Carrier 48TC*D08 appendix Troubleshooting Alarms

Page 53

Table 23 – Troubleshooting Alarms

 

BACnet

ACTION TAKEN BY

RESET

 

POINT NAME

OBJECT

PROBABLE CAUSE

CONTROL

METHOD

 

NAME

 

 

 

 

 

 

 

 

 

 

 

 

Alarm Generated

 

 

Safety Chain Alarm

safety_chain

Immediate

Automatic

Over load Indoor Fan or Electric Heater overheat.

 

 

Shutdown

 

 

 

 

Alarm Generated

 

Smoke detected by smoke detector or

Fire Shutdown Alarm

fire_alarm

Immediate

Automatic

configuration incorrect

 

 

Shutdown

 

 

 

 

 

 

 

 

 

 

Space Temp Sensor

 

Alarm Generated

 

Faulty, shorted, or open thermistor caused by

spt_alarm

Immediate

Automatic

Failure

wiring error or loose connection.

 

Shutdown

 

 

 

 

 

 

 

 

 

 

 

 

Alarm Generated

 

Faulty, shorted, or open thermistor caused by

SAT Sensor Alarm

sat_alarm

Immediate

Automatic

wiring error or loose connection.

 

 

Shutdown

 

 

 

 

 

 

 

 

 

 

High Space Temp Alarm

spt_hi

Alarm Generated

Automatic

The space temperature has risen above the cool

setpoint by more than the desired amount.

 

 

 

 

Low Space Temp Alarm

spt_lo

Alarm Generated

Automatic

The space temperature has dropped below the

heat setpoint by more than the desired amount.

 

 

 

 

High Supply Air Temp

sat_hi

Alarm Generated

Automatic

SAT is greater then 160 degrees for more than 5

minutes.

 

 

 

 

Low Supply Air Temp

sat_lo

Alarm Generated

Automatic

The supply air temperature is below 35_F for

more than 5 minutes.

 

 

 

 

Supply Fan Failed to

 

Alarm Generated

 

Tripped Circuit Breaker, Broken belt, Bad indoor

sf_fail

Immediately

Automatic

fan motor, Configuration incorrect, Bad fan status

Start

 

disable Operation

 

switch.

 

 

 

 

 

 

 

 

 

 

Alarm Generated

 

 

Supply Fan in Hand

sf_hand

Ramp down

Automatic

Bad Fan Status Switch, Configuration incorrect.

 

 

Operations

 

 

Compressor Safety

dx_compstat

Alarm Generated

Automatic

Compressor would not start.

Alarm

 

 

 

 

Setpoint Slider Alarm

slide_alarm

Alarm Generated

Automatic

STO sensor is open or shorted for more then 5

Offset set to zero

seconds.

 

 

 

 

 

 

Automatic/re

 

 

 

 

set timer

 

 

 

 

when

Dirty Filter, supply fan run time exceeded, filter

Dirty Filter Alarm

filter

Alarm Generated

configured

switch configuration wrong.

 

 

 

with or

 

 

 

 

 

 

 

without

 

 

 

 

switch

 

Switch Configuration

 

Alarm Generated

Configure

More than one binary input is configured for the

 

Disable

sw_cfg_alarm

same purpose. More then one discrete input is

Alarm

misconfigured switch

correctly

 

configured to provide the same function.

 

 

functions

 

 

 

 

 

Misconfigured Analog

 

Alarm Generated

Configure

More then one analog input is configured to

an_cfg_alarm

Disable 4 selectable

Input

correctly

provide the same function.

 

analog inputs

 

 

 

 

 

 

 

 

 

 

 

Alarm Generated

 

Faulty, shorted, or open thermistor caused by

OAT Sensor Alarm

oat_alarm

Economizer and Low

Automatic

ambient DX cooling

wiring error or loose connection.

 

 

 

 

 

lockout disabled.

 

 

 

 

Alarm Generated

 

Sensor reading is out of range. Bad sensor, bad

Space RH Sensor Alarm

sprh_alarm

Dehumidification

Automatic

wiring, or sensor configured incorrectly.

