Multiquip MQP60GM, MQP20IZ Diesel Fuel Supply, Minimum Fuel Supply / Return Hose and Pipe Sizes

Page 39

MECHANICAL INSTALLATION — FUEL SYSTEM (DIESEL)

Diesel Fuel Supply

Consider the following when installing a diesel fuel supply system:

„Fuel supply tank construction, location, installation, venting, piping, testing, and inspection must comply with all applicable codes. In addition, see NFPA Standards No. 30 and No. 37.

„Fuel supply tanks must be adequately vented to prevent pressurization, have provisions for manually draining or pumping out water and sediment, and have at least a five percent expansion space to prevent fuel spillage when the fuel heats up and expands.

„The fuel lift pump, day tank transfer pump, or float valve seat should be protected from fuel supply tank debris by a pre-filter or sediment bowl with a 100 to 120 mesh element.

„The supply tank must hold enough fuel to run the genset for the prescribed number of hours (NFPA No. 110 Class designation) without refueling. Tank sizing calculation should be based on the hourly fuel consumption rates on the genset specification sheet.

„For emergency power systems, codes might not permit the fuel supply to be used for any other purpose, or may specify a drawdown level for other equipment that guarantees the fuel supply for emergency power use.

„The cetane rating of No. 2 heating oil is not high enough for dependable starting of diesel engines in extreme cold weather climates. Therefore, separate supply fuel tanks for emergency power and building heating systems may have to be provided.

„Approved flexible fuel hose must be used for connections at the engine to prevent damage from genset movement and vibration.

„Diesel fuel lines should be black iron pipe. Cast iron and aluminum pipe and fittings must NOT be used because they are porous and can leak.

„Galvanized fuel lines, fittings, and tanks SHOULD NOT be used because the galvanized coating reacts with the sulfuric acid that forms when the sulfur in the fuel combines with tank condensation. Such a practice would result in debris that can clog fuel pumps and filters.

„Although copper has been used for diesel fuel lines in the past, black iron pipe is preferred. Diesel fuel polymerizes (thickens) in copper tubing during long periods of standby. This can cause the fuel injectors to clog.

„Refer to the engine specification sheet for the maximum fuel inlet and return restrictions, the maximum fuel flow, and the fuel consumption. Then refer to Table 10 for the minimum hose and pipe sizes for connections to a supply tank or day tank that is relatively close to the set at approximately the same elevation. Hose and pipe size should be based on the maximum fuel flow rather than the fuel consumption (The maximum fuel flow can be twice the full-load fuel consumption). It is highly recommended that the fuel inlet and return restrictions be checked before the set is placed into service.

„Separate fuel return lines to the day tank or supply tank must be provided for each generator set in a multiple-set installation to prevent the return lines of any idle set from being pressurized. Also, a fuel return line must NOT include a shut-off device. Engine damage will occur if the engine is run when the fuel line is shut off.

„A day tank is required whenever pipe friction and/or supply tank elevation, either below the fuel pump inlet or above the fuel injectors, would cause an excessive fuel inlet or return restriction.

„For critical start applications, where gensets are paralleled or must satisfy emergency start-time requirements, it is recommended that a fuel tank or reservoir be located such that the lowest possible fuel level is not less than 6 inches (150 mm) above the fuel pump inlet. This will prevent air from accumulating in the fuel line while the genset is in standby, eliminating the period during start- up when the air has to be purged.

Table 10. Minimum Fuel Supply / Return Hose and Pipe Sizes

 

 

Fuel Supply Line

 

 

Fuel Return Line

 

Maximum

0-10 Feet

10-50 Feet

0-10 Feet

10-50 Feet

(0-3 Metres)

(3-15 Metres)

(0-3 Metres)

(3-15 Metres)

GPH

Fuel Flow

Flex

Pipe I.D.

Flex

Pipe I.D.

Flex

Pipe I.D.

Flex

Pipe I.D.

