Carrier 48TC*D08 appendix Condenser Coil Service, Repairing Novation Condenser Tube Leaks

Page 35

CONDENSER COIL SERVICE

Condenser Coil

The condenser coil is new NOVATION Heat Exchanger Technology. This is an all-aluminum construction with louvered fins over single-depth crosstubes. The crosstubes have multiple small passages through which the refrigerant passes from header to header on each end. Tubes and fins are both aluminum construction. Connection tube joints are copper. The coil may be one-row or two-row. Two-row coils are spaced apart to assist in cleaning.

Repairing NOVATION Condenser Tube Leaks

RCD offers service repair kit Part Number 50TJ660007 for repairing tube leaks in the NOVATION coil crosstubes. This kit includes approved braze materials (aluminum flux core braze rods), a heat shield, a stainless steel brush, replacement fin segments, adhesive for replacing fin segments, and instructions specific to the NOVATION aluminum coil. See EPIC for instruction sheet 99TA526379.

The repair procedure requires the use of MAPP gas and torch (must be supplied by servicer) instead of conventional oxyacetylene fuel and torch. While the flame temperature for MAPP is lower than that of oxyacetylene (and thus provides more flexibility when working on aluminum), the flame temperature is still higher than the melting temperature of aluminum, so user caution is required. Follow instructions carefully. Use the heat shield.

Replacing NOVATION Condenser Coil

The service replacement coil is preformed and is equipped

 

with transition joints with copper stub tubes. When

 

brazing the connection joints to the unit tubing, use a wet

 

cloth around the aluminum tube at the transition joint.

 

Avoid applying torch flame directly onto the aluminum

 

tubing.

48TC

 

