48TC
To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the OAQ sensor. See Fig. 51. Connect the 4 to 20 mA terminal to
OAQ Sensor/RH Sensor
SEN J4-5
COM J4-6
24 VAC
C08463
Fig. 66 - RTU-MP / Outdoor CO2 Sensor
(33ZCSENCO2) Connections
On 48TC units equipped with
The Fire Shutdown Switch configuration, MENU→Config→Inputs→input 5, identifies the normally open status of this input when there is no fire alarm.
Alarm state is reset when the smoke detector alarm condition is cleared and reset at the smoke detector in the unit.
Connecting Discrete Inputs
Filter Status
The filter status accessory is a
Fan Status
The fan status accessory is a
configured for fan status by setting MENU→Config→Inputs→input 3, 5, 8, or 9 to Fan Status and normally open (N/O) or normally closed (N/C). Input 8 or 9 is recommended for easy of installation. Refer to Fig. 60 and 61 for wire terminations at J5.
Remote Occupancy
The remote occupancy accessory is a
Also set MENU→Schedules→occupancy source to DI on/off. Input 8 or 9 is recommended for easy of installation. Refer to Fig. 60 and Table 21 for wire terminations at J5.
Power Exhaust (output)
Connect the accessory Power Exhaust contactor coil(s) per Fig. 67.
Power Exhaust
PEC | TAN |
LCTB
THERMOSTAT
GRA C
C08464
Fig. 67 - RTU-MP Power Exhaust Connections
Space Relative Humidity Sensor - The RH sensor is not used with 48TC models at this time.
Communication Wiring - Protocols
General
Protocols are the communication languages spoken by control devices. The main purpose of a protocol is to communicate information in the most efficient method possible. Different protocols exist to provide different kinds of information for different applications. In the BAS application, many different protocols are used, depending on manufacturer. Protocols do not change the function of a controller; just make the front end user different.
The
NOTE: Power must be cycled after changing the
50