 

Hose

Inches

Hose

Inches

Hose

Inches

Hose

Inches

 

Size

(mm)

Size

(mm)

Size

(mm)

Size

(mm)

0-15

No. 6

5/16

No. 8

13/32

No. 4

3/16

No. 6

5/16

(7.9)

(10.3)

(4.8)

(7.9)

 

 

 

 

 

16-20

No. 8

13/32

No. 10

1/2

No. 4

3/16

No. 6

5/16

(10.3)

(12.7)

(4.8)

(7.9)

 

 

 

 

 

21-80

No. 10

1/2

No. 12

5/8

No. 8

13/32

No. 10

1/2

(12.7)

(15.9)

(10.3)

(12.7)

 

 

 

 

 

81-100

No. 12

5/8

No. 16

7/8

No. 8

13/32

No. 10

1/2

(15.9)

(22.3)

(10.3)

(12.7)

 

 

 

 

 

101-160

No. 16

7/8

No. 16

7/8

No. 10

1/2

No. 12

5/8

(22.3)

(22.3)

(12.7)

(15.9)

 

 

 

 

 

160<

No. 16

7/8

No. 16

7/8

No. 12

5/8

No. 12

5/8

(22.3)

(22.3)

(15.9)

(15.9)

 

 

 

 

 

Based on four straight fittings, two 90° fittings, and minimal fuel lift height

INDUSTRIAL GENERATOR SETS — APPLICATION & INSTALLATION MANUAL — REV. #4 (09/07/07) — PAGE 39

Image 39
Contents Application & Installation Manual MQ PowerPage Heres HOW to GET Help Table of Contents Page Foryour Safety and the Safety of Others Safety Message Alert SymbolsAccidental Starting Safety Message Alert SymbolsGeneral Safety Important Safety InstructionsGeneral Safety Radiator Important Safety InstructionsAlways know the location of the nearest fire extinguisher Operation SafetyMaintenance Safety EmergenciesBattery Safety Genset should be inspected regularly for fire hazards Fire ProtectionAlways drain fuel prior to lifting Lifting the Generator SetAbout This Manual Always remember Safety FIRST!!! Safety involves twoIntroduction IntroductionApplication Application and InstallationInstallation OverviewOutdoor Locations Installation OverviewCold Climates and Derating Factors LocationGenerator Set Sizing Calculations „ Static Uninterrupted Power Supplies UPSGenset Sizing Procedure Genset SizingStep Sequence Guidelines 765.7 Repeat steps a and b as necessary through all the worksheets Generator Set Sizing Calculations Select a Generator Set Establish the minimum size requiredRunning load should not be Genset Sizing Determining Load Characteristics Determining Load Characteristics LightingSingle-Phase Induction Motor Genset Sizing Determining Load Characteristics Three-Phase Induction MotorsCalculate SkVA as follows 100 Determining Load CharacteristicsCalculate SkW as follows Full SkVA201 Three Phase Nema Motor Code TableEquation above Output kVA is the nameplate kVA capacity Synchronous MotorsVariable Frequency Drives Static UPSNoise Zones Peak Day Noise ConsiderationRadiator discharge air high frequency sound Noise Laws and RegulationsEnvironmental Considerations dBA Comparison Chart dBABelow estimates the noise level from multiple noise sources Adding Additional Sound SourcesDistance Effects on dBA Effects of DistanceFollowing will help reduce airborne noise Reducing NoiseFollowing will help reduce structure-borne noise See on page 32 for typical measures in reducing noiseReducing Noise Acoustic MaterialMounting on a Sub-Base Fuel Tank Access to SetMounting Mounting on a Slab FloorMounting Foundation Mounting FoundationMountingthe Generator SET General InformationVibration Isolators Mounting Vibration Isolators Installation and Adjustment ProcedureSupply Tank Mechanical Installation Fuel System DieselFuel System Installation Diesel FuelMechanical Installation Fuel System Diesel Minimum Fuel Supply / Return Hose and Pipe Sizes Diesel Fuel SupplyMechanical Installation Fuel System Gaseous Fuels Mechanical Installation Fuel System Gaseous Fuels ContaminantsGaseous Fuel Supply Natural GAS Schedule 40 Iron Pipe Sizing