Multiquip MQP60IV, MQP20IZ Mountingthe Generator SET, General Information, Vibration Isolators

Page 35

General Information

Generator set installations must be engineered so the generator set will function properly under the expected load conditions. Use these instructions as a general guide only. Follow the instructions of the consulting engineer when locating or installing any components. The complete installation must comply with all local, state, and federal building codes, fire ordinances, and other applicable regulations.

Always consider the following prior to installation:

zLevel mounting surface

zAdequate cooling air

zAdequate fresh induction air

zDischarge of radiator hot air

zDischarge of exhaust gases

zElectrical connections

zAccessibility for operation and servicing

zNoise levels

zVibration isolation

Location

The generator set location is decided mainly by related systems such as ventilation, wiring, fuel, and exhaust. The set should be located as near as possible to the main power distribution panel.

The generator set should be installed in a protected location that is guarded against vandalism, theft, and unauthorized tampering.

Always provide an optimal installation site that is away from extreme ambient temperatures and that will provide maximum protection against adverse weather conditions.

Incorrect installation or service can result in severe personal injury or death, and/or equipment damage. Only qualified service personnel should be allowed to perform electrical and mechanical component installation.

NEVER install genset over combustible materials. Locate genset such that combustible material can not accumulate under the assembly. The possibility exists of fire or explosion, causing damage to the equipment and or severe bodily harm — even death!

MOUNTINGTHE GENERATOR SET

Mounting

Mount the generator set on a substantial and level base such as a concrete pad described previously in the Foundation section. Provide properly sized mounting bolts to secure the vibration isolators to the skid using flat or bevel washers and hexagonal nuts for each bolt. (See Figure 8 below.)

The isolators should be located as shown on the genset outline drawing.

Figure 8. Bolt Diagram

Vibration Isolators

Steel spring isolators can provide up to 98% reduction in the force of vibration transmission. Locate the vibration isolator between the genset skid and foundation in accordance with the installation drawing. The installation may require 4, 6, 8, or 12 vibration isolators.

Always consult local air quality authorities before completing your

NOTE construction plans. In most instances, standby power units must be registered with the local air pollution control district.

