MECHANICAL INSTALLATION — EXHAUST SYSTEM

„Thermally insulate exhaust piping and mufflers as required to prevent burns from accidental contact, prevent activation of fire detection devices and sprinklers, reduce corrosion due to condensate, and reduce the amount of heat radiated to the generator room.

Engine exhaust manifolds and turbocharger housing, unless approved by the engine manufacturer, must never be insulated. This can result in material temperatures that can destroy the manifold and turbocharger.

„Exhaust piping must be routed at least 12 inches (305

mm)from combustible construction. Use approved thimbles where exhaust piping must pass through combustible walls or ceilings.

„Exhaust pipe (steel) expands approximately 0.0076 inches per foot of pipe for every 100°F rise in exhaust gas temperature above room temperature (1.14 mm per 100°C rise). It is recommended that flexible, corrugated stainless steel tubing be used to take up expansion in long, straight runs of pipe.

„Horizontal runs of exhaust piping should slope downwards, away from the engine, to the outdoors or to a condensation trap.

„A condensation drain trap and plug should be provided where piping turns to rise vertically. See Figure 15.

„A rain cap should be used if the exhaust outlet is vertical.

„The exhaust system must terminate outdoors at a location where engine exhaust will disperse away from buildings, animals, and building air intakes. In addition, the exhaust must not be allowed to blacken walls or windows with soot.

„It is highly recommended that the exhaust system be carried up as high as practical on the downwind side of buildings and that it is discharged straight up to maximize dispersal.

Figure 15. Condensation Trap

Some codes specify that the exhaust outlet terminate at least 10 feet (3 meters) from

NOTEthe property line, 3 feet (1 meter) from an exterior wall or roof, 10 feet from openings into buildings, and at least 10 feet above the adjoining grade.

Exhaust back pressure must not exceed the allowable back pressure of the engine. Excessive exhaust back pressure reduces engine power, engine life, and may lead to high exhaust temperatures and smoke.

Exhaust pipes are very hot and they can cause severe personal injury or death from direct contact or from fire hazard. Shield or insulate exhaust pipes if there is danger of personal contact or when routed through walls or near other combustible materials.

PAGE 48 — INDUSTRIAL GENERATOR SETS — APPLICATION & INSTALLATION MANUAL — REV. #4 (09/07/07)

