstat with BACview6:

 

1. Press Function (FN) key and hold.

 

2. Then press period (.)

 

3. Release both buttons.

 

The report shows the date under Main board hardware.

Sticker on the back of the main control

The serial numbers are unique and contain embedded information:

module board

“RMP”

--- These first three digits are unique to RTU--- MP and are used as an identifier.

”Serial No: RMPYMxxxxN”

“YM”

--- These two digits identify the last digit of the year and month (in hex, A=10/Oct)

(Bar Coded & Typed Number)

xxxx”

of manufacture. ”74” would represent a date of manufacture of ”April 2007”.

 

--- These four digits represent the sequential number of units produced for a given

 

“N”

product for the mentioned manufacturing time period.

 

--- This final digit represents the decade and toggles between ”N” and ”M” every

 

 

ten years.

Table 25 – Basic Protocol Troubleshooting

Problem

Possible cause

Corrective action

No communication with 3rd

Incorrect settings on SW1, SW2 and SW3

Verify and correct switch settings. Cycle

party vendor

 

power to RTU--- MP after changing switch

 

 

settings.

 

RS485 Port has no voltage output

Verify RTU--- MP has correct power supply

 

(check with RTU--- MP disconnected from RS485

Possible bad driver on board.

 

communication bus)

 

 

Bacnet @ 9600/19.2K --- .01 to .045vdc

Check RS485 bus for external before

 

 

reconnecting to the bus

 

Bacnet @ 38.4K --- .06 to .09vdc

Voltage, shorts or grounding

 

Bacnet @ 76.8K --- .1vdc

before reconnecting to the bus

 

Modbus @ 9600 --- 76.8K --- .124vdc

 

 

N2 @ 9600 --- .124vdc

 

 

Verify devices are daisy chained and repeaters and bias

Check 3rd party vendor RS485

 

terminators are correctly installed

communication wiring guidelines and

 

 

troubleshooting procedures

Table 26 – Modbus Exception Codes that May be

Returned From This Controller

CODE

NAME

MEANING

 

 

 

 

 

The Modbus function code used

01

Illegal Function

in the query is not supported by

 

 

the controller.

 

 

 

 

 

The register address used in the

02

Illegal Data Address

query is not supported by the

 

 

controller.

 

 

 

 

 

The Modbus Master has

 

 

attempted to write to a

04

Slave Device Failure

non--- existent register or a

 

 

read--- only register in the

 

 

controller.

 

 

 

Modbus

1.Verify that the BAS and controller are both set to speak the Modbus RTU protocol. The protocol of the controller is set via SW3 (switches 3, 4, 5, and 6). The protocol can also be verified by getting a Modstat of the controller through the BACview. Hit the ”FN” key and the ’.’ key at the same time to pull up a Modstat. Scroll to the bottom of the page and there is a section entitled “Network Communications.” The active protocol and baud rate will be shown in this section.

2.Verify that the BAS and controller are set for the same baud rate. The baud rate of the controller is set via SW3 (switches 1 and 2). The baud rate can also be verified via the BACview by obtaining a Modstat (see Fig. 70).

3.Verify that the BAS is configured to speak 2-wire EIA-485 to the controller. The BAS may have to configure jumper or DIP switches on their end.

4.Verify that the BAS and the controller have the same communication settings (8 data bits, No Parity, and 1 stop bit).

5.Verify that the controller has a unique Modbus slave address. The controller’s Modbus slave address is set by its rotary address switches.

6.Verify that the BAS is using the proper Modbus function codes to access data from our controller. Supported function codes are shown above.

7.Verify proper wiring between the BAS and the controller.

8.Verify that the BAS is reading or writing to the proper Modbus register numbers on the controller. Download the latest points list for the controller to verify.

9.Verify that the BAS is sending his requests to the proper slave address of our controller.

