TUMBLER ENCLOSURE CONSTRUCTION

IMPORTANT: DO NOT block the airflow at the rear of the tumbler with laundry or other articles. Doing so would prevent adequate air supply to the combustion chamber of the tumbler.

A typical tumbler enclosure is shown in Figure 2. Note that the enclosure touches the tumbler top and side panels. Also, note the minimum and maximum dimensions. Be aware that there may be local codes and ordinances which must be complied with.

WARNING

To reduce the risk of serious injury, install lockable door(s) to prevent public access to rear of tumblers.

W055

IMPORTANT: Install tumblers with sufficient clearance for servicing and operation. Refer to Figure 2.

WARNING

To reduce the risk of severe injury, clearance of tumbler cabinet from combustible construction must conform to the minimum clearances.

W056

NOTE: Shaded areas indicate adjacent structure.

 

0" CLEARANCE PERMITTED

 

 

4" (10.16 cm)

 

 

 

FOR FIRST 4" (10.16 cm)

 

 

 

MAXIMUM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24" (61 cm) MINIMUM

0" CLEARANCE

36" (91.4 cm) RECOMMENDED

FOR MAINTENANCE PURPOSES

12" (30.5 cm)

MINIMUM

CLEARANCE

PERMITTED

FOR REMAINDER

GUARD

PROVISION

FOR

MAKE-UP

AIR

T038IE3D

Minimum Recommended Clearances

Model

Top

Top

Back

Sides

 

First 4" (10.2 cm)

(Remainder)

 

 

 

 

 

 

 

28"

0" (0.0 cm)

12" (30.5 cm)

24" (61 cm)

0" (0 cm)

 

 

 

 

 

31.5"

0" (0.0 cm)

12" (30.5 cm)

24" (61 cm)

0" (0 cm)

Figure 2

M414545