 

 

disabled

 

 

 

 

 

 

 

 

 

 

Outdoor RH Sensor

oarh_alarm

Alarm Generated

Automatic

Sensor reading is out of range. Bad sensor, bad

Alarm

wiring, or sensor configured incorrectly.

 

 

 

High Space Humidity

sprh_hi

Alarm Generated

Automatic

IRH is greater then 70% for more then 10

minutes.

 

 

 

 

Low Space Humidity

sprh_lo

Alarm Generated

Automatic

IRH is less then 35% for more then 10 minutes.

 

 

Alarm Generated

 

 

 

 

Disables IAQ

 

Sensor reading is out of range. Bad sensor, bad

IAQ Sensor Alarm

iaq_alarm

Operation

Automatic

wiring, or sensor configured incorrectly.

 

 

Economizer moves

 

 

 

 

 

 

 

to minimum position

 

 

OAQ Sensor Alarm

oaq_alarm

Alarm Generated Set

Automatic

Sensor reading is out of range. Bad sensor, bad

OAQ to 400

wiring, or sensor configured incorrectly.

 

 

 

High Carbon Dioxide

co2_hi

Alarm Generated

Automatic

CO2 reading is above 1200ppm.

Level

 

 

 

 

Supply Fan Runtime

sf_rntm

Alarm Generated

clear the

Supply fan run time exceeded user defined limit.

Alarm

timer

 

 

 

Compressor 1 Runtime

dx1_rntm

Alarm Generated

clear the

Compressor run time limit is exceeded.

Alarm

timer

 

 

 

Compressor 2 Runtime

dx2_rntm

Alarm Generated

clear the

Compressor run time limit is exceeded.

Alarm

timer

 

 

 