INDUSTRIAL GENERATOR SETS — APPLICATION & INSTALLATION MANUAL — REV. #4 (09/07/07) — PAGE 35

Image 35
Contents Application & Installation Manual MQ PowerPage Heres HOW to GET Help Table of Contents Page Foryour Safety and the Safety of Others Safety Message Alert SymbolsAccidental Starting Safety Message Alert SymbolsGeneral Safety Important Safety InstructionsGeneral Safety Radiator Important Safety InstructionsAlways know the location of the nearest fire extinguisher Operation SafetyMaintenance Safety EmergenciesBattery Safety Genset should be inspected regularly for fire hazards Fire ProtectionAlways drain fuel prior to lifting Lifting the Generator SetAbout This Manual Always remember Safety FIRST!!! Safety involves twoIntroduction IntroductionApplication Application and InstallationInstallation OverviewOutdoor Locations Installation OverviewCold Climates and Derating Factors LocationGenerator Set Sizing Calculations „ Static Uninterrupted Power Supplies UPSGenset Sizing Procedure Genset SizingStep Sequence Guidelines 765.7 Repeat steps a and b as necessary through all the worksheets Running load should not be Generator Set Sizing Calculations Select a Generator SetEstablish the minimum size required Single-Phase Induction Motor Genset Sizing Determining Load CharacteristicsDetermining Load Characteristics Lighting Calculate SkVA as follows Genset Sizing Determining Load CharacteristicsThree-Phase Induction Motors 100 Determining Load CharacteristicsCalculate SkW as follows Full SkVA201 Three Phase Nema Motor Code TableEquation above Output kVA is the nameplate kVA capacity Synchronous MotorsVariable Frequency Drives Static UPSNoise Zones Peak Day Noise ConsiderationRadiator discharge air high frequency sound Noise Laws and RegulationsEnvironmental Considerations dBA Comparison Chart dBABelow estimates the noise level from multiple noise sources Adding Additional Sound SourcesDistance Effects on dBA Effects of DistanceFollowing will help reduce airborne noise Reducing NoiseFollowing will help reduce structure-borne noise See on page 32 for typical measures in reducing noiseReducing Noise Acoustic MaterialMounting on a Sub-Base Fuel Tank Access to SetMounting Mounting on a Slab FloorMounting Foundation Mounting FoundationVibration Isolators Mountingthe Generator SETGeneral Information Mounting Vibration Isolators Installation and Adjustment ProcedureSupply Tank Mechanical Installation Fuel System DieselFuel System Installation Diesel FuelMechanical Installation Fuel System Diesel Minimum Fuel Supply / Return Hose and Pipe Sizes Diesel Fuel SupplyMechanical Installation Fuel System Gaseous Fuels Gaseous Fuel Supply Mechanical Installation Fuel System Gaseous FuelsContaminants Natural GAS Schedule 40 Iron Pipe Sizing Pipe and Tube SizingTypical Pipe Schematic for Propane Vapor Distribution Liquid Propane Schedule 40 Iron Pipe Sizing Mechanical Installation Fuel SystemAdditional references include Fuel Storage RegulationsEnvironmental Protection Field Installing a Generator Exhaust System Mechanical Installation Exhaust SystemExhaust System Installation Mechanical Installation Exhaust System Condensation Trap Factory Recommended Engine Exhaust Silencers Exhaust System Installation Reference DataHow BatteriesWork Mechanical Installation Battery SystemPurpose of the Battery MQ Power BatteriesEngine Starting System Mechanical Installation Battery System„ See the Battery Safety Instructions on Preparation of Dry Charged Charged and Moist Batteries Mechanical Installation NEW BatteryNew Battery Installation Preparation of Charged and Wet BatteriesCharged and Moist Batteries Activation Mechanical Installation NEW BatteryRemoving Old Battery Dry Charged BatteriesStep Three 3 Load Procedure Battery System -TESTING BatteryBatteryTesting Step One 1 -Visual Inspection See Flow Chart, on nextBattery Testing Chart Battery System Batterytesting ChartCharging LowWater-loss Batteries Battery System Charging BatteryBattery Storage Battery System Battery Charger FC1224-10-2011U Battery Charger Battery System Battery ChargerFC & FCA Battery Charger LC1224-500-2 Battery ChargerBattery Charger Safety Battery System Battery Charger SafetyBattery Charger Installation Vents and Ducts Mechanical Installation -VENTILATION and CoolingEngine Cooling Ventilation and CoolingLouvers Mechanical Installation -VENTILATION and CoolingFactory Mounted RadiatorVentilation Mechanical Installation Mounted Radiator CoolingRadiator Set Requirements Mechanical Installation Mounted Radiator CoolingMounted Radiator Cooling System Remote Radiator Cooling optional Mechanical Installation Remote Radiator CoolingRemote Radiator Cooling Mechanical Installation Remote Radiator CoolingHot Well Installation Mechanical Installation Hotwell Cooling19,200/60x8 = 40 gpm Mechanical Installation Heat Exchanger CoolingHeat Exchanger Coolant Heaters Coolant TreatmentCoolantTreatment Electrical Installation DC Controlwiring „ Control Box Back Panel Components DC Control Wiring Control BOX Back PanelControl Box Control box contains the following „ Digital Control ModuleL3 3 PH DC Controlwiring Control BOX Back PanelGenerator Set Wire Diagram AC Electrical Connections Transfer SwitchConnection Of Generator Leads For Correct Voltage Output AC Electrical ConnectionsLine circuit breaker Electrical TerminationsMounted fuel tank is used, the electrical stub-up BreakerAC Electrical Connections System Grounding Pole ATS AC Electrical Connections System GroundingEquipment Grounding AC Electrical Connections Equipment GroundingElectrical Distribution System Electrical Distribution SystemPRE-START Preparation Run the Generator Set PRE-START PreparationAppendix Installation Checklist Appendix MAIN-LINE Circuit Breaker For MQ Power Industrial GeneratorsAppendix MAIN-LINE Circuit Breaker MQ Power Industrial Generator Specifications Appendix Generator SpecificationsAppendix Generator Specifications MQ Power Industrial Generator Specifications Appendix Engine Specifications MQP175IV MQP200IV MQP250IV Appendix Engine SpecificationsGenerator Model MQP300IV MQP350IV MQP400IV Generator Model MQP30GM MQP45GM MQP60GM MQP80GM MQP100GM Appendix Engine SpecificationsMQ Power Generator Dimensions & Weights Appendix Dimensions and WeightsMQ Power Generator Dimensions & Weights Appendix Dimensions AndweightsHeres HOW to GET Help