Pipe and Tube SizingTypical Pipe Schematic for Propane Vapor Distribution Liquid Propane Schedule 40 Iron Pipe Sizing Mechanical Installation Fuel SystemFuel Storage Regulations Environmental ProtectionAdditional references include Mechanical Installation Exhaust System Exhaust System InstallationField Installing a Generator Exhaust System Mechanical Installation Exhaust System Condensation Trap Factory Recommended Engine Exhaust Silencers Exhaust System Installation Reference DataHow BatteriesWork Mechanical Installation Battery SystemPurpose of the Battery MQ Power BatteriesMechanical Installation Battery System „ See the Battery Safety Instructions onEngine Starting System Preparation of Dry Charged Charged and Moist Batteries Mechanical Installation NEW BatteryNew Battery Installation Preparation of Charged and Wet BatteriesCharged and Moist Batteries Activation Mechanical Installation NEW BatteryRemoving Old Battery Dry Charged BatteriesStep Three 3 Load Procedure Battery System -TESTING BatteryBatteryTesting Step One 1 -Visual Inspection See Flow Chart, on nextBattery Testing Chart Battery System Batterytesting ChartBattery System Charging Battery Battery StorageCharging LowWater-loss Batteries Battery System Battery Charger FC1224-10-2011U Battery Charger Battery System Battery ChargerFC & FCA Battery Charger LC1224-500-2 Battery ChargerBattery System Battery Charger Safety Battery Charger InstallationBattery Charger Safety Vents and Ducts Mechanical Installation -VENTILATION and CoolingEngine Cooling Ventilation and CoolingLouvers Mechanical Installation -VENTILATION and CoolingFactory Mounted RadiatorVentilation Mechanical Installation Mounted Radiator CoolingMechanical Installation Mounted Radiator Cooling Mounted Radiator Cooling SystemRadiator Set Requirements Remote Radiator Cooling optional Mechanical Installation Remote Radiator CoolingRemote Radiator Cooling Mechanical Installation Remote Radiator CoolingHot Well Installation Mechanical Installation Hotwell CoolingMechanical Installation Heat Exchanger Cooling Heat Exchanger19,200/60x8 = 40 gpm Coolant Treatment CoolantTreatmentCoolant Heaters Electrical Installation DC Controlwiring „ Control Box Back Panel Components DC Control Wiring Control BOX Back PanelControl Box Control box contains the following „ Digital Control ModuleL3 3 PH DC Controlwiring Control BOX Back PanelGenerator Set Wire Diagram AC Electrical Connections Transfer SwitchConnection Of Generator Leads For Correct Voltage Output AC Electrical ConnectionsLine circuit breaker Electrical TerminationsMounted fuel tank is used, the electrical stub-up BreakerAC Electrical Connections System Grounding Pole ATS AC Electrical Connections System GroundingEquipment Grounding AC Electrical Connections Equipment GroundingElectrical Distribution System Electrical Distribution SystemPRE-START Preparation Run the Generator Set PRE-START PreparationAppendix Installation Checklist Appendix MAIN-LINE Circuit Breaker For MQ Power Industrial GeneratorsAppendix MAIN-LINE Circuit Breaker MQ Power Industrial Generator Specifications Appendix Generator SpecificationsAppendix Generator Specifications MQ Power Industrial Generator Specifications Appendix Engine Specifications MQP175IV MQP200IV MQP250IV Appendix Engine SpecificationsGenerator Model MQP300IV MQP350IV MQP400IV Generator Model MQP30GM MQP45GM MQP60GM MQP80GM MQP100GM Appendix Engine SpecificationsMQ Power Generator Dimensions & Weights Appendix Dimensions and WeightsMQ Power Generator Dimensions & Weights Appendix Dimensions AndweightsHeres HOW to GET Help