48TC

53

Image 53
Contents Safety Considerations Table of ContentsWhat to do if you smell gas Unit Arrangement and AccessGeneral Seasonal Maintenance Routine MaintenanceManual Outside Air Hood Screen Supply FAN Blower SectionSupply Fan Belt-Drive Supply-Fan Pulley Adjustment Bearings Adjustable-Pitch Pulley on MotorPeriodic Clean Water Rinse Coil Maintenance and Cleaning RecommendationCooling Condenser CoilRoutine Cleaning of Evaporator Coil Sufaces Routine Cleaning of Novation Condenser Coil SurfacesRefrigerant Charge Refrigerant System Pressure Access PortsPuronr R-410A Refrigerant Seatcore Cooling Charging Charts D08 Cooling Charging ChartsCooling Charging Charts D12 Cooling Charging Charts D14 Circuit a Cooling Charging Charts D14 Circuit B Problem Cause Remedy Cooling Service AnalysisCondenser-Fan Adjustment D14 size Condenser-Fan Adjustment D08-D12 sizeTroubleshooting Cooling System CompressorsUnit-Powered Type Non-Powered TypeConvenience Outlets Duty CycleSmoke Detectors Typical Supply Air Smoke Detector Sensor Location Smoke Detector LocationsFiop Smoke Detector Wiring and Response Completing Installation of Return Air Smoke SensorSensor Alarm Test Procedure Sensor Alarm TestController Alarm Test Sensor and Controller TestsDirty Controller Test Procedure Controller Alarm Test ProcedureDirty Sensor Test Procedure To Configure the Dirty Sensor Test OperationSD-TRK4 Remote Alarm Test Procedure Detector CleaningRemote Test/Reset Station Dirty Sensor Test Dirty Sensor Test Using an SD-TRK4Troubleshooting Compressor Protection Protective DevicesFuel Types and Pressures GAS Heating SystemControl Circuit Combustion-Air Blower Flue Gas PassagewaysMain Burners Burners and IgnitersLimit Switch Cleaning and AdjustmentCheck Unit Operation and Make Necessary Adjustments Burner Ignition LED Error Code DescriptionLED Indication Error Code Description Gas Valve Orifice ReplacementOutputs Integrated Gas Control IGC Board IGC ConnectionsAltitude Compensation Orifice SizesOrifice Carrier Drill Drill Size Part Number ElevationMinimum Heating Entering Air Temperature Troubleshooting Heating SystemHeating Service Analysis Problem Cause RemedyIGC IGC Board LED Alarm CodesReplacing Novation Condenser Coil Condenser Coil ServiceRepairing Novation Condenser Tube Leaks PREMIERLINKt Control Typical PremierLinkt System Control Wiring Diagram Temp Resistance 55 Space Temperature Sensor WiringPremierLink Sensor Usage Space Sensor ModeTB1 Terminal Field Connection Input Signal 56 Internal Connections Thermostat ModeLctb Indoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection RTU-MP Control System Signal Type CCN BUS Wire CCN Plug PIN Color NumberRecommended Cables Color Code RecommendationsRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs Configurable InputsPoint Name Type of I/O Connection PIN Name Numbers InputsRTU-MP T-55 Sensor Connections Space Temperature SPT SensorsRTU-MP / Indoor CO2 Sensor 33ZCSENCO2 Connections Communication Wiring Protocols Connecting Discrete Inputs Power Exhaust output RTU-MP Troubleshooting LEDs BACview6 Handheld ConnectionsTroubleshooting Alarms BACnet MS/TP AlarmsModule Status Report Modstat Example Modbus Basic Protocol TroubleshootingManufacture Date Code Name MeaningEconoMi$er IV Component Locations ECONOMI$ER SystemsEconoMi$er IV Wiring Inputs Outputs EconoMi$erEconoMi$er IV Input/Output Logic Outdoor Air Lockout Sensor Supply Air Temperature SAT SensorEconoMi$er IV Control Modes Outdoor Dry Bulb ChangeoverOutdoor Enthalpy Changeover Differential Dry Bulb ControlMinimum Position Control Exhaust Setpoint AdjustmentIndoor Air Quality IAQ Sensor Input Demand Control Ventilation DCV Damper MovementThermostats Analog CO2 CO2 Sensor ConfigurationCO2 Sensor Standard Settings EconoMi$er IV Sensor Usage DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Preparation Differential EnthalpyEconoMi$er IV Troubleshooting Completion Wiring DiagramsDCV Minimum and Maximum Position Supply-Air Sensor Input48TC Typical Unit Wiring Diagram Power D08, 208/230-3-60 48TC Typical Unit Wiring Diagram Control D08, 208/230-3-60 START-UP, General PRE-START-UPUnit Preparation Gas PipingRefrigerant Service Ports Internal WiringReturn-Air Filters Outdoor-Air Inlet ScreensSTART-UP, RTU-MP Control Field Service TestVentilation Continuous Fan Perform System Check-OutConfiguration Cooling Lockout Temp Cooling/Econ SAT Low SetptHeating Heating SAT High Setpt Heating Lockout TempT55/56 Override Duration Power Exhaust SetptIAQ Low Reference @ 4mA IAQ High Reference @ 20mAOperating Sequences PremierLinkt Control Supplemental Controls48TC 48TC Number Stages Economizer Available Cooling Stages48TC 48TC Linkage Modes Rooftop Mode Value Linkage ModeAlways Occupied Default Occupancy Loadshed Command Gas and Electric Heat UnitsRTU-MP Sequence of Operation SchedulingBAS On/Off BACnet ScheduleDI On/Off Indoor FanFastener Torque Values Power ExhaustEconomizer Indoor Air QualityTorque Values Model Number Nomenclature Appendix I. Model Number SignificanceSerial Number Format Position Number Typical Designates12.5TONS Appendix II. Physical DataPhysical Data Physical Data Heating 12.5TONS Heat Anticipator Setting Amps48TC**08 48TC**12 48TC**14 Gas Connection Natural Gas Heat, Liquid Propane HeatCFM RPM BHP Appendix III. FAN Performance579 FAN PerformanceRPM BHP 48TC**14Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentElectrical Information MCA/MOCP Determination no C.O. or Unpwrd C.O Unit Combustion PowerNOM IFM FAN Motor Exhaust No P.E Type DISC. SizeSize Voltage Control Power Appendix IV. Wiring Diagram ListWiring Diagrams Catalog No 48TC-3SM Appendix V. Motormaster Sensor LocationsPreliminary Information Unit START-UP Checklist