MECHANICAL INSTALLATION —VENTILATION AND COOLING
Engine Cooling
Ventilation and Cooling
Generator Sets create considerable heat that must be removed by proper ventilation. Outdoor installations rely on natural air circulation but indoor installations need properly sized and positioned vents for adequate air flow.
Vents and Ducts
For indoor installations, locate vents so incoming air passes through the immediate area of the installation before exhausting. Install the air outlet higher than the air inlet to allow for convection air movement.
Size the vents and ducts (Figure 24) so they are large | Figure 23. Wind Barrier |
| |
enough to allow the required flow rate of air. The "free |
|
area" of ducts must be as large as the exposed area of |
|
the radiator. |
|
Wind will restrict free airflow if it blows directly into the air |
|
outlet vent. If possible, locate the outlet vent so the effects |
|
of wind are eliminated. See Figure 23. |
|
Figure 24. Wind Barrier Installation