Table 16 – PremierLink Sensor Usage
|
|
|
|
|
|
| |
APPLICATION | OUTDOOR AIR | RETURN AIR | OUTDOOR AIR | RETURN AIR | |||
TEMPERATURE | TEMPERATURE | ||||||
ENTHALPY SENSOR | ENTHALPY SENSOR | ||||||
|
|
| SENSOR | SENSOR | |||
|
|
|
|
| |||
|
|
|
|
| |||
Differential Dry Bulb |
| Required |
|
| |||
Temperature with | Included |
|
| ||||
PremierLink | 33ZCT55SPT | ||||||
CRTEMPSN001A00 | |||||||
(PremierLink requires | or equivalent |
|
| ||||
|
|
| |||||
|
|
|
| ||||
|
|
|
|
| |||
Single Enthalpy with | Included |
| Requires |
| |||
PremierLink |
|
| |||||
HH57AC077 | |||||||
(PremierLink requires | Not Used | ||||||
| or equivalent |
| |||||
|
|
| |||||
|
|
|
| ||||
|
|
|
|
| |||
Differential Enthalpy | Included |
| Requires | Requires | |||
with PremierLink | |||||||
HH57AC077 | HH57AC078 | ||||||
(PremierLink requires | Not Used | ||||||
| or equivalent | or equivalent | |||||
|
| ||||||
|
|
|
| ||||
|
|
|
|
|
|
| |
NOTES: |
|
|
|
|
|
| |
CO2 Sensors (Optional): |
|
|
|
| |||
33ZCSENCO2 | Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor. |
| |||||
33ZCASPCO2 | Aspirator box used for |
|
| ||||
33ZCT55CO2 | Space temperature and CO2 room sensor with override. |
|
| ||||
33ZCT56CO2 | Space temperature and CO2 room sensor with override and setpoint. |
|
Table 17 – Space Sensor Mode
|
|
|
|
|
| ||
TB1 TERMINAL |
| FIELD CONNECTION |
|
| INPUT SIGNAL | ||
| 1 |
|
|
|
| Analog (10k thermistor) | |
| 2 |
|
| RMTOCC |
|
| Discrete, 24VAC |
| 3 |
|
|
|
| Analog (10k thermistor) | |
| 4 |
|
| CMPSAFE |
|
| Discrete, 24VAC |
| 5 |
|
|
|
| Analog (10k thermistor) | |
| 6 |
|
| FSD |
|
| Discrete, 24VAC |
| 7 |
|
|
|
| Analog, 24VDC | |
| 8 |
|
| SPS |
|
| Discrete, 24VAC |
| 9 |
|
| IAQ |
|
| Analog, |
| 10 |
|
| FILTER |
|
| Discrete, 24VAC |
| 11 |
| IAQ |
|
| Analog, | |
| 12 |
|
| CCN + (RED) |
|
| Digital, , 5VDC |
| 13 |
|
| OAQ |
|
| Analog, |
| 14 |
|
| CCN Gnd (WHT) |
|
| Digital, 5VDC |
| 15 |
|
| AUX OUT(Power Exhaust) |
|
| (Output)Discrete 24VAC |
| 16 |
|
| CCN |
|
| Digital, 5VDC |
LEGEND: |
|
|
|
| FSD | Fire Shutdown | |
T55 | Space Temperature Sensor | ||||||
T56 | Space Temperature Sensor | IAQ | |||||
CCN | Carrier Comfort Network (communication bus) | OAQ | |||||
CMPSAFE | Compressor Safety |
| RH | Relative Humidity | |||
FILTER | Dirty Filter Switch |
| SFS | Supply Fan Status |
48TC