Image 48
Contents MQ Power Application & Installation ManualPage Heres HOW to GET Help Table of Contents Page Safety Message Alert Symbols Foryour Safety and the Safety of OthersSafety Message Alert Symbols Accidental StartingImportant Safety Instructions General SafetyImportant Safety Instructions General Safety RadiatorOperation Safety Maintenance SafetyEmergencies Always know the location of the nearest fire extinguisherBattery Safety Fire Protection Genset should be inspected regularly for fire hazardsLifting the Generator Set Always drain fuel prior to liftingAlways remember Safety FIRST!!! Safety involves two IntroductionIntroduction About This ManualApplication and Installation InstallationOverview ApplicationInstallation Overview Cold Climates and Derating FactorsLocation Outdoor Locations„ Static Uninterrupted Power Supplies UPS Genset Sizing ProcedureGenset Sizing Generator Set Sizing CalculationsStep Sequence Guidelines 765.7 Repeat steps a and b as necessary through all the worksheets Generator Set Sizing Calculations Select a Generator Set Establish the minimum size requiredRunning load should not be Genset Sizing Determining Load Characteristics Determining Load Characteristics LightingSingle-Phase Induction Motor Genset Sizing Determining Load Characteristics Three-Phase Induction MotorsCalculate SkVA as follows Determining Load Characteristics Calculate SkW as followsFull SkVA 100Three Phase Nema Motor Code Table 201Synchronous Motors Variable Frequency DrivesStatic UPS Equation above Output kVA is the nameplate kVA capacityNoise Consideration Radiator discharge air high frequency soundNoise Laws and Regulations Noise Zones Peak DayComparison Chart dBA Environmental Considerations dBAAdding Additional Sound Sources Below estimates the noise level from multiple noise sourcesEffects of Distance Distance Effects on dBAReducing Noise Following will help reduce structure-borne noiseSee on page 32 for typical measures in reducing noise Following will help reduce airborne noiseAcoustic Material Reducing NoiseAccess to Set MountingMounting on a Slab Floor Mounting on a Sub-Base Fuel TankMounting Foundation Mounting FoundationMountingthe Generator SET General InformationVibration Isolators Installation and Adjustment Procedure Mounting Vibration IsolatorsMechanical Installation Fuel System Diesel Fuel System InstallationDiesel Fuel Supply TankMechanical Installation Fuel System Diesel Diesel Fuel Supply Minimum Fuel Supply / Return Hose and Pipe SizesMechanical Installation Fuel System Gaseous Fuels Mechanical Installation Fuel System Gaseous Fuels ContaminantsGaseous Fuel Supply Pipe and Tube Sizing Natural GAS Schedule 40 Iron Pipe SizingTypical Pipe Schematic for Propane Vapor Distribution Mechanical Installation Fuel System Liquid Propane Schedule 40 Iron Pipe SizingFuel Storage Regulations Environmental ProtectionAdditional references include Mechanical Installation Exhaust System Exhaust System InstallationField Installing a Generator Exhaust System Mechanical Installation Exhaust System Condensation Trap Exhaust System Installation Reference Data Factory Recommended Engine Exhaust SilencersMechanical Installation Battery System Purpose of the BatteryMQ Power Batteries How BatteriesWorkMechanical Installation Battery System „ See the Battery Safety Instructions onEngine Starting System Mechanical Installation NEW Battery New Battery InstallationPreparation of Charged and Wet Batteries Preparation of Dry Charged Charged and Moist BatteriesMechanical Installation NEW Battery Removing Old BatteryDry Charged Batteries Charged and Moist Batteries ActivationBattery System -TESTING Battery BatteryTestingStep One 1 -Visual Inspection See Flow Chart, on next Step Three 3 Load ProcedureBattery System Batterytesting Chart Battery Testing ChartBattery System Charging Battery Battery StorageCharging LowWater-loss Batteries Battery System Battery Charger Battery System Battery Charger FC & FCA Battery ChargerLC1224-500-2 Battery Charger FC1224-10-2011U Battery ChargerBattery System Battery Charger Safety Battery Charger InstallationBattery Charger Safety Mechanical Installation -VENTILATION and Cooling Engine CoolingVentilation and Cooling Vents and DuctsMechanical Installation -VENTILATION and Cooling LouversMechanical Installation Mounted Radiator Cooling Factory Mounted RadiatorVentilationMechanical Installation Mounted Radiator Cooling Mounted Radiator Cooling SystemRadiator Set Requirements Mechanical Installation Remote Radiator Cooling Remote Radiator Cooling optionalMechanical Installation Remote Radiator Cooling Remote Radiator CoolingMechanical Installation Hotwell Cooling Hot Well InstallationMechanical Installation Heat Exchanger Cooling Heat Exchanger19,200/60x8 = 40 gpm Coolant Treatment CoolantTreatmentCoolant Heaters Electrical Installation DC Controlwiring DC Control Wiring Control BOX Back Panel Control BoxControl box contains the following „ Digital Control Module „ Control Box Back Panel ComponentsDC Controlwiring Control BOX Back Panel L3 3 PHGenerator Set Wire Diagram Transfer Switch AC Electrical ConnectionsAC Electrical Connections Connection Of Generator Leads For Correct Voltage OutputElectrical Terminations Mounted fuel tank is used, the electrical stub-upBreaker Line circuit breakerAC Electrical Connections System Grounding AC Electrical Connections System Grounding Pole ATSAC Electrical Connections Equipment Grounding Equipment GroundingElectrical Distribution System Electrical Distribution SystemPRE-START Preparation PRE-START Preparation Run the Generator SetAppendix Installation Checklist For MQ Power Industrial Generators Appendix MAIN-LINE Circuit BreakerAppendix MAIN-LINE Circuit Breaker Appendix Generator Specifications MQ Power Industrial Generator SpecificationsAppendix Generator Specifications MQ Power Industrial Generator Specifications Appendix Engine Specifications Appendix Engine Specifications MQP175IV MQP200IV MQP250IVGenerator Model MQP300IV MQP350IV MQP400IV Appendix Engine Specifications Generator Model MQP30GM MQP45GM MQP60GM MQP80GM MQP100GMAppendix Dimensions and Weights MQ Power Generator Dimensions & WeightsAppendix Dimensions Andweights MQ Power Generator Dimensions & WeightsHeres HOW to GET Help