56

Image 56
Contents Table of Contents Safety ConsiderationsWhat to do if you smell gas Unit Arrangement and AccessGeneral Routine Maintenance Seasonal MaintenanceManual Outside Air Hood Screen Supply FAN Blower SectionSupply Fan Belt-Drive Adjustable-Pitch Pulley on Motor Supply-Fan Pulley Adjustment BearingsCoil Maintenance and Cleaning Recommendation Periodic Clean Water RinseCooling Condenser CoilRoutine Cleaning of Novation Condenser Coil Surfaces Routine Cleaning of Evaporator Coil SufacesRefrigerant Charge Refrigerant System Pressure Access PortsPuronr R-410A Refrigerant Seatcore Cooling Charging Charts Cooling Charging Charts D08Cooling Charging Charts D12 Cooling Charging Charts D14 Circuit a Cooling Charging Charts D14 Circuit B Cooling Service Analysis Problem Cause RemedyCondenser-Fan Adjustment D08-D12 size Condenser-Fan Adjustment D14 sizeTroubleshooting Cooling System CompressorsNon-Powered Type Unit-Powered TypeConvenience Outlets Duty CycleSmoke Detectors Smoke Detector Locations Typical Supply Air Smoke Detector Sensor LocationCompleting Installation of Return Air Smoke Sensor Fiop Smoke Detector Wiring and ResponseSensor Alarm Test Sensor Alarm Test ProcedureController Alarm Test Sensor and Controller TestsController Alarm Test Procedure Dirty Controller Test ProcedureDirty Sensor Test Procedure To Configure the Dirty Sensor Test OperationDetector Cleaning SD-TRK4 Remote Alarm Test ProcedureRemote Test/Reset Station Dirty Sensor Test Dirty Sensor Test Using an SD-TRK4Troubleshooting Protective Devices Compressor ProtectionFuel Types and Pressures GAS Heating SystemControl Circuit Flue Gas Passageways Combustion-Air BlowerBurners and Igniters Main BurnersLimit Switch Cleaning and AdjustmentCheck Unit Operation and Make Necessary Adjustments Burner Ignition LED Error Code DescriptionLED Indication Error Code Description Orifice Replacement Gas ValveIntegrated Gas Control IGC Board IGC Connections OutputsOrifice Sizes Altitude CompensationOrifice Carrier Drill Drill Size Part Number ElevationTroubleshooting Heating System Minimum Heating Entering Air TemperatureHeating Service Analysis Problem Cause RemedyIGC Board LED Alarm Codes IGCReplacing Novation Condenser Coil Condenser Coil ServiceRepairing Novation Condenser Tube Leaks PREMIERLINKt Control Typical PremierLinkt System Control Wiring Diagram 55 Space Temperature Sensor Wiring Temp ResistancePremierLink Sensor Usage Space Sensor ModeTB1 Terminal Field Connection Input Signal Thermostat Mode 56 Internal ConnectionsLctb Indoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection Signal Type CCN BUS Wire CCN Plug PIN Color Number RTU-MP Control SystemRecommended Cables Color Code RecommendationsRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram Configurable Inputs RTU-MP Controller Inputs and OutputsPoint Name Type of I/O Connection PIN Name Numbers InputsSpace Temperature SPT Sensors RTU-MP T-55 Sensor ConnectionsRTU-MP / Indoor CO2 Sensor 33ZCSENCO2 Connections Communication Wiring Protocols Connecting Discrete InputsPower Exhaust output RTU-MP Troubleshooting BACview6 Handheld Connections LEDsTroubleshooting Alarms Alarms BACnet MS/TPModule Status Report Modstat Example Basic Protocol Troubleshooting ModbusManufacture Date Code Name MeaningECONOMI$ER Systems EconoMi$er IV Component LocationsEconoMi$er IV Wiring Inputs Outputs EconoMi$erEconoMi$er IV Input/Output Logic Supply Air Temperature SAT Sensor Outdoor Air Lockout SensorEconoMi$er IV Control Modes Outdoor Dry Bulb ChangeoverDifferential Dry Bulb Control Outdoor Enthalpy ChangeoverMinimum Position Control Exhaust Setpoint AdjustmentIndoor Air Quality IAQ Sensor Input Demand Control Ventilation DCV Damper MovementThermostats Analog CO2 CO2 Sensor ConfigurationCO2 Sensor Standard Settings DCV Demand Controlled Ventilation and Power Exhaust EconoMi$er IV Sensor UsageEconoMi$er IV Preparation Differential EnthalpyWiring Diagrams EconoMi$er IV Troubleshooting CompletionDCV Minimum and Maximum Position Supply-Air Sensor Input48TC Typical Unit Wiring Diagram Power D08, 208/230-3-60 48TC Typical Unit Wiring Diagram Control D08, 208/230-3-60 PRE-START-UP START-UP, GeneralUnit Preparation Gas PipingInternal Wiring Refrigerant Service PortsReturn-Air Filters Outdoor-Air Inlet ScreensField Service Test START-UP, RTU-MP ControlVentilation Continuous Fan Perform System Check-OutConfiguration Cooling/Econ SAT Low Setpt Cooling Lockout TempHeating Heating SAT High Setpt Heating Lockout TempPower Exhaust Setpt T55/56 Override DurationIAQ Low Reference @ 4mA IAQ High Reference @ 20mAOperating Sequences Supplemental Controls PremierLinkt Control48TC 48TC Available Cooling Stages Number Stages Economizer48TC 48TC Rooftop Mode Value Linkage Mode Linkage ModesLoadshed Command Gas and Electric Heat Units Always Occupied Default OccupancyRTU-MP Sequence of Operation SchedulingBACnet Schedule BAS On/OffDI On/Off Indoor FanPower Exhaust Fastener Torque ValuesEconomizer Indoor Air QualityTorque Values Appendix I. Model Number Significance Model Number NomenclatureSerial Number Format Position Number Typical Designates12.5TONS Appendix II. Physical DataPhysical Data Heat Anticipator Setting Amps Physical Data Heating 12.5TONS48TC**08 48TC**12 48TC**14 Gas Connection Natural Gas Heat, Liquid Propane HeatAppendix III. FAN Performance CFM RPM BHPFAN Performance 57948TC**14 RPM BHPPulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboElectrical Information Unit Combustion Power MCA/MOCP Determination no C.O. or Unpwrd C.ONOM IFM FAN Motor Exhaust No P.E Type DISC. SizeSize Voltage Control Power Appendix IV. Wiring Diagram ListWiring Diagrams Appendix V. Motormaster Sensor Locations Catalog No 48TC-3SMUnit START-UP Checklist Preliminary Information