C08199

Fig. 41 - PremierLinkt Controller

35

Image 35
Contents Safety Considerations Table of ContentsWhat to do if you smell gas Unit Arrangement and AccessGeneral Seasonal Maintenance Routine MaintenanceManual Outside Air Hood Screen Supply FAN Blower SectionSupply Fan Belt-Drive Supply-Fan Pulley Adjustment Bearings Adjustable-Pitch Pulley on MotorCondenser Coil Coil Maintenance and Cleaning RecommendationPeriodic Clean Water Rinse CoolingRoutine Cleaning of Evaporator Coil Sufaces Routine Cleaning of Novation Condenser Coil SurfacesRefrigerant Charge Refrigerant System Pressure Access PortsPuronr R-410A Refrigerant Seatcore Cooling Charging Charts D08 Cooling Charging ChartsCooling Charging Charts D12 Cooling Charging Charts D14 Circuit a Cooling Charging Charts D14 Circuit B Problem Cause Remedy Cooling Service AnalysisCompressors Condenser-Fan Adjustment D08-D12 sizeCondenser-Fan Adjustment D14 size Troubleshooting Cooling SystemDuty Cycle Non-Powered TypeUnit-Powered Type Convenience OutletsSmoke Detectors Typical Supply Air Smoke Detector Sensor Location Smoke Detector LocationsFiop Smoke Detector Wiring and Response Completing Installation of Return Air Smoke SensorSensor and Controller Tests Sensor Alarm TestSensor Alarm Test Procedure Controller Alarm TestTo Configure the Dirty Sensor Test Operation Controller Alarm Test ProcedureDirty Controller Test Procedure Dirty Sensor Test ProcedureDirty Sensor Test Using an SD-TRK4 Detector CleaningSD-TRK4 Remote Alarm Test Procedure Remote Test/Reset Station Dirty Sensor TestTroubleshooting Compressor Protection Protective DevicesFuel Types and Pressures GAS Heating SystemControl Circuit Combustion-Air Blower Flue Gas PassagewaysMain Burners Burners and IgnitersLimit Switch Cleaning and AdjustmentCheck Unit Operation and Make Necessary Adjustments Burner Ignition LED Error Code DescriptionLED Indication Error Code Description Gas Valve Orifice ReplacementOutputs Integrated Gas Control IGC Board IGC ConnectionsElevation Orifice SizesAltitude Compensation Orifice Carrier Drill Drill Size Part NumberProblem Cause Remedy Troubleshooting Heating SystemMinimum Heating Entering Air Temperature Heating Service AnalysisIGC IGC Board LED Alarm CodesReplacing Novation Condenser Coil Condenser Coil ServiceRepairing Novation Condenser Tube Leaks PREMIERLINKt Control Typical PremierLinkt System Control Wiring Diagram Temp Resistance 55 Space Temperature Sensor WiringPremierLink Sensor Usage Space Sensor ModeTB1 Terminal Field Connection Input Signal 56 Internal Connections Thermostat ModeLctb Indoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection Color Code Recommendations Signal Type CCN BUS Wire CCN Plug PIN Color NumberRTU-MP Control System Recommended CablesRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram Type of I/O Connection PIN Name Numbers Inputs Configurable InputsRTU-MP Controller Inputs and Outputs Point NameRTU-MP T-55 Sensor Connections Space Temperature SPT SensorsRTU-MP / Indoor CO2 Sensor 33ZCSENCO2 Connections Communication Wiring Protocols Connecting Discrete InputsPower Exhaust output RTU-MP Troubleshooting LEDs BACview6 Handheld ConnectionsTroubleshooting Alarms BACnet MS/TP AlarmsModule Status Report Modstat Example Code Name Meaning Basic Protocol TroubleshootingModbus Manufacture DateEconoMi$er IV Component Locations ECONOMI$ER SystemsEconoMi$er IV Wiring Inputs Outputs EconoMi$erEconoMi$er IV Input/Output Logic Outdoor Dry Bulb Changeover Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor EconoMi$er IV Control ModesOutdoor Enthalpy Changeover Differential Dry Bulb ControlMinimum Position Control Exhaust Setpoint AdjustmentIndoor Air Quality IAQ Sensor Input Demand Control Ventilation DCV Damper MovementThermostats Analog CO2 CO2 Sensor ConfigurationCO2 Sensor Standard Settings Differential Enthalpy DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Sensor Usage EconoMi$er IV PreparationSupply-Air Sensor Input Wiring DiagramsEconoMi$er IV Troubleshooting Completion DCV Minimum and Maximum Position48TC Typical Unit Wiring Diagram Power D08, 208/230-3-60 48TC Typical Unit Wiring Diagram Control D08, 208/230-3-60 Gas Piping PRE-START-UPSTART-UP, General Unit PreparationOutdoor-Air Inlet Screens Internal WiringRefrigerant Service Ports Return-Air FiltersPerform System Check-Out Field Service TestSTART-UP, RTU-MP Control Ventilation Continuous FanConfiguration Heating Lockout Temp Cooling/Econ SAT Low SetptCooling Lockout Temp Heating Heating SAT High SetptIAQ High Reference @ 20mA Power Exhaust SetptT55/56 Override Duration IAQ Low Reference @ 4mAOperating Sequences PremierLinkt Control Supplemental Controls48TC 48TC Number Stages Economizer Available Cooling Stages48TC 48TC Linkage Modes Rooftop Mode Value Linkage ModeScheduling Loadshed Command Gas and Electric Heat UnitsAlways Occupied Default Occupancy RTU-MP Sequence of OperationIndoor Fan BACnet ScheduleBAS On/Off DI On/OffIndoor Air Quality Power ExhaustFastener Torque Values EconomizerTorque Values Position Number Typical Designates Appendix I. Model Number SignificanceModel Number Nomenclature Serial Number Format12.5TONS Appendix II. Physical DataPhysical Data Natural Gas Heat, Liquid Propane Heat Heat Anticipator Setting AmpsPhysical Data Heating 12.5TONS 48TC**08 48TC**12 48TC**14 Gas ConnectionCFM RPM BHP Appendix III. FAN Performance579 FAN PerformanceRPM BHP 48TC**14Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentElectrical Information Type DISC. Size Unit Combustion PowerMCA/MOCP Determination no C.O. or Unpwrd C.O NOM IFM FAN Motor Exhaust No P.ESize Voltage Control Power Appendix IV. Wiring Diagram ListWiring Diagrams Catalog No 48TC-3SM Appendix V. Motormaster Sensor LocationsPreliminary Information Unit START-UP Checklist