APPENDIX — GENERATOR SPECIFICATIONS
TABLE 26. MQ POWER INDUSTRIAL GENERATOR SPECIFICATIONS (cont.)
GENERATOR | MQP250IV* | MQP300IV | MQP350IV | MQP400IV* | MQP450VO | MQP500VO | MQP550VO | MQP600VO |
|
|
|
|
|
|
|
|
|
Standby Power | 250 kW | 300 kW | 350 kW | 400 kW | 450 kW | 500 kW | 550 kW | 600 kW |
Output Rating | (312.5 kVA) | (375 kVA) | (437.5 kVA) | (500 kVA) | (562.5 kVA) | (625 kVA) | (687.5 kVA) | (750 kVA) |
Prime Power | 225 kW | 270 kW | 315 kW | 360 kW | 400 kW | 450 kW | 500 kW | 540 kW |
Output Rating | (281 kVA) | (337.5 kVA) | (394 kVA) | (450 kVA) | (500 kVA) | (562.5 kVA) | (625 kVA) | (675 kVA) |
Design |
| Synchronous, Revolving Field, |
| |||||
|
|
|
|
|
|
|
|
|
Number Of Poles |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
Generator RPM |
|
|
| 1800 |
|
|
| |
Insulation Class |
|
|
| Class H |
|
|
| |
|
|
|
|
|
|
|
|
|
Excitation System |
|
| Brushless, Shunt Excitation Design |
|
| |||
|
|
|
|
|
|
|
|
|
Armature Connection |
|
|
| Wye or Delta |
|
|
| |
|
|
|
|
|
|
|
|
|
Frequency |
|
|
| 60 Hertz |
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| Generator Output Three Phase (3Ø) |
|
|
| ||||||
Voltage Output |
|
|
|
| 208, 220, 240, 416, 440, 480 |
|
|
| ||||
|
|
|
| Broad Range Reconnectable |
|
|
| |||||
|
|
|
|
|
|
|
| |||||
Power Factor |
|
|
|
| 0.8 |
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
Amperage Output - | 867 | 1,041 |
| 1,214 |
| 1,388 |
| 1,561 |
| 1,735 | 1,908 | 2082 |
120/208VAC |
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
Amperage Output - | 752 | 902 |
| 1,052 |
| 1,203 |
| 1,353 |
| 1,503 | 1,654 | 1804 |
120/240VAC |
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
Amperage Output - | 376 | 451 |
| 526 |
| 601 |
| 677 |
| 752 | 827 | 902 |
277/480VAC |
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
Voltage Regulation |
|
|
|
| ±1.0% |
|
|
|
|
| ||
(No Load To Full Load) |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| Environmental Operation |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
Control Panel Operation |
|
|
|
|
| 0°C ~ +50°C |
|
|
| |||
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
| |
Control Panel |
|
|
|
|
|
|
|
| ||||
Storage Temperature |
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| |
Cooling System Rating |
|
|
| 104°F (40°C) With 50/50% Mixture Glycol & Water |
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
*Data for this unit is preliminary.
CONTINUED FROM PREVIOUS PAGE | CONTINUED ON NEXT PAGE |
INDUSTRIAL GENERATOR SETS — APPLICATION & INSTALLATION MANUAL — REV. #4 (09/07/07) — PAGE 87