Multiquip MQP45GM, MQP20IZ, MQP40IZ, MQP60IV, MQP50IZ, MQP30GM Appendix Installation Checklist

Page 82

APPENDIX — INSTALLATION CHECKLIST

INSTALLATION CHECKLIST

General

‰Genset wattage capacity is sufficient to handle maximum anticipated load.

‰At least three (3) feet of clearance is provide around entire genset for servicing and ventilation.

‰Genset is located in an area not subject to flooding.

‰All operators have been thoroughly briefed on correct operating and exercise procedures.

‰All operators have been thoroughly briefed on preventive maintenance procedures.

‰All operators have read and understand all Safety Precautions and know how to react in an emergency.

Genset Support

‰Floor, roof, or earth on which the genset is mounted is strong enough and will not allow shifting or movement. Observe local codes on soil bearing capacity due to freezing and thawing.

‰Genset is properly supported and retained to approved base which is separate and independent of the surface on which it rests. Vibration isolators are installed appropriately based on size requirements.

‰Supporting base is large enough and exceeds 12 inches on all sides of genset.

‰Genset is securely fastened to foundation or subbase fuel tank.

Cooling Air Flow

‰Cooling system is efficient, properly cools the engine, and ventilates genset area.

‰Genset air inlet is faced into direction of strongest prevailing winds.

‰Air inlet openings are unrestricted and at least 1-1/2 times larger than air outlet area.

‰Cooling air outlet is on downwind side of building (if not, wind barrier is constructed).

‰Proper ducting material (sheet metal, canvas) is used between radiator and air outlet.

Diesel Fuel System

‰Fuel tanks meet or exceed all local, state, and national codes.

‰Fuel lines are properly installed, supported, and protected against damage.

‰Flexible fuel lines is installed between main fuel supply line and genset to protect against vibration, expansion, and contraction.

‰Fuel line shut-off valves are installed to prevent fuel flow in case of leaks.

‰External fuel pumps are connected and operated to be turned "on" when genset is started and turned "off" when genset is shutdown.

‰Fuel system is properly primed.

‰No fuel leaks exist in supply line or engine fuel system.

Gaseous Fuel System

‰The gas supplied to the genset is of acceptable quality.

‰The gas supply has sufficient pressure and volume to operate the genset at full load.

‰Gaseous fuel supply system design, materials, components, fabrication, testing and inspections comply with all applicable codes.

‰Proper layout and sizing of gas piping is adequate for handling the volume of gas required.

‰No leaks exist in any gas line or connection.

Exhaust System

‰Exhaust piping is not restricted by tight bends and allowed to flow at maximum velocity.

‰Condensation drain is installed at appropriate area.

‰Exhaust system is tight and leakproof.

‰Exhaust is routed safely outdoors to a well ventilated area away from people and building vents

‰Operators are thoroughly briefed on the dangers of carbon monoxide gas, preventing the buildup of this gas in inhabited areas.

‰Areas around the genset are well ventilated. No possibility of exhaust fumes entering building doors, windows, or intake fans.

‰Exhaust piping passing through walls or ceilings have approved fireproof materials and are in compliance with all codes.

‰Exhaust piping is large enough to prevent back pressure on engine.

AC and DC Wiring

‰Wire sizes, insulation, conduits, and connection methods all meet applicable codes.

‰AC and DC wires are separated in their own conduit to prevent electrical induction.

‰All load, line, and generator connections are proper and correct.

‰Genset and equipment are correctly grounded.

Genset Pre-start

‰All laws and codes are meet and all certificates received.

‰Genset engine is properly serviced with oil and coolant.

‰Batteries are properly installed, serviced, and charged.

‰Battery charger and engine coolant heater are connected and operational.

‰All genset covers and safety shields are installed properly.

‰All fuel and coolant shut-off valves are operational.

‰Fuel system is primed.

‰Operators have read the instruction manual.

PAGE 82 — INDUSTRIAL GENERATOR SETS — APPLICATION & INSTALLATION MANUAL — REV. #4 (09/07/07)

