Carrier 48TC*D08 appendix BACnet Schedule, BAS On/Off, DI On/Off, Indoor Fan, Cooling

Page 84

48TC

The Holiday schedule is created to override the Daily schedule and identify a specific day and month of the year to start and stop the unit and change control to the unoccupied heating and cooling setpoints. Follow the same steps to turn on one of the twelve Holiday schedules and start and stop times. Next, select one out of the twelve months and one out of the thirty-one days of that month. The RTU-MP will now ignore the Daily schedule for the specific day and time you selected and follow the Holiday Schedule for this period.

The Override schedules primary purpose is to provide a temporary change in the occupied heating and cooling setpoints and force the unit to control to the unoccupied heating and cooling setpoints. This would occur on a set day in a particular month and last during the start and stop time configured. The Override schedule is enabled by following the same steps to create the Holiday schedule.

NOTE: Push button override is only available when running a local or BACnet Schedule.

BACnet Schedule

For use with a Building Automation System that supports native BACnet scheduling is scheduling the unit. With the Occupancy Source set to BACnet schedule the BAS will control the unit through network communication and it’s own scheduling function.

BAS On/Off

The Building Automation System is scheduling the unit via an On/Off command to the BAS ON/OFF software point. The Building Automation System can be speaking BACnet, Modbus, or N2 and is writing to the BAS On/Off point in the open protocol point map.

NOTE: If the BAS supports NATIVE BACnet scheduling, then set the Occupancy Source to BACnet schedule. If the BAS is BACnet but does NOT support NATIVE BACnet scheduling, then set the Occupancy Source to BAS On/Off.

DI On/Off

Ahard-wired input on the RTU-MP will command the unit to start/stop. Inputs 3, 5, 8, and 9 on plug J5 can be hard-wired to command the unit to start/stop.

NOTE: Scheduling can either be controlled via the unit or the BAS, but NOT both.

Indoor Fan

The indoor fan will be turned on whenever any one of the following conditions is true:

SIt is in the occupied mode. This will be determined by its own internal occupancy schedule.

SWhenever there is a demand for cooling or heating in the unoccupied mode.

S Whenever the remote occupancy switch is closed during DI On/Off schedule type or if occupancy is forced occupied by the BAS during BAS On/Off schedule type.

When transitioning from unoccupied to occupied, there will be a configured time delay of 5 to 600 seconds before starting the fan. The fan will continue to run as long as compressors, heating stages, or the dehumidification relays are on when transitioning from occupied to unoccupied with the exception of Shutdown mode. If Fire Shutdown, safety chain, SAT alarm or SPT alarm are active; the fan will be shutdown immediately regardless of the occupancy state or demand.

The RTU-MP has an optional Supply Fan Status input to provide proof of airflow. If this is enabled, the point will look for a contact closure whenever the Supply Fan Relay is on. If it is not enabled then it will always be the same state as the Supply Fan Relay. The cooling, economizer, heating, dehumidification, CO2 and power exhaust routines will use this input point for fan status.

Cooling

The compressor outputs are controlled by the Cooling Control PID Loop and Cooling Stages Capacity algorithm. They will be used to calculate the desired number of stages needed to satisfy the space by comparing the Space Temperature (SPT) to the Occupied Cool Setpoint plus the T56 slider offset when occupied and the Unoccupied Cool Setpoint (UCSP) plus the T56 slider offset, if unoccupied. The economizer, if available, will be used for cooling in addition to the compressors. The following conditions must be true in order for this algorithm to run:

S Indoor Fan has been ON for at least 30 seconds.

S Heat mode is not active and the time guard between modes equals zero.

S If occupied and the SPT >(occupied cool setpoint plus the T56 slider offset).

S Space Temperature reading is available.

S If it is unoccupied and the SPT > (unoccupied cool setpoint plus the T56 slider offset). The indoor fan will be turned on by the staging algorithm.

S If economizer is available and active and economizer open > 85% and SAT > (SAT low limit + 5_F) and SPT > effective setpoint + 0.5_F.

OR

Economizer is available, but not active

OR Economizer is not available

S OAT > DX Lockout temperature.

If all of the above conditions are met, the compressors will be energized as required, otherwise they will be de-energized.

There is a fixed 3-minute minimum on time and a 5-minute off time for each compressor output and a 3-minute minimum time delay between staging up or down.

Any time the compressors are running the RTU-MP will stage down the compressors if the SAT becomes less than the cooling low supply air setpoint.

After a compressor is staged off, it may be started again after a normal time-guard period and the supply air temperature has increased above the low supply air setpoint.