Image 82
Contents MQ Power Application & Installation ManualPage Heres HOW to GET Help Table of Contents Page Safety Message Alert Symbols Foryour Safety and the Safety of OthersSafety Message Alert Symbols Accidental StartingImportant Safety Instructions General SafetyImportant Safety Instructions General Safety RadiatorEmergencies Operation SafetyMaintenance Safety Always know the location of the nearest fire extinguisherBattery Safety Fire Protection Genset should be inspected regularly for fire hazardsLifting the Generator Set Always drain fuel prior to liftingIntroduction Always remember Safety FIRST!!! Safety involves twoIntroduction About This ManualOverview Application and InstallationInstallation ApplicationLocation Installation OverviewCold Climates and Derating Factors Outdoor LocationsGenset Sizing „ Static Uninterrupted Power Supplies UPSGenset Sizing Procedure Generator Set Sizing CalculationsStep Sequence Guidelines 765.7 Repeat steps a and b as necessary through all the worksheets Establish the minimum size required Generator Set Sizing Calculations Select a Generator SetRunning load should not be Determining Load Characteristics Lighting Genset Sizing Determining Load CharacteristicsSingle-Phase Induction Motor Three-Phase Induction Motors Genset Sizing Determining Load CharacteristicsCalculate SkVA as follows Full SkVA Determining Load CharacteristicsCalculate SkW as follows 100Three Phase Nema Motor Code Table 201Static UPS Synchronous MotorsVariable Frequency Drives Equation above Output kVA is the nameplate kVA capacityNoise Laws and Regulations Noise ConsiderationRadiator discharge air high frequency sound Noise Zones Peak DayComparison Chart dBA Environmental Considerations dBAAdding Additional Sound Sources Below estimates the noise level from multiple noise sourcesEffects of Distance Distance Effects on dBASee on page 32 for typical measures in reducing noise Reducing NoiseFollowing will help reduce structure-borne noise Following will help reduce airborne noiseAcoustic Material Reducing NoiseMounting on a Slab Floor Access to SetMounting Mounting on a Sub-Base Fuel TankMounting Foundation Mounting FoundationGeneral Information Mountingthe Generator SETVibration Isolators Installation and Adjustment Procedure Mounting Vibration IsolatorsDiesel Fuel Mechanical Installation Fuel System DieselFuel System Installation Supply TankMechanical Installation Fuel System Diesel Diesel Fuel Supply Minimum Fuel Supply / Return Hose and Pipe SizesMechanical Installation Fuel System Gaseous Fuels Contaminants Mechanical Installation Fuel System Gaseous FuelsGaseous Fuel Supply Pipe and Tube Sizing Natural GAS Schedule 40 Iron Pipe SizingTypical Pipe Schematic for Propane Vapor Distribution Mechanical Installation Fuel System Liquid Propane Schedule 40 Iron Pipe SizingEnvironmental Protection Fuel Storage RegulationsAdditional references include Exhaust System Installation Mechanical Installation Exhaust SystemField Installing a Generator Exhaust System Mechanical Installation Exhaust System Condensation Trap Exhaust System Installation Reference Data Factory Recommended Engine Exhaust SilencersMQ Power Batteries Mechanical Installation Battery SystemPurpose of the Battery How BatteriesWork„ See the Battery Safety Instructions on Mechanical Installation Battery SystemEngine Starting System Preparation of Charged and Wet Batteries Mechanical Installation NEW BatteryNew Battery Installation Preparation of Dry Charged Charged and Moist BatteriesDry Charged Batteries Mechanical Installation NEW BatteryRemoving Old Battery Charged and Moist Batteries ActivationStep One 1 -Visual Inspection See Flow Chart, on next Battery System -TESTING BatteryBatteryTesting Step Three 3 Load ProcedureBattery System Batterytesting Chart Battery Testing ChartBattery Storage Battery System Charging BatteryCharging LowWater-loss Batteries Battery System Battery Charger LC1224-500-2 Battery Charger Battery System Battery ChargerFC & FCA Battery Charger FC1224-10-2011U Battery ChargerBattery Charger Installation Battery System Battery Charger SafetyBattery Charger Safety Ventilation and Cooling Mechanical Installation -VENTILATION and CoolingEngine Cooling Vents and DuctsMechanical Installation -VENTILATION and Cooling LouversMechanical Installation Mounted Radiator Cooling Factory Mounted RadiatorVentilationMounted Radiator Cooling System Mechanical Installation Mounted Radiator CoolingRadiator Set Requirements Mechanical Installation Remote Radiator Cooling Remote Radiator Cooling optionalMechanical Installation Remote Radiator Cooling Remote Radiator CoolingMechanical Installation Hotwell Cooling Hot Well InstallationHeat Exchanger Mechanical Installation Heat Exchanger Cooling19,200/60x8 = 40 gpm CoolantTreatment Coolant TreatmentCoolant Heaters Electrical Installation DC Controlwiring Control box contains the following „ Digital Control Module DC Control Wiring Control BOX Back PanelControl Box „ Control Box Back Panel ComponentsDC Controlwiring Control BOX Back Panel L3 3 PHGenerator Set Wire Diagram Transfer Switch AC Electrical ConnectionsAC Electrical Connections Connection Of Generator Leads For Correct Voltage OutputBreaker Electrical TerminationsMounted fuel tank is used, the electrical stub-up Line circuit breakerAC Electrical Connections System Grounding AC Electrical Connections System Grounding Pole ATSAC Electrical Connections Equipment Grounding Equipment GroundingElectrical Distribution System Electrical Distribution SystemPRE-START Preparation PRE-START Preparation Run the Generator SetAppendix Installation Checklist For MQ Power Industrial Generators Appendix MAIN-LINE Circuit BreakerAppendix MAIN-LINE Circuit Breaker Appendix Generator Specifications MQ Power Industrial Generator SpecificationsAppendix Generator Specifications MQ Power Industrial Generator Specifications Appendix Engine Specifications Appendix Engine Specifications MQP175IV MQP200IV MQP250IVGenerator Model MQP300IV MQP350IV MQP400IV Appendix Engine Specifications Generator Model MQP30GM MQP45GM MQP60GM MQP80GM MQP100GMAppendix Dimensions and Weights MQ Power Generator Dimensions & WeightsAppendix Dimensions Andweights MQ Power Generator Dimensions & WeightsHeres HOW to GET Help