84

Image 84
Contents Table of Contents Safety ConsiderationsUnit Arrangement and Access GeneralWhat to do if you smell gas Routine Maintenance Seasonal MaintenanceSupply FAN Blower Section Supply Fan Belt-DriveManual Outside Air Hood Screen Adjustable-Pitch Pulley on Motor Supply-Fan Pulley Adjustment BearingsCoil Maintenance and Cleaning Recommendation Periodic Clean Water RinseCooling Condenser CoilRoutine Cleaning of Novation Condenser Coil Surfaces Routine Cleaning of Evaporator Coil SufacesRefrigerant System Pressure Access Ports Puronr R-410A RefrigerantRefrigerant Charge Seatcore Cooling Charging Charts Cooling Charging Charts D08Cooling Charging Charts D12 Cooling Charging Charts D14 Circuit a Cooling Charging Charts D14 Circuit B Cooling Service Analysis Problem Cause RemedyCondenser-Fan Adjustment D08-D12 size Condenser-Fan Adjustment D14 sizeTroubleshooting Cooling System CompressorsNon-Powered Type Unit-Powered TypeConvenience Outlets Duty CycleSmoke Detectors Smoke Detector Locations Typical Supply Air Smoke Detector Sensor LocationCompleting Installation of Return Air Smoke Sensor Fiop Smoke Detector Wiring and ResponseSensor Alarm Test Sensor Alarm Test ProcedureController Alarm Test Sensor and Controller TestsController Alarm Test Procedure Dirty Controller Test ProcedureDirty Sensor Test Procedure To Configure the Dirty Sensor Test OperationDetector Cleaning SD-TRK4 Remote Alarm Test ProcedureRemote Test/Reset Station Dirty Sensor Test Dirty Sensor Test Using an SD-TRK4Troubleshooting Protective Devices Compressor ProtectionGAS Heating System Control CircuitFuel Types and Pressures Flue Gas Passageways Combustion-Air BlowerBurners and Igniters Main BurnersCleaning and Adjustment Check Unit Operation and Make Necessary AdjustmentsLimit Switch LED Error Code Description LED Indication Error Code DescriptionBurner Ignition Orifice Replacement Gas ValveIntegrated Gas Control IGC Board IGC Connections OutputsOrifice Sizes Altitude CompensationOrifice Carrier Drill Drill Size Part Number ElevationTroubleshooting Heating System Minimum Heating Entering Air TemperatureHeating Service Analysis Problem Cause RemedyIGC Board LED Alarm Codes IGCCondenser Coil Service Repairing Novation Condenser Tube LeaksReplacing Novation Condenser Coil PREMIERLINKt Control Typical PremierLinkt System Control Wiring Diagram 55 Space Temperature Sensor Wiring Temp ResistanceSpace Sensor Mode TB1 Terminal Field Connection Input SignalPremierLink Sensor Usage Thermostat Mode 56 Internal ConnectionsLctb Indoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection Signal Type CCN BUS Wire CCN Plug PIN Color Number RTU-MP Control SystemRecommended Cables Color Code RecommendationsRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram Configurable Inputs RTU-MP Controller Inputs and OutputsPoint Name Type of I/O Connection PIN Name Numbers InputsSpace Temperature SPT Sensors RTU-MP T-55 Sensor ConnectionsRTU-MP / Indoor CO2 Sensor 33ZCSENCO2 Connections Connecting Discrete Inputs Power Exhaust outputCommunication Wiring Protocols RTU-MP Troubleshooting BACview6 Handheld Connections LEDsTroubleshooting Alarms Alarms BACnet MS/TPModule Status Report Modstat Example Basic Protocol Troubleshooting ModbusManufacture Date Code Name MeaningECONOMI$ER Systems EconoMi$er IV Component LocationsEconoMi$er IV Wiring EconoMi$er EconoMi$er IV Input/Output LogicInputs Outputs Supply Air Temperature SAT Sensor Outdoor Air Lockout SensorEconoMi$er IV Control Modes Outdoor Dry Bulb ChangeoverDifferential Dry Bulb Control Outdoor Enthalpy ChangeoverExhaust Setpoint Adjustment Indoor Air Quality IAQ Sensor InputMinimum Position Control Damper Movement ThermostatsDemand Control Ventilation DCV CO2 Sensor Configuration CO2 Sensor Standard SettingsAnalog CO2 DCV Demand Controlled Ventilation and Power Exhaust EconoMi$er IV Sensor UsageEconoMi$er IV Preparation Differential EnthalpyWiring Diagrams EconoMi$er IV Troubleshooting CompletionDCV Minimum and Maximum Position Supply-Air Sensor Input48TC Typical Unit Wiring Diagram Power D08, 208/230-3-60 48TC Typical Unit Wiring Diagram Control D08, 208/230-3-60 PRE-START-UP START-UP, GeneralUnit Preparation Gas PipingInternal Wiring Refrigerant Service PortsReturn-Air Filters Outdoor-Air Inlet ScreensField Service Test START-UP, RTU-MP ControlVentilation Continuous Fan Perform System Check-OutConfiguration Cooling/Econ SAT Low Setpt Cooling Lockout TempHeating Heating SAT High Setpt Heating Lockout TempPower Exhaust Setpt T55/56 Override DurationIAQ Low Reference @ 4mA IAQ High Reference @ 20mAOperating Sequences Supplemental Controls PremierLinkt Control48TC 48TC Available Cooling Stages Number Stages Economizer48TC 48TC Rooftop Mode Value Linkage Mode Linkage ModesLoadshed Command Gas and Electric Heat Units Always Occupied Default OccupancyRTU-MP Sequence of Operation SchedulingBACnet Schedule BAS On/OffDI On/Off Indoor FanPower Exhaust Fastener Torque ValuesEconomizer Indoor Air QualityTorque Values Appendix I. Model Number Significance Model Number NomenclatureSerial Number Format Position Number Typical DesignatesAppendix II. Physical Data Physical Data12.5TONS Heat Anticipator Setting Amps Physical Data Heating 12.5TONS48TC**08 48TC**12 48TC**14 Gas Connection Natural Gas Heat, Liquid Propane HeatAppendix III. FAN Performance CFM RPM BHPFAN Performance 57948TC**14 RPM BHPPulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboElectrical Information Unit Combustion Power MCA/MOCP Determination no C.O. or Unpwrd C.ONOM IFM FAN Motor Exhaust No P.E Type DISC. SizeAppendix IV. Wiring Diagram List Wiring DiagramsSize Voltage Control Power Appendix V. Motormaster Sensor Locations Catalog No 48TC-3SMUnit START-UP Checklist Preliminary Information